PSR-...- 24DC/SSM/2X1
102759_02_en PHOENIX CONTACT 3
Safety Instructions
General Data
Permissible ambient operating temperature -20°C ... +55°C
Nominal operating mode 100% operating factor
Degree of protection according to VDE 0470-1
Housing
Connection terminal blocks
Installation location
IP40
IP20
IP54, minimum
Mounting position Any
Air and creepage distances between circuits
Basic insulation
1
According to EN 60664/VDE 0110
Impulse voltage withstand level 4 kV
1
Pollution degree 2
Surge voltage category III
Dimensions (W x H x D):
PSR-SCP- 24DC/SSM/2X1
PSR-SPP- 24DC/SSM/2X1
22.5 mm x 99 mm x 114.5 mm
22.5 mm x 112 mm x 114.5 mm
Conductor cross section 0.2 mm
2
... 2.5 mm
2
Housing material Polyamide PA, not reinforced
1
Safe isolation, increased insulation, and 6 kV between input circuit and output contact current paths.
Tests/Approvals
TÜV (German Technical Inspectorate)
UL applied for
– During operation, parts of electrical switching devices carry hazardous voltages.
– Before working on the device, disconnect the power.
– Please observe the safety regulations of electrical engineering and industrial safety and liability
associations.
Disregarding these safety regulations may result in death, serious personal injury or damage to
equipment.
– Startup, assembly, modifications, and upgrades may only be carried out by a skilled electrical
engineer.
– For emergency stop applications, the machine must be prevented from restarting automatically by
a higher-level control system.
– Protective covers must not be removed when operating electrical switching devices.
– In the event of an error, replace the device immediately.
– Repairs, especially if the housing must be opened, may only be carried out by the manufacturer or
authorized persons. Otherwise the warranty is invalidated.
The device must be operated in a closed control cabinet (according to EN 61508-6:2001, Table 01).
When operating relay modules the operator must meet the requirements for noise emission for electrical and
electronic equipment (EN 61000-6-4) on the contact side and, if required, take appropriate measures.
T
Ü
V
R
h
e
in
la
n
d
/
B
e
rlin
-B
ra
n
d
e
n
b
u
rg