MINI-PS- 12- 24DC/48DC/0.7
104349_en_00 PHOENIX CONTACT 7
8 Installation
OUT DC
DC
OK
DC
OK
VDC
-
-
--
+
+
IN DC
+
+
NC
NC
ATTENTION: Module can become
damaged
To ensure sufficient convection, we
recommend the following minimum spacing be
used between modules: 5 cm above and below
The power supply unit can be snapped onto all
DIN rails in acc. with EN 60715.
9 Installation position
107
113,5
22,5
30
129
159
OUT DC
MINI POWER
DC
OK
DC
OK
VDC
-
-
--
+
+
IN DC
+
+
-
NC NC
Mounting position: Installation depth 107 mm (+ DIN rail)
MINI-PS- 12- 24DC/48DC/0.7
104349_en_00 PHOENIX CONTACT 8
A
B
B
1
B
2
Assembly
Position the module with the DIN rail guide on the upper edge
of the DIN rail, and snap it in with a downward motion.
Removing
Pull the snap lever open with the aid of a screwdriver and slide
the module out at the lower edge of the DIN rail.
10 Input
OUT DC
D
C
O
K
DC
OK
VDC
-
-
--
+
+
IN DC
+
+
NC
NC
The 12 V DC ... 24 V DC connection is established using the
"+" and "-" screw connections.
Protection of the primary side
The device must be installed in acc. with the regulations as in
EN 60950. An internal fuse is provided for device protection.
Additional device protection is not required.
ATTENTION: Module can become
damaged
If an internal fuse is triggered, there is a device
malfunction. In this case, the device must be
inspected in the factory.
MINI-PS- 12- 24DC/48DC/0.7
104349_en_00 PHOENIX CONTACT 9
11 Output
OUT DC
DC
OK
DC
OK
VDC
-
-
--
+
+
IN DC
+
+
NC
NC
The connection is established via screw connection terminal
blocks "+" and "-" of the DC output. The output voltage can be
adjusted on the potentiometer from 30 V DC ... 56 V DC.
Protection of the secondary side
The device is electronically protected against short circuit and
idling. In the event of a malfunction, the output voltage is
limited to 60 V DC. Make sure that all output lines are
dimensioned according to the maximum output current or are
separately protected! The cables on the secondary side
should have large cross sections in order to keep the voltage
drops on the lines to a minimum.
ATTENTION: Module can become
damaged
Make sure that all output lines are dimensioned
according to the maximum output current or are
separately protected. The cables on the
secondary side must have sufficiently large
cross sections in order to keep the voltage
drops on the lines as low as possible.
12 Signaling
For function monitoring, there is the active DC OK switching output and the DC OK LED.
State 1 State 2
"DC OK" LED ON OFF
Active DC OK switching
output
U
OUT
(with reference to "–") U = 0 V (in reference to "–")
Meaning Normal operation of the power supply unit.
U
OUT
> 0.9 x UN
U
OUT
0.9 x UN
Secondary load short-circuit or overload
No mains voltage or device defective

2320021