J OVERLOAD PROTECTION
The protective function prevents damage to the load as well as to
the power supply itself due to overload. If the load current rises
above the overload set value (105% to 135% of the rated load
current), the protective function will engage, and the voltage will
be reduced. Reset is automatic, so the power supply will return to
normal operation when the overload condition is corrected.
If the output voltage falls below 70% of the rated value in an
overload condition, the low-voltage sensing circuit will engage
and shut off the output if the low voltage condition continues for
more than 5 s. In this situation, reset is not automatic. To reset
the power supply, turn off the input power for at least 30 s and
then turn it on again.
Output voltage (V)
Output current (%)
Rated voltage
Output shut off after 5 s
J INRUSH CURRENT, START UP TIME, HOLD TIME
AC input
voltage
AC input
current
Output
voltage
Input ON
Input OFF
Start up time
300 ms max.
Hold time
20 ms min.
Inrush current on input application
5
Switching Power Supply S82D
Nomenclature
11 10 9 6 4 512
1
2378
11 10 9 6 4 512
2378 1
1. DC Output Terminals: Connect load wiring.
2. Input Terminals: Connect input wiring.
3. Voltage Select Terminals: Switch the input voltage by
connecting or removing the short bar. (short circuited: 100 to
120 V; open: 200 to 240 V)
4. V. ADJ Adjustor: Use to adjust the output voltage.
5. Output LED Indicator: Lights when DC current is being
output.
6. Remote Sensing Terminals: These correct the voltage
drop in the load lines.
7. ACG Terminal: The intermediate point of the input filter.
Shorted to FG terminal for normal operation.
8. FG Terminal: Shorted to the housing, and connected to a
ground line.
9. Current Balance Terminal: Connected to the CB terminal
of another Power Supply wired in parallel.
10. Remote Control Terminals: Connected to an external
device to enable remote control of the output while the input
voltage is being applied.
11. Fan Alarm Output: Turns ON (shorted) when the speed of
the internal fan drops.
12. Output Voltage Monitoring Terminals: Take-off from the
DC output terminals. Connected to the remote sensing
terminals (+S and –S) when the remote sensing function is
not used.
Noise filter
Fuse
*
GR
FG
AC (L)
AC (N)
Input
100/200 V
Inrush current
prevention
Rectifier Rectifier
Drive
Detection
Overvoltage
detection
Low-voltage
detection
Fan alarm circuit
Remote control
circuit
Control circuit
Overload
detection
Auxiliary
power
circuit
+ V
– V
+ S
– S
CB
FAN ALM
+ RC
– RC
FAN ALM
DC Output
Remote sensing
Current balance
Fan alarm
Remote control
* Fuse capacity:
Short bar
300 W: 8 A
600 W: 15 A
J BLOCK DIAGRAM
6
Switching Power Supply S82D
O
p
eration
J REMOTE SENSING FUNCTION
This function corrects a voltage drop in the load wiring. When
using the remote sensing function, remove the short bars from
the remote sensing terminals as shown in the following diagram.
Remote sensing connection
(2-wire shielded cable)
Load
Load wiring
Remove the
short bar
Note: 1. When the voltage drop in the load wiring is large, the
overvoltage protection function might engage just from
the increase in voltage to correct the voltage drop, so
be sure to use high capacity wiring.
2. If the +S and +V terminals are left unconnected, the
high voltage protection function will engage and the
output voltage will be cut off. If the -S and -V terminals
are left unconnected, the output voltage will increase
about 5%.
J REMOTE CONTROL FUNCTION
This function allows the output voltage to be turned on and off
with an external signal (as long as the input voltage is being
applied). When using the remote control function, remove the
short bar from the remote control terminals and connect a switch
or transistor as shown in the diagram below. The remote control
circuit is insulated from input, output, and GR.
Remove the
short bar
Tr
*
*
Use a transistor with V
CE
> 20 V and I
c
> 5 mA.
Voltage level Output voltage
Low: (0.8 V max.) ON
High: (2 V min.) OFF
J FAN ALARM
When the speed of the internal fan drops, the fan alarm output
(SPST-NO) will turn ON (shorted).
Normal condition
Alarm condition