1
Switching Power Supply S82D
Switching Power Supply
S82D
High-Grade Power Supply for
Demanding Industrial Applications
D Wide range of output voltages: 5 V or 12 V.
D Selectable 85 to 132 VAC or
170 to 264 VAC input voltage.
D Equipped with overvoltage and overload protection,
remote sensing and remote control functions.
D Fan alarm signal warns of possible fan malfunction.
D For loads drawing high current, parallel connection of
two power supplies possible.
D Two pairs of output terminals simplify wiring of two
loads (300 W).
D Optional multiple output terminal available (600 W).
D 3-year warranty.
Ordering Information
J SWITCHING POWER SUPPLIES
Stock Note: Shaded models are normally stocked.
Rated input voltage
Power ratings
Output
Part number
pg
g
Voltage Current
120/240VAC 300 W
5 VDC 60 A S82D-3005
12 VDC 27 A S82D-3012
600 W
5 VDC 120 A S82D-6005
12 VDC 53 A S82D-6012
Note: For mounting brackets and other accessories, refer to the Accessories Section on the next page.
J MODEL NUMBER LEGEND
1. Power ratings
30: 300 W
60: 600 W
S82D -
12
2. Output voltage
05: 5 V
12: 12 V
24: 24 V
2
Switching Power Supply S82D
J ACCESSORIES (ORDER SEPARATELY)
Stock Note: Shaded models are normally stocked.
Item
Mounting type Applicable power supply Part number
Mounting brackets Bottom mounting
S82D-30jj
S82Y-D30B
g
g
S82D-60jj
S82Y-D60B
Side mounting
S82D-30jj
S82Y-D30S
g
S82D-60jj
S82Y-D60S
Terminal expansion bracket
S82D-60jj
S82Y-D60T
Connection kit Parallel
S82D-30jj
S82Y-D30A
S82D-60jj
S82Y-D60A
Fan
S82D-30jj
S82Y-DFAN
S82D-60jj
Specifications
Power rating 300 W 600 W
Efficiency (typical) 74% to 84% (depending on types)
Life expectancy 10 yrs. min. (used at 40°C at the rated input with a 50% load)
The life expectancy of the fan is lower.
Input
Voltage (AC only) 120 V (85 to 132 V) or 240 V (170 to 264 V) selectable
Frequency 47 to 450 Hz
Current (with rated I/O)
100-V input 8 A max. 14 A max.
()
200-V input 4 A max. 7 A max.
Leakage current (with rated I/O)
100-V input 0.5 mA max.
g( )
200-V input 1 mA max.
Inrush current (with rated I/O)
100-V input 25 A typ. 30 A typ.
()
200-V input 50 A typ. 60 A typ.
Noise filter Yes
Output
Voltage fluctuation 3% max. (combined input, load, and temperature variations)
Voltage adjustment range ±10%, adjustable with variable resistor (V.ADJ)
Ripple 2% (p-p) max.
Input variation influence 0.4% max. (85 to 132 VAC/170 to 264 VAC input, 100% load)
Load variation influence 0.8% max. (rated input, 0% to 100% load)
Temperature variation influence 0.04%/°C max. (0° to 50°C, with rated input and output)
Rise time 300 ms max. (output voltage rise to 90%, with rated input and output)
Hold time 20 ms min.
Additional functions
Overload protection 120% of rated load current (typical), inverted L drop, automatic reset (output shut off
after 5 s, reset by input reset)
Overvoltage protection 120% of rated output voltage (typical), shut-off type, reset by input reset
Fan alarm Relay output, connector SPST, 250 VAC, 1 A load resistance, but switching capacity
is 125 VA
Remote sensing Yes
Remote control Yes
Parallel connection Yes
(This table continues on the next page.)
3
Switching Power Supply S82D
Specifications Table – continued from previous page
Power rating
300 W 600 W
Characteristics
Ambient temperature
Operating See the derating curve in the Engineering Data section
p
Storage –25°C to 85°C (–13°F to 185°F)
Ambient humidity
Operating 25% to 85%
y
Storage 25% to 95%
Dielectric strength (see note below table) 2000 VAC, 50/60Hz for 1 min (between all inputs and outputs/housing)
500 VDC for 1 min (between all inputs and outputs/housing)
Insulation resistance (see note below table) 100 MΩ min. at 500 VDC (between all outputs and inputs/housing)
Vibration resistance Malfunction: 10 to 55 Hz, 0.75-mm double amplitude (approx. 4.5G) each in X, Y,
and Z directions for 2 hours.
Shock resistance Malfunction: 294 m/s
2
(30G), 3 times each in ±1X, ±1Y, and ±1Z directions
Output indicator Yes (red)
Electromagnetic interference Meets FCC class A standards
Approved standards UL 1012, CSA E.B. 1402
Weight 2.5 kg max. 4 kg max.
Note: Be sure to remove short bar attached between FC and ACG terminals before performing dielectric strength test or insulation resis-
tance test because surge absorber is connected across input lines.
Engineering Data
J DERATING CURVE
Note: The derating curve differs depending on the mounting
position of the power supply. The curve above was ob-
tained with the power supply mounted in the standard
position.
Load (%)
Ambient temperature _C
J OVERVOLTAGE PROTECTION
The protective function prevents damage to the load and to the
power supply itself (from overvoltage). The output is shut off if the
output voltage rises above about 120% of the rated voltage. The
input power must be turned off for at least 30 s. Then, turn it on
again to reset the power supply.
Output voltage (V)
Overvoltage
Approx.
20%
10%
–10%
Rated output
voltage
Variable

S82Y-D60S