D1U-W-1600-48-HB2C

D1U-W-1600-48-Hx Series
AC-DC Front End Power Supply
CPS_D1U-W-1600-48-Hx.E01 Page 1 of 5
www.murata-ps.com
www.murata-ps.com/support
For full details go to
www.murata-ps.com/rohs
SELECTION GUIDE
Part Number
Power Output
High Line AC
Power Output
Low Line AC
Main Output
Standby
Output
Airflow
D1U-W-1600-48-HC2C 1600W 1200W 48V 3.3V Back to front
D1U-W-1600-48-HA2C 1600W 1200W 48V 5V Back to front
D1U-W-1600-48-HB2C 1600W 1200W 48V 12V Back to front
D1U-W-1600-48-HC1C 1600W 1200W 48V 3.3V Front to back
D1U-W-1600-48-HA1C 1600W 1200W 48V 5V Front to back
D1U-W-1600-48-HB1C 1600W 1200W 48V 12V Front to back
INPUT CHARACTERISTICS
Parameter Conditions Min. Typ. Max. Units
Input Voltage Operating Range 90 115/230 264 Vac
Input Frequency 47 50/60 63 Hz
Turn-on Input Voltage Ramp up 78.5 86.5
Vac
Turn-off Input Voltage Ramp down 70.5 78
Maximum Input Current
Low Line AC 90Vac 15
Arms
High Line AC 180Vac 10
Inrush Current Cold start between 0-1msec 90 Apk
Power Factor
Output load >90% 95%
Output load >50% 75%
FEATURES
RoHS compliant
1600W (220Vac), 1200W (110Vac)
Output power
48V Main output, 3.3V, 5V or 12V standby
output
1U sized; dimensions 4.75"x12.00"x1.61"
17.5 Watts per cubic inch density
N+1 redundancy capable, including hot-docking
Active current sharing on main output
Over-voltage, over-current,
over-temperature protection
Internal cooling fans
I²C Bus Interface with status indicators
PRODUCT OVERVIEW
The D1U-W-1600 is a 1600 Watt, power-factor-corrected (PFC) front-end power supply for hot-swapping redun-
dant systems. The main output is 48V and standby output of either 12V, 5V or 3.3V. Packaged in 1U low profile, it is
designed to deliver reliable bulk power to servers, workstations, storage systems or any 48V distributed power archi-
tecture systems requiring high power density. The highly efficient electrical and thermal design with internal cooling
fans supports reliable operation conditions. The D1U-W-1600 is designed to auto-recover from over-temperature
faults. Status information is provided with front panel LEDs, logic signals and I
2
C management interface. Three units
can be packaged into a 19" 1U power shelf to provide up to 4.8kW of power.
To Be Discontinued*
*LAST TIME BUY: 10/1/2017. CLICK HERE FOR DISCONTINUANCE NOTICES.
D1U-W-1600-48-Hx Series
AC-DC Front End Power Supply
CPS_D1U-W-1600-48-Hx.E01 Page 2 of 5
www.murata-ps.com/support
OUTPUT VOLTAGE CHARACTERISTICS
Output
Voltage
Parameter Conditions Min. Typ. Max. Units
48V
Voltage Set Point Accuracy 48
Vdc
Line and Load Regulation 46.54 49.44
Ripple Voltage & Noise
1
20MHz Bandwidth 480 mV p-p
Output Current 2 33 A
Load Capacitance 10000 µF
3.3Vsb
Voltage Set Point Accuracy 3.3
Vdc
Line and Load Regulation 3.2 3.4
Ripple Voltage & Noise
1
20MHz Bandwidth 50 mV p-p
Operating Range 0 4.5 A
Load Capacitance 1530 µF
5Vsb
Voltage Set Point Accuracy 5
Vdc
Line and Load Regulation 4.85 5.15
Ripple Voltage & Noise
1
20MHz Bandwidth 50 mV p-p
Operating Range 0 4 A
Load Capacitance 1530 µF
12Vsb
Voltage Set Point Accuracy 12
Vdc
Line and Load Regulation 11.6 12.4
Ripple Voltage & Noise
1
20MHz Bandwidth 120 mV p-p
Operating Range 0 1.7 A
Load Capacitance 1530 µF
OUTPUT CHARACTERISTICS
Parameter Conditions Min. Typ. Max. Units
Remote Sense 240 mV
Efficiency 220Vac 90.6 %
Output Rise Monotonicity Overshoot less than 10% for all outputs, no voltage negative between 10% to 95% during ramp up
Start-up Time
AC ramp up 1.5 s
PS_On activated 150 ms
Transient Response
48V Ramp 1A/μs, 50% load step ±2700
mV
3.3Vsb Ramp 1A/μs, 50% load step ±165
5Vsb Ramp 1A/μs, 50% load step ±250
12Vsb Ramp 1A/μs, 50% load step ±600
Current sharing accuracy (up to 6 in parallel) At 100% load ±10 %
Hot Swap Transients All outputs within regulation
Hold-up Time Max. load, nominal Vin 20 ms
GENERAL CHARACTERISTICS
Parameter Conditions Min. Typ. Max. Units
Storage Temperature Range Non-condensing -40 70
°C
Operating Temperature Range 0 50
Operating Humidity Non-condensing 10 90
%
Storage Humidity 5 90
Shock 30G non operating
Sinusoidal Vibration 0.5G, 5 – 500 Hz operating
MTBF
Calculated per Bellcore at Ta=30°C 200 Khrs
Demonstrated 200 Khrs
Acoustic ISO 7779-1999 60 dB LpAm
Safety Approvals
c-CSA-us (CSA 60950-1-03/UL 60950-1, Second Edition)
TUV approval (Bauart) EN 60950-1:2001
Input Fuse
Power Supply has internal 20A/250V fast blow fuse on the AC line input
Material Flammability
UL 94V-0
Switching Frequency
90KHz for Boost PFC Converter
165KHz for Main Output Converter
200KHz for Standby Output Converter
Weight
2.1kg
1
Ripple and noise are measured with 0.1 uF of ceramic capacitance and 10 uF of tantalum capacitance on each of the power supply outputs. The output noise requirements apply
over a 0 Hz to 20 MHz bandwidth. A short coaxial cable with 50ohm scope termination is used.
D1U-W-1600-48-Hx Series
AC-DC Front End Power Supply
CPS_D1U-W-1600-48-Hx.E01 Page 3 of 5
www.murata-ps.com/support
PROTECTION CHARACTERISTICS
Output
Voltage
Parameter Conditions Min. Typ. Max. Units
Over-temperature Auto-restart 55 65 °C
48V
Over Voltage Latching 54 59 V
Over Current Latching 37 42 A
12Vsb
Over Voltage Latching 13 14 V
Over Current Latching 2.5 3 A
3.3Vsb
Over Voltage Latching 3.57 4.02 V
Over Current Latching 6.5 8 A
5Vsb
Over Voltage Latching 5.6 6 V
Over Current Latching 5 7 A
ISOLATION CHARACTERISTICS
Parameter Conditions Min. Typ. Max. Units
Insulation Safety Rating / Test Voltage
Input to Output - Reinforced 3000 Vrms
Input to Chassis - Basic 1500 Vrms
Isolation
Output to Chassis
Output to Output
Material Flammability UL 94V-0
Grounding
Main Output Return and Standby Output Return are connected internally. 100kΩ resistor parallel with 100nF
capacitor is connected between Return and power supply chassis. Main Output Return should be connected to
the System Chassis.
CONTROL SIGNALS
Status Conditions Description
LED
Off No AC input to all PS
Flashing Yellow Power Supply Failure
Flashing Green Main Output Absent
Green Power Supply Good
I
2
C Registers
Status
PS-ON, PGOOD, ACOK, PS_BAD, FANFAIL, OT Warning &
shutdown, AC Range
Output Fault 48V OV, 48V UV, 48V OC, Vsb Fail, Fan1 Fail, Fan2 Fail
48V Output 8 bit scaled output voltage
48V 8 bit scaled output current
Fan1 Monitor 8 bit scaled output current
Fan2 Monitor 8 bit scaled output current
EMISSIONS AND IMMUNITY
Characteristic Description Criteria
Harmonics IEC/EN 61000-3-2
Voltage Fluctuation and Flicker IEC/EN 61000-3-3
Emission Conducted FCC 47 CFR Parts 15/CISPR 22/EN55022 Class A, 6dB margin
Emission Radiated FCC 47 CFR Parts 15/CISPR 22/EN55022 Class A, 6dB margin
ESD IEC/EN 61000-4-2
4kV contact discharge
8kV operational air discharge
15kV non-operational air discharge
Electromagnetic Field IEC/EN 61000-4-3
Electrical Fast Transients/Burst IEC/EN 61000-4-4
Surge IEC/EN 61000-4-5 1kV/2kV, Performance Criteria B
RF Conducted Immunity IEC/EN 61000-4-6 3 Vac, 80% AM, 1kHz, Performance Criteria A
Magnetic Immunity IEC/EN 61000-4-8 3 A/m
Voltage dips, interruptions IEC/EN 61000-4-11

D1U-W-1600-48-HB2C

Mfr. #:
Manufacturer:
Description:
Rack Mount Power Supplies AC/DC 1600W 48V Main 12V Standby
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union