General Description
-
mid-trip handle available for visual identification of
fault-tripped circuit breakers
-
optional internal low voltage shunt to meter
current (single and multi-pole units are
dimensionally equivalent in depth)
-
terminal options for design flexibility in various
applications
-
multiple trip time delays for application flexibility
-
electrical and mechanical actuated auxiliary switch
options for external monitoring of circuits
-
reduced voltage drop through the circuit breaker
vs. other circuit protective devices
Number of Poles
-
1, 2, 3, 4, 5, 6
Current and Voltage Ratings
-
100 to 250 amps, 160Vdc
-
100 to 250 amps, 125/250Vdc
-
100 to 250 amps, 65Vdc
-
275 to 800 amps, 160Vdc (paralleled poles)
-
275 to 1200 amps, 65Vdc (paralleled poles)
Interrupting Capacity
-
10,000 amps, 160Vdc
-
10,000 amps, 125/250Vdc
-
100,000 amps, 65Vdc (1 amps to 800 amps)
-
10,000 amps, 160Vdc (ratings ≤1000 amps)
-
65,000 amps, 65Vdc (801 amps to 1200 amps)
Approvals
-
UL 489 Listed
-
UL 489A Listed
-
CSA Certified
-
CUL/CUR Certified
- TUV Certified
-
CCC Certified
-
AS 60947.2-2005 (equivalent to IEC 60947-2:2006+A1)
Single-pole ratings: UL489, 250 amps max at 160 Vdc, 10,000
amp interrupting capacity and 250 amps max at 65 Vdc, 65,000
amp interrupting capacity. Multi-pole ratings: UL 489A, 800
amps max at 160 Vdc, 10,000 amp interrupting capacity and
1,200 amps max at 65 Vdc, 65,000 amp interrupting capacity.
ISO-9001 Certified