AXL E IOL AI1 I M12 S
8594_en_04 PHOENIX CONTACT 4
IO-Link port supply
Typical current consumption 16.5 mA ±15% (at 24 V DC)
Current consumption max. 120 mA
Protection against polarity reversal Yes
Short-circuit protection Yes
Overload protection Yes
I/O supply voltage 24 V DC
This supply voltage is provided via the IO-Link interface of the IO-Link
master.
Sensor supply voltage 24 V DC (max. 100 mA)
This supply voltage is provided via the I/O supply voltage.
Analog input
Number of inputs 1 (current)
Connection method M12 connector, A-coded
Connection method 3-conductor
Current input signal 4 mA ... 20 mA
Input resistance current input max. 500
Resolution A/D 12 bit
Data formats IB IL, S7-compatible
Filtering None or mean-value generation over 4, 16, or 32 measured values
Precision < 0.25 % (from the measuring range final value in the nominal range)
Permissible cable length max. 30 m (shielded cable)
Error messages to the higher level control or computer system
Overrange or underrange Message in the diagnostic code (in the IBIL format)
Measured value invalid/no valid measured value present Message in the diagnostic code (in the IBIL format)
Short circuit Message in the diagnostic code (in the IBIL format)
Open circuit; goes to 0mA Message in the diagnostic code (in the IBIL format)
Module faulty Message in the diagnostic code (in the IBIL format)
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 Operation: 2g
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 Storage/transport:5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 Operation:30g, 11ms, three shocks in each space direction
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 Storage/transport:50g, 11ms, three shocks in each space direction
Continuous shock according to EN60068-2-27/IEC60068-2-27 10g,16ms, 1000shocks, in all space directions
Approvals
For the latest approvals, please visit phoenixcontact.net/products.
AXL E IOL AI1 I M12 S
8594_en_04 PHOENIX CONTACT 5
5 Additional tables
The data is valid for nominal operation
(supply voltage=24V) in the default configuration
(measurement range 4 mA ... 20 mA).
The tolerance values refer to the measuring range final
value.
6 Internal circuit diagram
Figure 1 Internal wiring of connections
Key:
Tolerance and temperature response at T
A
= -25°C to
+60°C
Drift
Typical Maximum
±45 ppm/K ±75 ppm/K
Tolerances influenced by electromagnetic interfer-
ence
Type of electro-
magnetic inter-
ference
Standard Toler-
ance
Criterion
Electromagnetic fields EN61000-4-3/
IEC61000-4-3
< ±1.0% A
Fast transients (burst) EN61000-4-4/
IEC61000-4-4
< ±1.0% A
Conducted interference EN61000-4-6/
IEC61000-4-6
< ±0.5% A
Protective circuit
IO-Link circuit
Microprocessor
Analog/digital converter
Protection
µC
L+
C/Q
L-
FE
FE
IO-Link
IC
Protection
1
4
3
Analog
IO-Link
Protection
IO-Link
IC
µC
AXL E IOL AI1 I M12 S
8594_en_04 PHOENIX CONTACT 6
7 Pin assignment
7.1 Connections on the device
Figure 2 Connections on the converter
7.2 Pin assignment of the IO-Link interface
Figure 3 Pin assignment of the I/O link interface
(M12 A-coded, pin)
7.3 Pin assignment of the analog input
Figure 4 Pin assignment of the analog input
(M12 A-coded, socket)
8 Connection notes
Always connect the analog sensors using shielded, twisted
pair cables.
9 Connection example
Figure 5 Connection example
No. Connection
1IO-Link interface
(indicated by IO-Link symbol)
2 Fixing options;
options for connection to functional earth ground
3 Analog input
Pin Signal Meaning
1L+ +24V supply voltage;
from IO-Link master
2- Not used
3 L- GND, reference potential for L+
4 C/Q IO-Link data transmission channel
3
2 1
1
4
3
2
Pin Assignment
1 +24 V, 100 mA sensor supply
2 Current input 4mA...20mA
3GND
4Not used
5Not used
2
3
4
5
1
1
4
3
2
L-
C/Q
L+
2
3
4
5
1
+24 V
GND
4...20 mA

2700338

Mfr. #:
Manufacturer:
Phoenix Contact