AXL E IOL AI1 I M12 S
8594_en_04 PHOENIX CONTACT 4
IO-Link port supply
Typical current consumption 16.5 mA ±15% (at 24 V DC)
Current consumption max. 120 mA
Protection against polarity reversal Yes
Short-circuit protection Yes
Overload protection Yes
I/O supply voltage 24 V DC
This supply voltage is provided via the IO-Link interface of the IO-Link
master.
Sensor supply voltage 24 V DC (max. 100 mA)
This supply voltage is provided via the I/O supply voltage.
Analog input
Number of inputs 1 (current)
Connection method M12 connector, A-coded
Connection method 3-conductor
Current input signal 4 mA ... 20 mA
Input resistance current input max. 500 Ω
Resolution A/D 12 bit
Data formats IB IL, S7-compatible
Filtering None or mean-value generation over 4, 16, or 32 measured values
Precision < 0.25 % (from the measuring range final value in the nominal range)
Permissible cable length max. 30 m (shielded cable)
Error messages to the higher level control or computer system
Overrange or underrange Message in the diagnostic code (in the IBIL format)
Measured value invalid/no valid measured value present Message in the diagnostic code (in the IBIL format)
Short circuit Message in the diagnostic code (in the IBIL format)
Open circuit; goes to 0mA Message in the diagnostic code (in the IBIL format)
Module faulty Message in the diagnostic code (in the IBIL format)
Mechanical tests
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 Operation: 2g
Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 Storage/transport:5g
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 Operation:30g, 11ms, three shocks in each space direction
Shock in acc. with EN 60068-2-27/IEC 60068-2-27 Storage/transport:50g, 11ms, three shocks in each space direction
Continuous shock according to EN60068-2-27/IEC60068-2-27 10g,16ms, 1000shocks, in all space directions
Approvals
For the latest approvals, please visit phoenixcontact.net/products.