3130-F120-P7T1-W02Q-8A

Thermal Overcurrent Circuit Breaker 3130
www.e-t-a.de
1646
4
1
The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, please multiply the circuit
breaker current ratings by the derating factor shown below. See also section
Technical information.
Ambient °F
temperature °C
-22
-30
-4
-20
+14
-10
+32
0
+73.4
+23
+104
+40
+122
+50
+140
+60
Derating factor
0.8 0.76 0.84 0.92 1 1.08 1.16 1.24
Trip time in seconds
+23 °C
+73.4 °F
+60 °C
+140 °F
-30 °C
-22 °F
… times rated current
Trip time in seconds
+23 °C
+73.4 °F
+60 °C
+140 °F
-30 °C
-22 °F
12468102040
10000
1000
100
10
1
0.1
0.1…2 A
2.5…20 A 1-pole
2.5…16 A 2- and 3-pole
Multipole types: all poles symmetrically loaded.
With single pole overload, thermal tripping will be at
approx. 1.54 x I
N
with 2-pole devices and at
approx. 1.68 x I
N
with 3-pole devices.
12468102040
10000
1000
100
10
1
0.1
… times rated current
This is a metric design and millimeter dimensions take precedence (
mm
)
inch
Installation drawing 3130-F1...
mounting area
When installing the circuit breaker apply pressure on bezel only.
I.2
LINE
I.II.3
10
32
7
25
20
5
8
7
operating area
.984
1.26
.276.276.315
.787
.197
.394
Accessories 3130-F130-...
Typical time/current characteristics
ø4.4
.173
36.5
1.44
41.5
1.63
1.97
.197
.472
.315
1.97
.433
2.17
12
5
50
55
50
ø11
ø8
Splash cover, transparent, for 3-pole version
X
221 258 01 (IP54), comprising bezel Y 306 109 01
and transparent cover Y 306 108 01
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications
without notice is reserved.Product markings may not be exactly as the ordering codes.
Errors and omissions excepted.
Appliance Inlet Module X3130 for 2-pole circuit breaker 3130-FA.A
www.e-t-a.de
1646
5
1
Thermal Overcurrent Circuit Breaker 3130
Dimensions
Mounting hole X3130
24
82
72
40.236.5
Circuit breaker 3130 (2-pole)
ø 3.3
I.2
LINE
I.II.3
72 ± 0.2
M3/Ø 3.3
31.6 ± 0.1
63.6 ± 0.15
2.50
2.83
Ø.130
1.24
Description
Typical applications
The appliance inlet module X3130 with double pole circuit breaker
3130-FA.A combines three functions within a single component: A C14
appliance inlet and rocker switch with resettable overcurrent protection;
screw mounting from the front or the rear.
Electrical medical apparatus, laboratory equipment, professional audio
equipment and office machines.
Ordering information
Type No.
X3130 Appliance inlet module for circuit breaker type 3130-FA.A
Module
A appliance inlet C14
Design
04 screw-type mounting
Accessories
00 without
Version
00 not wired; mounting position 3130:
I to connector
01 not wired; mounting position 3130:
0 to connector (standard)
Delivery condition
M module supplied with
circuit breaker FA.A
X3130 - A 04 00 01 - M Ordering example
Approvals
Technical data
Rated voltage AC 240 V
Rated current 10 A (IEC)
15 A (UL/CSA)
Ambient temperature -25°C ... 70°C
Number of poles L, N + ground
Cable cross section max. 1.5 mm
2
Degree of protection Class I
Mounting method screw-type mounting (front or rear)
Terminal design blade terminals DIN 46244 A6.3 x 0.8
Housing material thermoplastics, black UL94V-0
Appliance inlet C14 according to IEC/EN 60320-1, UL 498
Switch circuit breaker type 3130, 2-pole
Authority Standard Rated voltage Current ratings
UL UL 489
C22.2 No 42
Thermal Overcurrent Circuit Breaker 3130
www.e-t-a.de
1646
6
1

3130-F120-P7T1-W02Q-8A

Mfr. #:
Manufacturer:
E-T-A Circuit Breakers
Description:
Circuit Breakers Thermal circuit breaker with rocker actuation, single, double or three pole
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union