MINI-PS-100-240AC/2X15DC/1
100299_en_04 PHOENIX CONTACT 7
6Block diagram
NC
NC
L (+)
N (-)
OV
OV
7Safety notes
DANGER OF EXPLOSION!
Only remove equipment when it is disconnected and not in the potentially explosive area.
DANGER
Components with dangerously high voltage and high stored energy are located in the device!
Never carry out work on live parts!
Depending on the ambient temperature and the load, the housing can become very hot!
Cover termination area after installation in order to avoid accidental contact with live parts (e. g., installation in
control cabinet).
CAUTION:
Before startup please ensure:
The mains connection has been carried out by a competent person and protection against electric shock is
guaranteed!
The device can be disconnected outside the power supply unit in accordance with the regulations as in EN
60950 (e.g. through primary side line protection)!
All feed lines are sufficiently protected and dimensioned!
All output lines are dimensioned according to the maximum output current of the device or separately
protected!
Sufficient convection must be guaranteed.
ATTENTION: Danger if used improperly
The power supply units are built-in devices. The device may only be installed and put into operation by qualified
personnel. The corresponding national regulations must be observed.
Note: Electrical damage
Plug connectors may only be connected/disconnected when under no load.
MINI-PS-100-240AC/2X15DC/1
100299_en_04 PHOENIX CONTACT 8
8 Installation
MINI POWER
ATTENTION: Module can become
damaged
To ensure sufficient convection, we
recommend the following minimum spacing be
used between modules: 8 cm in a vertical
direction.
The power supply unit can be snapped onto all
DIN rails in acc. with EN 60715.
9Mounting position
259
99
80
80
114,5
107
MINI POWER
45
Mounting position: Installation depth 107 mm (+ DIN rail)
MINI-PS-100-240AC/2X15DC/1
100299_en_04 PHOENIX CONTACT 9
A
B
B
1
B
2
Assembly
Position the module with the DIN rail guide on the upper edge
of the DIN rail, and snap it in with a downward motion.
Removing
Pull the snap lever open with the aid of a screwdriver and slide
the module out at the lower edge of the DIN rail.
10 Connection to various systems
iT
L
N
PE
+
LN
TN-S
MINI
L
PEN
+
LN
TN-C
MINI
L
N
+
LN
TN-C
MINI
L1
L2
L3
N
PE
+
LN
MINI
L1
L2
L3
PEN
+
LN
MINI
L1
L2
L3
N
+
LN
MINI
L1
L2
L3
+
LN
MINI
The 100 V AC ... 240 V AC connection is made using the L and N screw connections.
The device can be connected to 1-phase AC networks or to two of the phase conductors of three-phase systems (TN, TT or
IT networks in acc. with VDE 0100-300/IEC 60364-3) with nominal voltages of 100 V AC ...240 V AC.
ATTENTION: Module can become damaged
In order to comply with the UL certification, use copper cables that are designed for operating temperatures of
>75°C.
In order to comply with EN 60950/UL 60950, flexible cables require ferrules. To safely connect a device, the
ferrules should have a length of at least 10 mm. To achieve a reliable and shockproof connection, strip the
connecting ends according to section "Structure".
In order to comply with the UL approval, use copper cables that are designed for operating temperatures
>75°C.
In order to comply with EN 60950/UL60950, flexible cables require ferrules. In order to fulfill GL requirements,
unused terminal spaces must be closed. Strip the connection ends as per the table in the chapter "Structure"