MINI-PS-100-240AC/2X15DC/1
100299_en_04 PHOENIX CONTACT 9
A
B
B
1
B
2
Assembly
Position the module with the DIN rail guide on the upper edge
of the DIN rail, and snap it in with a downward motion.
Removing
Pull the snap lever open with the aid of a screwdriver and slide
the module out at the lower edge of the DIN rail.
10 Connection to various systems
iT
L
N
PE
+
LN
–
TN-S
MINI
L
PEN
+
LN
–
TN-C
MINI
L
N
+
LN
–
TN-C
MINI
L1
L2
L3
N
PE
+
LN
–
MINI
L1
L2
L3
PEN
+
LN
–
MINI
L1
L2
L3
N
+
LN
–
MINI
L1
L2
L3
+
LN
–
MINI
The 100 V AC ... 240 V AC connection is made using the L and N screw connections.
The device can be connected to 1-phase AC networks or to two of the phase conductors of three-phase systems (TN, TT or
IT networks in acc. with VDE 0100-300/IEC 60364-3) with nominal voltages of 100 V AC ...240 V AC.
ATTENTION: Module can become damaged
In order to comply with the UL certification, use copper cables that are designed for operating temperatures of
>75°C.
In order to comply with EN 60950/UL 60950, flexible cables require ferrules. To safely connect a device, the
ferrules should have a length of at least 10 mm. To achieve a reliable and shockproof connection, strip the
connecting ends according to section "Structure".
In order to comply with the UL approval, use copper cables that are designed for operating temperatures
>75°C.
In order to comply with EN 60950/UL60950, flexible cables require ferrules. In order to fulfill GL requirements,
unused terminal spaces must be closed. Strip the connection ends as per the table in the chapter "Structure"
for a reliable and shockproof connection.