VAL-MS 230/3+1/FM-UD Order No.: 2858959
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2858959
PHOENIX CONTACT Deutschland GmbH Page 3 / 6
http://www.phoenixcontact.de Feb 25, 2011
Lightning test current (10/350) µs, peak value l
imp
12 kA (N-PE)
Impulse operate voltage at 6 kV (1.2/50)µs (N-PE) ≤ 1.5 kV
Protection level U
P
(L-N) ≤ 1.35 kV
Protection level U
P
(L-PE) ≤ 1.6 kV
Protection level UP (N-PE) ≤ 1.5 kV
Residual voltage (L-N) ≤ 1.35 kV (at In)
≤ 1.2 kV (at 10 kA)
≤ 1.1 kV (at 5 kA)
≤ 0.95 kV (at 3 kA)
Residual voltage (L-PE) ≤ 1.6 kV (at In)
≤ 1.35 kV (at 10 kA)
≤ 1.2 kV (at 5 kA)
≤ 1 kV (at 3 kA)
Residual voltage (N-PE) ≤ 0.4 kV (at In)
≤ 0.25 kV (at 10 kA)
≤ 0.15 kV (at 5 kA)
≤ 0.1 kV (at 3 kA)
Clamping voltage SVR (L-N) ≤ 0.9 kV (6kV - 500 A)
Clamping voltage SVR (L-PE) ≤ 1.2 kV (6kV - 500 A)
Clamping voltage SVR (N-PE) ≤ 1 kV (6kV - 500 A)
Response time (L-N) ≤ 25 ns
Response time (L-PE) ≤ 100 ns
Response time (N-PE) ≤ 100 ns
Max. required backup fuse with branch wiring 125 A (gL)
Short-circuit resistance I
P
with max. backup fuse
(effective)
25 kA
Follow current quenching capacity If (N-PE) 100 A (260 V)
Connection, protective circuit
Type of connection Screw connection
Connection type IN Biconnect screw terminal block
Connection type OUT Biconnect screw terminal block
Screw thread M5
Tightening torque 4.5 Nm
Stripping length 14.5 mm
Conductor cross section stranded min. 0.5 mm²