Electrical Products Division
6801 River Place Blvd.
Austin, TX 78726-9000
http://www.3M.com/elpd
Litho in USA.
© 3M 2002 78-8126-0833-5-A
IMPORTANT NOTICE
Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume all risks and liability
associated with such use.
Warranty; Limited Remedy; Limited Liability. This product will be free from defects in material and manufacture as of the date of purchase.
3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR
FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be,
at 3M’s option, to replace or repair the 3M product or refund the purchase price of the 3M product. Except where prohibited by law, 3M will
not be liable for any loss or damage arising from this 3M product, whether direct, indirect, special, incidental or consequential
regardless of the legal theory asserted.
Engineering Specification
Crimp-type terminals shall, electrically and mechni-
cally, connect to a pre-stripped end of a stranded cop-
per wire and have a flat tongue portion with a central
opening for mounting around a screw or stud.
The terminal line shall offer tongue variations in hole
(stud) size (6, 8 10, etc.) and configuration (ring, fork,
block fork, flanged block fork, locking fork, etc.):
and barrel variations in wire (AWG) size (22-18,
16-14, 12-10, etc.) and construction (non-insulated
brazed seam, vinyl insulated butted seam, nylon insu-
lated with insulation grip, etc.). The terminal line shall
have regulatory agency coverage (UL Listing, CSA
Certification). The terminal tongue shall be marked
with the wire range and manufacturer’s symbol (
).
The nylon insulated, multi-stud ring tongue terminal
with insulation grip shall be tin-plated, annealed cop-
per, with the tongue having a tapered stud hole (size 6
thru 10 and size 2 through 6) and a butted seam barrel
with a tin plated brass funnel entry insulation grip,
covered by a molded nylon sleeve, color coded and
sized for a specified (AWG) wire range (22-18, 16-14,
12-10).
Insulated terminals shall be UL Listed and CSA
Certified for 600 Volts maximum building wire: 1000
Volts maximum in signs, fixtures and luminaries and
have a maximum operating temperature of 221°F
(105°C).
3M is a trademark of 3M.
is a trademark of Underwriters Laboratories.
is a trademark of Canadian Standards Association.