https://www.phoenixcontact.com/pi/products/1697166
08/20/2018Page6/17
Sensor/actuator cable-SAC-5P-M12MS-M12FR-3L/.../...-1697166
Technical data
PUR irradiated halogen-free orange[150]
Flame resistance DINVDE0472 part 804, test type B
Halogen-free The cable is halogen-free
Other resistance hydrolysis and microbe resistant
UV resistant
Resistant to welding splashes
Ambient temperature (operation) -50 °C ... 105 °C (cable, fixed installation)
-40 °C ... 105 °C (cable, flexible installation)
PUR halogen-free orange[180]
Cable type PUR halogen-free orange
Cable type (abbreviation) 180
Cable abbreviation Li9YLi9Y-11Y
UL AWM style 20549
Conductor cross section 4x 0.34 mm² (Signal line)
1x 0.5 mm² (PE connection)
AWG signal line 22
AWG power supply 20
Conductor structure signal line 42x 0.10 mm
Conductor structure, voltage supply 28x 0.15 mm
Core diameter including insulation 1.27 mm ±0.02 mm (Signal line)
1.46 mm ±0.02 mm (PE connection)
Thickness, insulation ≥ 0.21 mm (Signal line)
≥ 0.21 mm (PE connection)
approx. 0.65 mm (Outer cable sheath)
Wire colors brown, white, blue, black, green-yellow
Overall twist 5 wires around filler to the core
External sheath, color orange RAL 2003
External cable diameter D 5 mm ±0.15 mm
Cable weight 36 kg/km
Outer sheath, material PUR
Material conductor insulation PP
Conductor material Bare Cu litz wires
Insulation resistance ≥ 10 GΩ*km (at 20 °C)
Conductor resistance ≤ 58 Ω/km (Signal line)
≤ 39 Ω/km (PE connection)
Nominal voltage, cable ≤ 300 V
Test voltage, cable ≥ 3000 V
Flame resistance in accordance with DIN UL-Style 20549
Halogen-free in accordance with DIN VDE 0472 part 815
Ambient temperature (operation) -25 °C ... 80 °C (Cable)
PUR halogen-free gray[280]