GE
Preliminary Data Sheet
Compact Power Line Shelves
RS485 shelf for the CP3500 rectifier
March 7, 2016 ©2014 General Electric Company. All rights reserved. Page 3
General Specifications
Parameter Min Typ Max Units Notes
Reliability TBD
Hrs
Full load, 25C ; MTBF per SR232 Reliability protection for
electronic equipment, issue 2, method I, case III,
Service Life 10 Yrs Full load, excluding fans
Unpacked Weight Kgs/Lbs
Packed Weight TBD Kgs/Lbs
Safety/Standards Compliance
Safety Standards UL60950-1, CAN/CSA C22.2 No 60950-1, EN60950-1
Certification Marks TUV Licensed, UL Recognized (Canada and U.S.)
Environmental Specifications
Parameter Min Typ Max Units Notes
Ambient Temperature
Operating
-40
3
65
°C
Storage -40 85 °C
Humidity Operating
Storage
5
5
95
95
%
Relative humidity, non-condensing
Shock and Vibration acceleration 6 Grms NEBS GR-63-CORE, Level 3, 20 -2000Hz, min 30 minutes
Earthquake Rating 4
Zone
NEBS GR-63-CORE, all floors, Seismic Zone 4 Designed and
tested to meet NEBS specifications.
EMC
Parameter Criteria Standard Level Test
Conducted emissions AC input & DC output EN55022, FCC Docket 20780 part 15, subpart J
EN61000-3-2
Meets Telcordia GR1089-CORE by a 6dB margin
A 0.15 – 30MHz
0 – 2 KHz
Radiated emissions EN55022 by a 6dB margin A 30 – 10000MHz
Lightning surge AC input EN61000-4-5, Level 4, 1.2/50µs – error free A 4kV, common mode
A 2kV, differential mode
ANSI C62.41 - damage free A3 6kV, common & differential
Fast transients Input immunity EN61000-4-4, Level 3 B 5/50ns, 2kV (common mode)
Conducted RF fields Enclosure immunity EN61000-4-6, Level 3 A 130dBµV, 0.15-80MHz, 80% AM
Radiated RF fields EN61000-4-3, Level 3 A 10V/m, 80-1000MHz, 80% AM
ENV 50140 A
ESD AC input & DC output EN61000-4-2, Level 3 B 6kV contact, 8kV air
3
Designed to start and work at an ambient as low as -40°C, but may not meet operational limits until above -5°C