J2014004L001

GE
Preliminary Data Sheet
March 7, 2016 ©2014 General Electric Company. All rights reserved.
Compact Power Line Shelves
RS485 shelf for the CP3500 rectifier
Model: J2014004
Features
Mounts into standard 19” EIA-310-D racks
Single main output feeder either grounded or isolated
+5V standby power isolated from main output
Adjustable mounting ears for flush or set back positions.
Supports hot-swapping of modules
Accommodates mechanical latching into the slot
Communicates via RS485 using the Galaxy Protocol
LAN/Ethernet remote connectivity
Daisy chained RJ45 connections may configure up to 20
shelves of rectifiers in parallel
Passes Zone 4 earthquake requirements
CUR*
recognized
TUV
certified
CE Mark
§
Shock & Vibration: Meets IPC 9562 Class II standards
Description
The 1U (1.75”) high family of J2014004 type shelves are designed to mount into 19-inch wide frames providing up to
14kW of 54V output power. There are four slots for modules. These shelves are designed for the CP3500AC54TE rectifier.
The shelves are parallelable. A slide switch identifies the first shelf. Subsequent shelf addressing is automatically
configured internally. These shelves are designed for RS485 communications.
* UL is a registered trademark of Underwriters Laboratories, Inc.
CSA is a registered trademark of Canadian Standards Association.
VDE is a trademark of Verband Deutscher Elektrotechniker e.V.
§ This product is intended for integration into end-user equipment. All CE marking procedures of end-user equipment should be
followed. (The CE mark is placed on selected products.)
** ISO is a registered trademark of the International Organization of Standards
GE
Preliminary Data Sheet
Compact Power Line Shelves
RS485 shelf for the CP3500 rectifier
March 7, 2016 ©2014 General Electric Company. All rights reserved. Page 2
Absolute Maximum Ratings
Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings only, functional
operation of the device is not implied at these or any other conditions in excess of those given in the operations sections of the data sheet. Exposure to
absolute maximum ratings for extended periods can adversely affect the device reliability.
Parameter Symbol Min Max Unit
Input Voltage: Continuous VIN 0 300 V
ac
Operating Ambient Temperature TA -40 65
1
°C
Storage Temperature Tstg -40 85 °C
I/O Isolation voltage to Frame (100% factory Hi-Pot tested) 2250 V
ac
Electrical Specifications
Unless otherwise indicated, specifications apply over all operating input voltage, load, and temperature conditions.
INPUT
Parameter Symbol Min Typ Max Unit
Operational Range V
IN
85 110/230 300 V
AC
Frequency Range
F
IN
47 50/60 63 Hz
AC Input Current, per module
I
IN
20 A
AC
MAIN OUTPUT
Parameter Symbol Min Typ Max Unit
Output Power V
in
> 200V
AC
W
0 - 14,000 W
V
in
140V
AC
0 - 6,000 W
Max output current
I
OUT
270 A
DC
Isolation
2
Output/frame – other circuits non-POE
POE
V
100
2250
V
DC
AUXILIARY OUTPUT
Parameter Symbol Min Typ Max Unit
Set point V
OUT
5.0 V
DC
Overall regulation (load, temperature, aging) V
OUT
-10 +5 %
Output current I
OUT
0 8 A
DC
Isolation Output/Frame
Output/Main output non-POE
POE
V 50
V
DC
V
50
2250
V
DC
The auxiliary output should be accessible to the user via a two position panel mounted connector
capable of carrying 9A of current. The 5V and ground symbol should be located near the
connector to identify the two pins.
1
See the derating guidelines published in the rectifier data sheet
2
The standard CP3500AC54TEZ currently in development is not designed for POE .
GE
Preliminary Data Sheet
Compact Power Line Shelves
RS485 shelf for the CP3500 rectifier
March 7, 2016 ©2014 General Electric Company. All rights reserved. Page 3
General Specifications
Parameter Min Typ Max Units Notes
Reliability TBD
Hrs
Full load, 25C ; MTBF per SR232 Reliability protection for
electronic equipment, issue 2, method I, case III,
Service Life 10 Yrs Full load, excluding fans
Unpacked Weight Kgs/Lbs
Packed Weight TBD Kgs/Lbs
Safety/Standards Compliance
Safety Standards UL60950-1, CAN/CSA C22.2 No 60950-1, EN60950-1
Certification Marks TUV Licensed, UL Recognized (Canada and U.S.)
Environmental Specifications
Parameter Min Typ Max Units Notes
Ambient Temperature
Operating
-40
3
65
°C
Storage -40 85 °C
Humidity Operating
Storage
5
5
95
95
%
Relative humidity, non-condensing
Shock and Vibration acceleration 6 Grms NEBS GR-63-CORE, Level 3, 20 -2000Hz, min 30 minutes
Earthquake Rating 4
Zone
NEBS GR-63-CORE, all floors, Seismic Zone 4 Designed and
tested to meet NEBS specifications.
EMC
Parameter Criteria Standard Level Test
Conducted emissions AC input & DC output EN55022, FCC Docket 20780 part 15, subpart J
EN61000-3-2
Meets Telcordia GR1089-CORE by a 6dB margin
A 0.15 30MHz
0 – 2 KHz
Radiated emissions EN55022 by a 6dB margin A 30 – 10000MHz
Lightning surge AC input EN61000-4-5, Level 4, 1.2/50µs – error free A 4kV, common mode
A 2kV, differential mode
ANSI C62.41 - damage free A3 6kV, common & differential
Fast transients Input immunity EN61000-4-4, Level 3 B 5/50ns, 2kV (common mode)
Conducted RF fields Enclosure immunity EN61000-4-6, Level 3 A 130dBµV, 0.15-80MHz, 80% AM
Radiated RF fields EN61000-4-3, Level 3 A 10V/m, 80-1000MHz, 80% AM
ENV 50140 A
ESD AC input & DC output EN61000-4-2, Level 3 B 6kV contact, 8kV air
3
Designed to start and work at an ambient as low as -40°C, but may not meet operational limits until above -5°C

J2014004L001

Mfr. #:
Manufacturer:
Description:
Rack Mount Power Supplies Power Line Shelf for CP3500 Rectifie
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet