FLT-CP-3C-350 Order No.: 2859725
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2859725
PHOENIX CONTACT Deutschland GmbH Page 3 / 6
http://www.phoenixcontact.de Feb 4, 2011
Lightning test current (10/350) µs, peak value l
imp
25 kA (1-pos.)
Protection level U
P
(L-PEN) ≤ 1.5 kV
Residual voltage (L-PEN) ≤ 1.3 kV
≤ 1.1 kV (10 kA)
≤ 1 kV (5 kA)
≤ 1 kV (3 kA)
Clamping voltage SVR (L-PEN) ≤ 0.9 kV
Response time (L-N) ≤ 25 ns
Max. required backup fuse with branch wiring 315 A (gL / gG)
Max. required backup fuse with V-type through
wiring
125 A (gL / gG)
Recommended backup fuse maximum 160 A (gL/gG, 125 A with serial through wiring)
Short-circuit resistance I
P
with max. backup fuse
(effective)
25 kA
Follow current quenching capacity If (L-PE) 25 kA (264 V AC)
3 kA (350 V AC)
Connection, protective circuit
Type of connection Screw terminal blocks
Connection type IN Biconnect screw terminal block
Connection type OUT Biconnect screw terminal block
Connection method Biconnect terminal block
Screw thread M5
Tightening torque 4.5 Nm
Stripping length 18 mm
Conductor cross section stranded min. 2.5 mm²
Conductor cross section stranded max. 25 mm²
Conductor cross section solid min. 2.5 mm²
Conductor cross section solid max. 35 mm²
Conductor cross section AWG/kcmil min. 13
Conductor cross section AWG/kcmil max 2
Remote indicator contact
Connection name Remote fault indicator contact
Switching function PDT contact
Type of connection Plug-in/screw connection via COMBICON
Screw thread M2