https://www.phoenixcontact.com/us/products/2858674
10/21/2014Page2/5
Type 2 surge protection base element-VAL-MS/3+1-BE/FM-UD-2858674
Technical data
General
T2
EN type T2
Mounting type DIN rail: 35 mm
Color black
Housing material PBT
Pollution degree 2
Inflammability class according to UL 94 V-0
Type DIN rail module, two-section, divisible
Protective circuit
Nominal frequency f
N
50 Hz (60 Hz)
Maximum continuous operating voltage U
C
500 V AC
Rated load current I
L
80 A
Short-circuit current rating I
SCCR
25 kA
Max. backup fuse with branch wiring 125 A AC (gG)
Max. backup fuse with V-type through wiring 80 A AC (gG)
Indicator/remote signaling
Connection name Remote fault indicator contact
Switching function PDT contact
Operating voltage 5 V AC ... 250 V AC
125 V AC (UL)
30 V DC
Operating current 5 mA AC ... 0.75 A AC
1 A AC (UL)
1 A DC
Connection method Screw connection
Screw thread M2
Tightening torque 0.25 Nm
4 lb
f
-in. (UL)
Stripping length 7 mm
Conductor cross section stranded min. 0.14 mm²
Conductor cross section stranded max. 1.5 mm²
Conductor cross section solid min. 0.14 mm²
Conductor cross section solid max. 1.5 mm²
AWG conductor cross section 28 ... 16
30 ... 14 (UL)
Connection data