Surge protection device-TTC-6-GDT-C-110AC-PT-I-2906861
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Coarse surge protection with integrated status indicator for a signal wire with grounded reference potential.
Why buy this product
Space-saving installation due to the narrow overall width of 6.2 mm
Signaling without additional auxiliary power, thanks to the mechanical status indicator
Optional remote signaling module monitors up to 40 items, without additional wiring
Quick and tool-free installation of surge protective devices, thanks to Push-in connection technology
Safe behavior in the event of overload, thanks to the integrated disconnect device
Coarse surge protection by means of gas discharge tube
Key Commercial Data
Packing unit 1 STK
GTIN
GTIN 4055626137162
Technical data
Dimensions
Height 92 mm
Width 6.2 mm
Depth 69.5 mm (incl. DIN rail 7.5mm)
Ambient conditions
Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Altitude ≤ 4000 m (amsl (above mean sea level))
Degree of protection IP20 (with end cover)
https://www.phoenixcontact.com/pi/products/2906861
08/19/2018Page2/4
Surge protection device-TTC-6-GDT-C-110AC-PT-I-2906861
Technical data
General
Housing material PBT
Flammability rating according to UL 94 V-0
Color traffic grey A RAL 7042
Mounting type DIN rail: 35 mm
Type DIN rail module, one-piece
Direction of action Line-Earth Ground
Protective circuit
IEC test classification C1
C2
C3
D1
Nominal voltage U
N
110 V AC
Maximum continuous voltage U
C
130 V AC
Rated current 2 A (60 °C)
Operating effective current I
C
at U
C
≤ 1 µA
Residual current I
PE
≤ 1 µA
Nominal discharge current I
n
(8/20) µs (line-earth)
5 kA
Pulse discharge current I
imp
(10/350)µs (line-earth)
0.5 kA
Voltage protection level U
p
(line-earth)
≤ 800 V (C1 - 2 kV)
≤ 1 kV (C2 - 10 kV)
≤ 800 V (C3 - 25 A)
≤ 900 V (C3 - 100 A)
Response time t
A
(line-earth)
≤ 100 ns
Input attenuation aE, asym. typ. 0.3 dB (≤ 8 MHz / 150 Ω)
typ. 0.3 dB (≤ 30 MHz / 50 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 50 Ohm system typ. 130 MHz
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system typ. 25 MHz
Capacity (line-earth) 5 pF
Resistance in series ≤ 100 mΩ
Surge protection fault message optical
Impulse durability (line-earth) C1 - 1 kA
C2 - 5 kA
C3 - 100 A
D1 - 500 A
Pulse reset time (line-earth) ≤ 1 ms
Connection data
Connection method Push-in connection
Stripping length 8 mm
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
https://www.phoenixcontact.com/pi/products/2906861
08/19/2018Page3/4
Surge protection device-TTC-6-GDT-C-110AC-PT-I-2906861
Technical data
Connection data
Conductor cross section solid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12
Standards and Regulations
Standards/specifications IEC61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN61643-21 2001 + A1:2009 + A2:2013
Drawings
Diagram
2
1
3
8040 50 60 70
I [A]
T [°C]
90
Dimensional drawing
62
69,5
92
6,2
Circuit diagram
3
4
1
2
!
unprotected
protected
Approvals
Approvals
Approvals
UL Listed / CSA / CSAus / DNV GL / cCSAus
Ex Approvals
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 138168

2906861

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Surge Suppressors TTC-6-GDT-C-110AC- PT-I
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet