DRT-960-48

SPECIFICATION
DRT-960-24
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (max.)
LEAKAGE CURRENT
OVER TEMPERATURE
SAFETY STANDARDS
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
24V
40A
0 ~ 40A
960W
80mVp-p
24 ~ 28V
±1.0%
±0.5%
±0.5%
200ms, 60ms/400VAC 200ms, 60ms/500VAC at full load
14ms/400VAC 30ms/500VAC at full load
Three-Phase 340 ~ 550VAC (Dual phase operation possible in connecting L1,L3,FG )
Note.5
47 ~ 63Hz
91%
2A/400VAC 1.6A/500VAC
COLD START 50A
<3.5mA / 530VAC
105 ~ 125% rated output power
30 ~ 36V
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
UL508, UL60950-1, TUV EN60950-1 EAC TP TC 004 approved
,
Compliance to EN55011 (CISPR11), EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3, EAC TP TC 020
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61204-3, EN61000-6-2 (EN50082-2), heavy industry level, criteria A, EAC TP TC 020
-20 ~ +60 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH non-condensing
±℃ )0.03%/ (0 ~ 50
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
122.5K hrs min. MIL-HDBK-217F (25 )
276*125.2*100mm (W*H*D)
3.3Kg; 4pcs/14.2Kg/1.14CUFT
File Name:DRT-960-SPEC 2018-01-15
DRT-960-48
48V
20A
0 ~ 20A
960W
80mVp-p
48 ~ 55V
±1.0%
±0.5%
±0.5%
59 ~ 66V
960W Three Phase Industrial DIN RAIL Power Supply
Three-Phase AC 340 ~ 550V wide range input
High efficiency 91% and low dissipation
Protections: Short circuit / Overload / Over voltage / Over temperature
Optional parallel function(1+1)
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
EN61000-6-2(EN50082-2) industrial immunity level
100% full load burn-in test
3 years warranty
Features :
DRT-960 series
ENVIRONMENT
SAFETY &
EMC
(Note 4)
PROTECTION
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC
/ 25 / 70% RH
NOTE
1. All parameters NOT specially mentioned are measured at 400VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Dual phase operation(connecting L1,L3,FG)is allowed under certain derating to output load. Please refer to the derating curves for details.
6. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
92%
Protection type : Constant current limiting, unit will shut down o/p voltage after 3 sec. , re-power on to recover
EMC IMMUNITY
EMC EMISSION
Bauar
Sicherheit
egel gema
t gepruft
od
be
www.
ID 2000000000
tuv.com
wac g
os
Mechanical Specification
Derating Curve
Case No.934 Unit:mm
AMBIENT TEMPERATURE ( )
LOAD (%)
-2001020304045506070
20
40
60
50
80
100
Static Characteristics
LOAD (%)
INPUT VOLTAGE (VAC) 60Hz
340 355 380 385 400 415 475430 490460 505 520 550
90
100
80
70
60
50
40
(VERTICAL)
Three phase operation
Dual phase operation
Block Diagram
fosc : 55KHz
ADMISSIBLE DIN-RAIL: TS35/7.5 OR TS35/15
35
Terminal Pin No. Assignment (TB1)
Terminal Pin No. Assignment (TB2)
Pin No.
Pin No.
1
1,2,3
2
4,5,6
3
4
Assignment
Assignment
FG
AC/L2
AC/L1
AC/L3
DC OUTPUT +V
DC OUTPUT -V
3621243 1 45
276100
TB1 TB2
125.2
LED
+V ADJ
ALARM
960W Three Phase Industrial DIN RAIL Power Supply
DRT-960 series
File Name:DRT-960-SPEC 2018-01-15
O.V.P.
FG
I/P
-V
+V
RECTIFIERS
&
FILTER
SWITCHING
PWM CONTROL
POWER
PHASE-SHIFT
FILTER
&
RECTIFIERS
FILTER
EMI
DETECTION
CIRCUIT
O.T.P.
CURRENT
LIMIT
TB2 Terminal Pin No. Assignment
Pin No.
1,2,3
4,5,6
7
8
Assignment
DC OUTPUT +V
DC OUTPUT -V
GND
P(Current Share)
TB1 Terminal Pin No. Assignment
Note: Under parallel operation, if the load current is too small, only one PSU(master) would provide the power and hence the LED
indicator of other PSUs may not light up.
Pin No.
1
3
4
2
Assignment
FG
AC/L2
AC/L3
AC/L1
5413
TB1 TB1
PSU PSU
42 126387 783621243 1 45
LOAD
+V -V
TB2
LED LED
TB2
When in parallel operation, the minimum output load should be greater than 3% of total output load.
(Min. load >3% rated current per unit x number of unit)
Parallel Function (1+1)-Optional (Special order required)
960W Three Phase Industrial DIN RAIL Power Supply
DRT-960 series
File Name:DRT-960-SPEC 2018-01-15

DRT-960-48

Mfr. #:
Manufacturer:
MEAN WELL
Description:
DIN Rail Power Supplies 960W 48V 20A
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union