SPECIFICATION
SPECIFICATION for SPD-20HP-277S only
Repetitive Surge Capability
SPD-20HP-480SSPD-20HP-277S
MODEL
OPERATING VOLTAGE
CONTINUOUS CURRENT (max.)
(MEASURED LIMITING VOLTAGE)
(VOLTAGE PROTECTION LEVEL)
MLV
U
P
MCOV/U
C
Note.1
Note.2
Note.3
(MAX. CONTINUOUS OPERATING VOLTAGE)
I (NOMINAL DISCHARGE CURRENT)
n
Note.4
I (MAX. DISCHARGE CURRENT)
max.
Note.5
OPERATING TEMPERATURE
SAFETY STANDARDS
DIMENSION
PACKING
SPECIFICATION
Temporary Overvoltage (V)
TOV UT @ t = 5s
T
Temporary Overvoltage (V)
TOV UT @ t = 120 min.
T
403VAC
529VAC
TN
50
Test Class II and III
Type 2 and 3
4CA
21A
Yes
Power grids
Max earth leakage current at Uc (μA)
IEC 61643-11 Test Classification
EN 61643-11 Type Classification
UL 1449 Type
Backup fuse (A)
End of life indication
LV System Fault for TN power Grid
LV System Fault for TN power Grid
Maximum gG Fuse
Optical
Light ON: SPD is functional
Light OFF: SPD has reached end-of-life
Value Condition
NOTE:
120 ~ 277VAC 50/60Hz
5A
347 ~ 480VAC 50/60Hz
5A
320VAC 510VAC
L-N: 810V
L-G: 1560V
N-G: 1570V
L-N: 1000V
L-G/PE: 3800V
N-G/PE: 2900V
L-N: 1400V
L-G: 1560V
N-G: 1570V
-----
10kA, 8/20 sμ
20kA, 8/20 sμ
-40 ~ +75℃
UL1449(Fourth Edition), EN61643-11 approved UL1449(Fourth Edition) approved
71.6*67.7*32 (L*W*H)
0.243Kg/Unit ; 1.73Kg/one box(6pcs); 9.3Kg/carton(including 5 boxs)
0.233Kg/Unit ; 1.67Kg/one box(6pcs); 9Kg/carton(including 5 boxs)
1. MCOV/U
C
: Maximum Continuous Operating Voltage - maximum r.m.s. voltage that could be continuously applied to the SPD.
. MLV: UL1449 Measured limiting voltage; the highest value of residual voltage measurements during the application of impuls μ2 es of 8/20 s
nominal discharge current (I
n
); an average voltage value of 15 impulses.
. U : IEC 61643-11 Voltage protection level; the highest value / μ3 s
P
of residual voltage measurements during the application of impulses of 8 20
(); .nominal discharge current In a rounding voltage value of maximum measurement
. Nominal Discharge Current I (A): The nominal discharge current is a measure of the SPDs endurance capability; 15 impulses of discharge4
n
current uses the 8/20μs current waveform.
. Maximum Discharge Current I (A): The maximum discharge current is a measure of the SPDs maximum capability; single impulse of5
max
discharge current uses the 8/20μs current waveform. All Devices pass maximum discharge current with possible, safe opening of thermal
disconnect.
File Name:SPD-20HP-SPEC 2018-05-09
20kA High Performance Surge Protection Device
SPD-20HP series
Pulse Rating
(8x20 Sec)µ
Strikes Surge
1 20,000A
2 15,000A
15 10,000A
100 3,000A
1,000 1,600A
10,000 650A
100,000 400A
1,000,000 240A
10000
1000
100
10
1
10
100 1000 1
0000
IMPULSE DURATION (μs)
SURGE CURRENT (A)
MODEL SIZE = 20MM
T = -55 C
A
o
TO 85 C
o
100000
10
4
10
5
10
6
1
2
10
2
10
3
15
∞
130
to 625V
M(
AC) RATING