ILB ETH 24 DI16 DIO16-2TX Order No.: 2832962
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2832962
PHOENIX CONTACT Deutschland GmbH Page 2 / 5
http://www.phoenixcontact.de Feb 8, 2011
Note on dimensions Specfications with male connectors
Weight 500 g
Note on weight specifications with male connectors
Mounting type DIN rail
Ambient temperature (operation) -25 °C ... 60 °C
Ambient temperature (storage/transport) -25 °C ... 85 °C
Permissible humidity (operation) max. 85 % ((no condensation))
Air pressure (operation) 80 kPa ... 108 kPa (up to 2000 m above mean sea level)
Air pressure (storage/transport) 66 kPa ... 108 kPa (up to 3500 m above mean sea level)
Degree of protection IP20
Test section I/O / Logic 500 V AC 50 Hz 1 min
I/O area / FE 500 V AC 50 Hz 1 min
Logic / FE 500 V AC 50 Hz 1 min
Conformance with EMC directives EN 55011:1998+A1:1999 Class A
Noise emission Industrial environment
Mechanical tests Vibration resistance in acc. with IEC 60068-2-6 5g
Shock in acc. with IEC 60068-2-27:1997 25g
Diagnostics messages Short-circuit / overload of the digital outputs Message in the
diagnostics register
Short-circuit, sensor supply Message in the diagnostics register
Undervoltage Power supply for sensors Message in the
diagnostics register
Interface
Fieldbus system Modbus TCP/IP
Name Ethernet
Type of connection RJ45 female connector
Transmission speed 10/100 MBit/s (with autonegotiation)
Transmission physics Copper
Power supply for module electronics
Supply voltage 24 V DC
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Supply current 60 mA
Current consumption 60 mA
Digital inputs
Input name Digital inputs