2810625

https://www.phoenixcontact.com/pi/products/2810625
08/19/2018Page1/5
Current transducers-MACX MCR-SL-CAC- 5-I-UP-2810625
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Current measuring transducer for 1 A and 5 A AC, the output signal 0...20 mA or 4...20 mA, can be configured
using a DIP switch with an operating mode indication through an LED
Product Description
The MACX MCR-SL-CAC-5-I(-UP) current measuring transducers convert sinusoidal alternating currents of 1 A or 5 A into standard analog signals
0...20 mA or 4...20 mA. The DIP switches, which can be accessed on the upper side of the housing, can be used to configure the input and output
current.
The MACX MCR-SL-CAC-5-I current transducer contains a supply voltage range of 19.2 V DC to 30 V DC.
The MACX MCR-SL-CAC-5-I current transducer contains a long range version with a supply voltage range of 19.2 V AC/DC to 253 V AC/DC.
Why buy this product
Input/output can be configured via DIP switches
Key Commercial Data
Packing unit 1 STK
GTIN
GTIN 4046356153782
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width 22.5 mm
Height 104 mm
Depth 114.5 mm
Ambient conditions
Ambient temperature (operation) -20 °C ... 65 °C (-4 °F...149 °F)
Ambient temperature (storage/transport) -40 °C ... 85 °C (-40 °F ... 185 °F)
https://www.phoenixcontact.com/pi/products/2810625
08/19/2018Page2/5
Current transducers-MACX MCR-SL-CAC- 5-I-UP-2810625
Technical data
Ambient conditions
Maximum altitude 2000 m
Input data
Configurable/programmable Via DIP switches
Input current range 0 A ... 5 A
Operate threshold 0.3 % (1 A)
0.45 % (5 A)
Setting range for min. input current 0 A AC ... 1 A (configurable)
Setting range for max. input current 0 A AC ... 5 A (configurable)
Overload capacity
2 x I
N (
continuous)
Surge strength
20 x I
N
(1 s)
Nominal frequency f
N
50 Hz
Frequency measuring range 45 Hz ... 65 Hz
Connection method Screw terminal block
Output data
Output name Current output
Configurable/programmable Via DIP switches
Current output signal 0 mA ... 20 mA (configurable)
4 mA ... 20 mA (configurable)
Max. output current 25 mA
Load/output load current output < 500 Ω (at 20 mA)
Ripple
< 10 mV
PP
(for 500 Ω at 20 mA)
Status display LED red (error), LED green (ready)
Switching output
Output name No switching output
Power supply
Supply voltage range 19.2 V AC/DC ... 253 V AC/DC
Max. current consumption
< 30 mA (at U
B
=24 V DC, I
OUT
=20 mA)
< 13 mA (at U
B
= 230 V AC, I
OUT
=20 mA)
Power consumption
< 0.9 W (at U
B
=24 V DC, I
OUT
=20 mA)
< 3.4 W (at U
B
= 230 V AC, I
OUT
=20 mA)
Connection data
Connection method Screw connection
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
https://www.phoenixcontact.com/pi/products/2810625
08/19/2018Page3/5
Current transducers-MACX MCR-SL-CAC- 5-I-UP-2810625
Technical data
Connection data
Stripping length 8 mm
Screw thread M3
General
Maximum transmission error ≤ 0.5 % (of nominal range value under nominal conditions)
Maximum temperature coefficient < 0.02 %/K
Temperature coefficient, typical < 0.015 %/K
Step response (10-90%) max. 300 ms
typ. 200 ms
Overvoltage category III
Degree of pollution 2
Test voltage input/output 4 kV (50 Hz, 1 min.)
Test voltage output/power supply 2 kV (50 Hz, 1 min.)
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
Color green
Housing material Polyamide PA non-reinforced
Mounting position any
Conformance CE-compliant
ATEX  II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada UL 508 Recognized
Standards and Regulations
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Connection in acc. with standard CUL
Standards/regulations EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
Comments Criterion B
Standards/regulations EN 61000-4-5
EN61000-4-6
Conformance CE-compliant
ATEX  II 3 G Ex nA IIC T4 Gc X
UL, USA/Canada UL 508 Recognized
Environmental Product Compliance
REACh SVHC N,N-dimethylacetamide 127-19-5
China RoHS Environmentally Friendly Use Period = 50

2810625

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
Industrial Current Sensors MACX MCR-SL- CAC-5-I-UP
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet