FWC (10 x 38mm)
Specifications
Description: Ferrule style high
speed fuses.
Dimensions: See dimensions
illustration.
Ratings:
Volts: — 600Vac/dc
Amps: — 6-32A
IR: — 200kA RMS Sym.
— 50kA @ 700Vdc (6-25A)
Agency Information: CE, UL Recognition: 6-32A.
UL Recognition: 6-25A
Electrical Characteristics
Total Clearing I
2
t
The total clearing I
2
t at rated
voltage and at power factor
of 15% are given in the
electrical characteristics. For
other voltages, the clearing
I
2
t is found by multiplying by
correction factor, K, given as
a function of applied working
voltage, E
g
, (rms).
Arc Voltage
This curve gives the peak
arc voltage, U
L
, which
may appear across the
fuse during its operation
as a function of the
applied working voltage,
E
g
, (rms) at a power
factor of 15%.
Power Losses
Watts loss at rated
current is given in the
electrical characteristics.
The curve allows the
calculation of the power
losses at load currents
lower than the rated
current. The correction
factor, K
p
, is given as a
function of the RMS load
current, I
b
, in % of the
rated current.
Catalog Numbers
Electrical Characteristics
Rated I
2
t (A
2
Sec)
Catalog Current Clearing Watts
Numbers Size RMS-Amps Pre-arc at 600V Loss
FWC-6A10F 6 4 30 1.5
FWC-8A10F 8 6 50 2.0
FWC-10A10F 10 9 70 2.5
FWC-12A10F 10 x 38mm 12 15 120 3.0
FWC-16A10F (
13
⁄32” x 1
1
⁄2”) 16 25 150 3.5
FWC-20A10F 20 34 260 4.8
FWC-25A10F 25 60 390 6.0
FWC-30A10F 30 95 600 7.5
FWC-32A10F 32 95 600 7.5
• Watts loss provided at rated current.
• See accessories on page 216.
Features and Benefits
• Excellent cycling capability and DC performance
• Low arc voltage and low energy let-through (I
2
t)
• Low watts loss in a compact size
• Used with finger-safe holders/blocks
Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters