FWC-20A10F

Ferrule — FWC 600V: 6-32A
Dimensions - mm (inches)
38.1
(1.500")
9.5
(0.375")
10.3
(0.406")
FWC (10 x 38mm)
Specifications
Description: Ferrule style high
speed fuses.
Dimensions: See dimensions
illustration.
Ratings:
Volts: — 600Vac/dc
Amps: — 6-32A
IR: — 200kA RMS Sym.
— 50kA @ 700Vdc (6-25A)
Agency Information: CE, UL Recognition: 6-32A.
UL Recognition: 6-25A
Electrical Characteristics
Total Clearing I
2
t
The total clearing I
2
t at rated
voltage and at power factor
of 15% are given in the
electrical characteristics. For
other voltages, the clearing
I
2
t is found by multiplying by
correction factor, K, given as
a function of applied working
voltage, E
g
, (rms).
Arc Voltage
This curve gives the peak
arc voltage, U
L
, which
may appear across the
fuse during its operation
as a function of the
applied working voltage,
E
g
, (rms) at a power
factor of 15%.
Power Losses
Watts loss at rated
current is given in the
electrical characteristics.
The curve allows the
calculation of the power
losses at load currents
lower than the rated
current. The correction
factor, K
p
, is given as a
function of the RMS load
current, I
b
, in % of the
rated current.
Catalog Numbers
Electrical Characteristics
Rated I
2
t (A
2
Sec)
Catalog Current Clearing Watts
Numbers Size RMS-Amps Pre-arc at 600V Loss
FWC-6A10F 6 4 30 1.5
FWC-8A10F 8 6 50 2.0
FWC-10A10F 10 9 70 2.5
FWC-12A10F 10 x 38mm 12 15 120 3.0
FWC-16A10F (
13
32” x 1
1
2”) 16 25 150 3.5
FWC-20A10F 20 34 260 4.8
FWC-25A10F 25 60 390 6.0
FWC-30A10F 30 95 600 7.5
FWC-32A10F 32 95 600 7.5
• Watts loss provided at rated current.
• See accessories on page 216.
Features and Benefits
• Excellent cycling capability and DC performance
• Low arc voltage and low energy let-through (I
2
t)
• Low watts loss in a compact size
• Used with finger-safe holders/blocks
Typical Applications
• DC common bus
• DC drives
• Power converters/rectifiers
• Reduced voltage starters
500 600400250100
1.5
1.0
0.5
0.3
0.2
0.15
E
g
K
U
L
2.0
1.6
1.2
10
3
800
600
500
400
300
400300200 500 600
E
g
Kp
1.0
0.8
0.4
0.5
0.6
0.3
0.2
0.1
30 40 50 60
70
80 90 100%
I
b
Data Sheet: 720011
For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa
205
High Speed
Fuses
High Speed Fuses
For product data sheets, visit www.cooperbussmann.com/datasheets/ulcsa
206
High Speed Fuses
Ferrule — FWC 600V: 6-32A
10
3
10
4
10
2
10
–1
10
–2
10
–3
10
–4
10
1 22468 2
10
2 2468
10
3
2
4
6
2
6
4
10
0
2
6
4
10
1
2
6
4
2
6
4
2
6
4
6
4
2
6
2
4
Prospective Current In Amps RMS
Virtual Pre-Arcing Time In Seconds
FWC-10A10F
FWC-30A10F & FWC-32A10F
FWC-20A10F
FWC-25A10F
FWC-12A10F
FWC-16A10F
FWC-8A10F
FWC-6A10F
Prospective Short-Circuit Current Symmetrical RMS
Peak Let-Through Current
2
4
2
6
6
4
2
6
4
246 246 246 246
10
1
10
2
10
3
10
4
10
1
10
2
10
3
10
4
10
5
FWC-6A10F
FWC-8A10F
FWC-10A10F
FWC-12A10F
FWC-16A10F
FWC-20A10F
FWC-25A10F
FWC-30A10F & FWC-32A10F
Peak Let-Through Curve
FWC 6-32A: 600V (10 x 38mm)
Time-Current Curve
Data Sheet: 35785306

FWC-20A10F

Mfr. #:
Manufacturer:
Bussmann / Eaton
Description:
Specialty Fuses 600V 20Arms Semiconductor
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment: