J7KNA-AR-22 125VS

10 Mini Contactor Relays 4-pole J7KNA-AR
Specifications
Coil Voltages
Standard voltages in bold type letters. Coil not exchangeable
Suffix Voltage Marking Rated Control Voltage U
s
to contactor type e.g. at the coil
range for
50Hz 60Hz
J7KNA-AR-40-24
for 50Hz
V
for 60Hz
V
min
V.
max
V.
min
V.
max
V.
12 12 12 11 12 12 12
24 24 24 22 24 24 24
42 42 42 38.5 42 42 42
48 48-50 48 48 50 48 50
60 60 60 52 66 54 60
90 90-95 100-105 90 95 100 105
95 95-100 105-110 95 100 105 110
100 100 110-115 100 105 110 115
105 105-110 115-120 105 110 115 120
110 110-115 120-125 110 115 120 125
200 200 210-220 195 205 210 220
Suffix Voltage Marking Rated Control Voltage U
s
to contactor type e.g. at the coil
range for
50Hz 60Hz
J7KNA-AR-40- 230
for 50Hz
V
for 60Hz
V
min
V.
max
V.
min
V.
max
V.
210 205-215 220-230 205 215 220 230
220 210-220 230-240 210 220 230 240
230 220-230 240 220 230 240 250
240 230-240 230 240 250 260
400 380-400 440 380 400 415 440
500 475-500 520-545 475 500 520 545
550 525-550 600 525 550 570 600
Mini Contactor Relays 4-pole J7KNA-AR 11
Engineering data and Characteristics
Mini Contactor Relays
Data according to IEC 947-5-1, VDE 0660, EN 60947-5-1
AC DC DC + Diode
Auxiliary Contacts Typ e J7KNA-AR... J7KNA-AR...D J7KNA-AR...VS J73KN-A...
Rated insulation voltage U
i
V AC 690
*1
*1) Suitable at 690V for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): U
imp
= 8kV.
Data for other conditions on request.
690
*1
690
*1
690
*1
Thermal rated current I
th
to 690V
Ambient temperature 40°C A 10 10 10 10
60°C A 6 6 6 6
Power loss per pole at I
th
W 0.5 0.5 0.5 0.5
Utilization category AC15
Rated operational current I
e
220-240V A 3 3 3 3
380-415V A 2 2 2 2
440V A 1.6 1.6 1.6 1.6
500V A 1.2 1.2 1.2 1.2
660-690V A 0.6 0.6 0.6 0.6
Utilization category DC13
Rated operational current I
e
60V A 2 2 2 2
110V A 0.4 0.4 0.4 0.4
220V A 0.1 0.1 0.1 0.1
Maximum ambient temperature
Operation open °C -40 to +60 (+90)
*2
*2) With reduced control voltage range 0.9 up to 1.0 x U
s
and with reduced thermal rated current I
th
to I
e
/AC15
enclosed °C -40 to +40
Storage °C -40 to +90
Short circuit protection
short-circuit current 1kA,
contact welding not accepted
max. fuse size gL (gG) A 20 20 20 20
Power consumption of coils
AC operated inrush VA 25 - - -
sealed VA 4 - 5 - - -
W1.2---
DC operated inrush W - 2.5 2.5 -
sealed W - 2.5 2.5 -
Operation range of coils
in multiples of control voltage U
s
0.85 - 1.1 0.8 - 1.1 0.8 - 1.1 -
Switching time at control voltage U
s
±10%
*3,*4
*3) Summary switching time = release time + arc duration
*4) Release time of NC make time of NO increase when suppressor units for voltage peak protection are used (Varistor, RC-units, Diode units).
AC operated make time ms 15 - 25 - - -
release time ms 8 - 25 - - -
arc duration ms 10 -15 - - -
DC operated make time ms - 15 - 19 15 - 19 -
release time ms - 8 - 25 8 - 25 -
arc duration ms - 10 -15 10 -15 -
Cable cross-section
all connectors solid mm² 0.75 - 2.5 0.75 - 2.5 0.75 - 2.5 0.75 - 2.5
flexible mm² 0.75 - 2.5 0.75 - 2.5 0.75 - 2.5 0.75 - 2.5
flexible with multicore cable end mm² 0.5 - 1.5 0.5 - 1.5 0.5 - 1.5 0.5 - 2.5
Clamps per pole 2 2 2 2
solid or stranded AWG 18 - 14 18 - 14 18 - 14 18 - 14
12 Mini Contactor Relays 4-pole J7KNA-AR
Dimensions
Mini Contactor Relays for North America
Data according to UL508
Main Contacts (cULus) Ty pe J7KNA-AR... J73KN-A...
Rated operational current "General Use" A 10 10
Rated operational power of three-phase motors 115V hp - -
at 60Hz (3ph) 200V hp - -
230V hp - -
460V hp - -
575V hp - -
Rated operational power of of AC motors 115V hp - -
at 60Hz (1ph) 200V hp - -
230V hp - -
Fuses A - -
Suitable for use on a capability of delivering not more than rms A - -
V- -
Rated voltage V AC 600 600
Auxiliary Contacts (cULus) heavy pilot duty AC A600 A600
standard pilot duty DC Q600 Q600
AC and DC operated
with screw terminals
Auxiliary Contact Blocks
J7KNA-AR... J73KN-A...
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
Cat. No. J04E-EN-01A
Do not use/install these products before having read the applicable precautions as listed in Cat. No. J09-EN-01
available from www.europe.omron.com or on request from OMRON local sales office.

J7KNA-AR-22 125VS

Mfr. #:
Manufacturer:
Description:
Industrial Relays Contacte
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union