Characteristics and ordering codes
I
R
A
u
k
%
R
typ
1)
mΩ
L
R
2)
µH
P
L
3)
W
Approx. weight
kg
f
P
max.
kHz
Ordering code
1) Typical values at 20 °C, tolerance ± 10%
2) At I
R
; tolerance ±10%
3) Typical values at I
R
, 50 Hz, 20 °C. Varies with type and length of motor cable, pulse frequency and modulation mode.
V
R
= 520 V AC
8 0.79 57 730 13 1.3 16 B86301U0008R000
12 0.65 31.0 400 19 1.8 16 B86301U0012R000
24 0.82 12.50 250 25 2.6 16 B86301U0024R000
45 0.80 5.80 130 45 5.6 10 B86301U0045R000
112 0.76 1.60 50 75 9.4 8 B86301U0112R000
180 0.78 0.85 32 100 11.0 6 B86301U0180S000
250 0.75 0.70 22 150 13.7 6 B86301U0250S000
320 0.78 0.40 18 180 17.0 6 B86301U0320S000
360 0.73 0.35 15 170 19.5 4 B86301U0360S000
400 0.71 0.32 13 200 20.5 4 B86301U0400S000
500 0.75 0.3 11 320 23.5 4 B86301U0500S000
720 0.78 0.24 8 480 30.5 2.5 B86301U0720S000
950 0.78 0.14 6 600 43 2.5 B86301U0950S000
1500 0.8 0.09 3.9 1050 65 2.5 B86301U1500S000
Line reactors, output chokes and output filters B86301U
3-phase dv/dt output reactors
Page 4 of 15Please read Cautions and warnings and
Important notes at the end of this document.