AXL E IOL AI1 I M12 R
8587_en_05 PHOENIX CONTACT 10
13 Significant values in various formats
13.1 IB IL format
Resolution: 1 bit (0000 -> 0008) accords 4.27
µA.
13.2 S7-compatible format
Resolution: 1 bit (000 0 -> 0008) accords 4.63
µA.
The value 8000
hex
is specified in S7-compatible format for all errors for which diagnostic codes 8001
hex
to 8040
hex
are output
in IB IL format.
Input data Range 4 mA ... 20 mA
hex dec mA
8001 32769 Overrange > 21.339
7F00 32512 Overdrive range (End) 21.339
7538 30008 Overrange (Start) 20.000427
7530 30000 Nominal range (End) 20.0
3A98 15000 Nominal range 12.0
0008 8 Nominal range 4.00427
0000 0 Nominal range (Start) 4.0
8080 32896 Underflow < 4.0
8002 32770 Wire break 0
Input data Range 4 mA ... 20 mA
hex dec mA
7FFF 32767 Overrange > 22.81
7EF8 32504 Overdrive range (End) 22.81
6C08 27656 Overrange (Start) 20.00463
6C00 27648 Nominal range (End) 20.0
3600 13824 Nominal range 12.0
0008 8 Nominal range 4.00463
0000 0 Nominal range (Start) 4.0
ED00 -4864 Underdrive range 1.185
8000 32768 Underflow/wire break/short circuit < 1.185