IBS RL 24 DIO 8/8/8-T
5632B 13
Switching frequency
- Ohmic nominal load 300 Hz, maximum
This switching frequency is limited by the selected data rate, the number of bus devices,
the bus structure, the software and the control or computer system used.
- Lamp nominal load 300 Hz, maximum
This switching frequency is limited by the selected data rate, the number of bus devices,
the bus structure, the software and the control or computer system used.
- Inductive nominal load 0.5 Hz (1.2 H; 48
W), maximum
Overload response Auto restart
Response time with ohmic overload (12
W,25°C
[77°F])
Approximately 3 s
Response after inductive overload Output can be destroyed
Reverse voltage endurance against short pulses Protection up to 2 A DC
Strength against permanently applied surge
voltage
No
Limitation of the demagnetization voltage
induced on circuit interruption
U (demag)
-8 V
Overvoltage disconnection At 0.7 A, minimum
Output current when switched off 100 µA, maximum
Output voltage when switched off 1 V, maximum
Output current with ground connection
interrupted
25 mA, maximum
Switching power with ground connection
interrupted
100 mW at 1 k
W load resistance, typical
Digital Outputs (Continued)
Output Characteristic When Switched On (Typical)
Output Current (A) Differential Output Voltage (V)
00
0.1 0.04
0.2 0.08
0.3 0.12
0.4 0.16
0.5 0.20