4 5
OVERVOLTAGE PROTECTION ( *10)
V
HOLD-UP TIME -
DISPLAY
VOLTAGE
-
CURRENT
-
STATUS
-
OUTPUT PROTECTIONS
-
INPUT
INPUT VOLTAGE ( *11)
-
INPUT CURRENT ( *12 )
A
INRUSH CURRENT ( 100/200Vac )
A
EFFICIENCY ( *12 )
%
INPUT CURRENT HARMONICS
-
POWER FACTOR (TYP)
-
ENVIRONMENT
OPERATING TEMPERATURE
-
OPERATING HUMIDITY
-
STORAGE TEMPERATURE
-
STORAGE HUMIDITY
-
MECHANICAL
VIBRATION
-
SHOCK
-
WEIGHT
Kg
SIZE (WxHxD) mm
EXTERNAL CONTROL OUTPUT ON/OFF
-
FUNCTIONS
OUTPUT GOOD
-
OUTPUT VOLTAGE PROGRAMMING
-
OUTPUT CURRENT PROGRAMMING
-
REMOTE SENSING
-
COMMUNICATION INTERFACE
-
APPROVALS
SAFETY STANDARDS
-
EMC STANDARDS
-
CONDUCTED EMI -
RADIATED EMI -
SERIES OPERATION -
PARALLEL OPERATION -
COOLING -
WITHSTAND VOLTAGE -
ISOLATION RESISTANCE -
0.2
0.5
ZUP20-20 ZUP20-40 ZUP36-6 ZUP36-12 ZUP36-24 ZUP60-3.5 ZUP60-7 ZUP60-14 ZUP80-2.5 ZUP80-5 ZUP120-1.8 ZUP120-3.6
0-20 0-36 0-60
0-20 0-40 0-6 0-12 0-24 0-3.5 0-7 0-14 0-2.5 0-5 0-1.8 0-3.6
400 800 216 432 864 210 420 840 200 400 216 432
5555555520202020
50 80 50 50 70 50 50 60 70 70 80 80
0.2 0.2
50 60 50 50 60 50 50 60 100 100 100 100
50 50 50 50 50 50 50 70 60 60 80 80
400 500 750
0.01%+5mA
0.07%+10mA
0.01%+5mA 0.01%+5mA
0.07%+10mA
0.01%+5mA 0.01%+5mA
0.07%+10mA
0.01%+5mA 0.01%+5mA 0.01%+5mA 0.01%+5mA
0.01%+2mA 0.01%+5mA 0.01%+2mA 0.01%+2mA 0.01%+5mA 0.01%+2mA 0.01%+2mA 0.01%+5mA 0.01%+2mA 0.01%+2mA 0.01%+2mA 0.01%+2mA
30 60 7.5 15 30 5 10 20 5 5 5 5
0.02%+5mA
0.05%+10mA
0.02%+5mA 0.02%+5mA
0.05%+10mA
0.02%+5mA 0.02%+5mA
0.05%+10mA
0.02%+5mA 0.02%+5mA 0.02%+5mA 0.02%+5mA
0.02%+12mV 0.02%+20mV 0.02%+35mV
0-24 0-40 0-66
0-80 0-120
800 1000
0.2 0.2
0-88 0-132
0.02%+50mV 0.02%+80mV
ZUP6-33 ZUP6-66 ZUP6-132 ZUP10-20 ZUP10-40 ZUP10-80 ZUP20-10
0-6 0-10
0-33 0-66 0-132 0-20 0-40 0-80 0-10
198 396 792 200 400 800 200
0.005%+2mV From No load to Full load, constant input voltage.
0.005%+1mV From 85-132VAC or 170-265VAC, constant load.
5585585
50 50 100 50 50 90 50
1
30ppm/ºC from rated voltage following 30-minute warm-up.
50 50 60 50 50 60 50
50 50 50 50 50 50 50
250 350
0.01%+5mA
0.01%+5mA
0.07%+10mA
0.01%+5mA 0.01%+5mA
0.07%+10mA
0.01%+5mA
0.01%+2mA
0.01%+2mA 0.01%+5mA
0.01%+2mA 0.01%+2mA 0.01%+5mA 0.01%+2mA
50 100 200 25 50 100 15
100ppm/ ºC from rated current following 30-minute warm-up.
0.02%+5mA
0.02%+5mA
0.05%+10mA
0.02%+5mA 0.02%+5mA
0.05%+10mA
0.02%+5mA
Better than 0.028% of rated output voltage
0.02%+5mV 0.02%+8mV
Better than 0.03% of rated output current
0.4%+40mA
0-7.5 0-13
0.01%+2mV Change in output over 8-hour interval under constant line, load and ambient temp following 30-minute warm-up.
5.6/2.7 11.2/5.4 2.9/1.4 5.6/2.7 11.2/5.4 2.9/1.4 5.6/2.7 11.2/5.4 2.6/1.3 4.9/2.4 2.9/1.4 5.3/2.6
15 30 15/30 (*7) 15 30 15/30 (*7) 15 30 15/30 (*7) 15 15/30 (*7) 15
79/83 79/82 76/80 80/84 80/84 75/79 80/84 80/84 78/82 83/87 78/82 82/86
3.2 5.8 2.9 3.2 5.8 2.9 3.2 5.8 2.9 3.2 2.9 3.2
20mS At 100V/200VAC, rated output voltage and output current.
3 digits ( 6v; 20v; 36v; 60v; 80v); 3.5 digits ( 10v; 120v ) accuracy: 0.2% +/- 2 digits.
3.5 digits (132A); All others 3 digits, accuracy: 0.5% +/- 3 digits.
CV/CC, Alarm, Fold, Local/Remote, On/Off.
Over Voltage, Over Temperature, Foldback.
85-265Vac Continuous, 47-63Hz
3.0/1.5 5.6/2.7 11.2/5.4 2.9/1.4 5.6/2.7 11.2/5.4 2.9/1.4
15/30 (*7) 15 30 15/30 (*7) 15 30 15/30 (*7)
69/72 74/77 74/77 73/77 79/82 77/81 74/78
Complies with EN61000-3-2, Class A
0.99 at 100/200Vac, 100% load.
0 to 50 ºC ; 100% Load.
30-90% RH ( No dewdrop ).
-20 to 70 ºC
10 - 95% RH (No dewdrop).
10-55Hz, Amplitude (sweep 1 min ) 2G, X, Y, Z, When mounted with mounting screws.
Less than 20G
2.9 3.2 5.8 2.9 3.2 5.8 2.9
200W and 400W units: 70 x 124 x 350. 800W units: 140 x 124 x 350 (Refer to outline drawing)
By TTL Signal or Dry Contact (Refer to instruction manual).
Open collector (Refer to instruction manual).
By Voltage ( 0-4V ) or by Resistance ( 0-4K ) (Refer to instruction manual).
By Voltage ( 0-4V ) or by Resistance ( 0-4K ) (Refer to instruction manual).
Maximum 0.5V drop on each load wire for model up to 60V and 2V for the 80V, 120V models
RS-232 and RS-485 Built-in, IEEE488 Optional.
UL3111-1, EN61010-1
EN61326-1, IEC 61326-1, FCC part 15 (class A).
EN55022-B, FCC-B, VCCI-B
EN55022-A, FCC-A, VCCI-A
Up to 2 units (Refer to instruction manual).
Master - Slave method; up to 5 units (Refer to instruction manual).
Forced air by blower fan (Blower fan is mounted within unit).
Input - Chassis...2.0kVAC 1 min, Input - Output...3.0kVac 1 min, Output - GND...500VAC 1 min.
More than 100MOhm at 25 ºC and 70% R.H.
mS
MODEL
OUTPUT VOLTAGE ( *1) V
OUTPUT CURRENT ( *2) A
RATED OUTPUT POWER W
CONSTANT LOAD REGULATION -
VOLTAGE LINE REGULATION -
RMS RIPPLE (5Hz-1MHz Bandwidth) mV
RIPPLE (pk to pk) (20MHz Bandwidth) mV
RECOVERY TIME ( *3) mS
TEMPERATURE COEFFICIENT
-
TEMPERATURE DRIFT
-
UP PROGRAMMING RESPONSE TIME (*4)
mS
DOWN PROGRAMMING
FULL LOAD mS
RESPONSE TIME
NO LOAD
CONSTANT
LOAD REGULATION ( *5)
-
CURRENT
LINE REGULATION ( *6)
-
RMS RIPPLE (5Hz-1MHz Bandwidth)
mA
TEMPERATURE COEFICIENT
-
TEMPERATURE DRIFT ( *8)
-
PROGRAMMING ( *9)
RESOLUTION -
VOLTAGE
ACCURACY -
RESOLUTION -
CURRENT
ACCURACY -
0.005%+4mV
0.005%+2mV
NOTES:
*1. Minimum voltage is guaranteed to maximum 0.2% of the rated output voltage.
*2. Minimum current is guaranteed to maximum 0.4% of the rated output current.
*3. Time for recovery to within +/-50mV against current change of 50% to 100%.
*4. From zero volts to full scale , resistive load and current setting at maximum.
*5. From no load to full load , constant input voltage.
*6. From 85~132Vac or 170~265Vac constant load.
*7. At cold start Ta=25 ºC.
*8. Change in output over 8 hour interval constant line, load and ambient temperature
following 30-minutes warm-up.
*9.
Given for control of the output via the serial communication or via front panel controls.
*10. Inverter shut down method, manual reset (OVP will shut down output)
*11. For cases where conformance to various safety specs. (UL, IEC, etc.) are
required, to be described as 100-240VAC (50/60Hz) on name plate.
*12. At 100/200Vac and Maximum Output Power.
Zup Series Specifications