127-F-P10-H-KF-4A

www.e-t-a.de
1
Thermal Overcurrent Circuit Breaker 127-...
1646
1
Description
Typical applications
Ordering information
Approvals
Technical data
Single pole thermal circuit breaker with push-to-reset, tease-free,
trip-free, snap action mechanism (R-type TO CBE to EN 60934; M-type
when fitted with optional manual release feature). Available in versions
for plug-in or integral mounting, track mounting, or with a frame for
snap-in panel mounting. The optional -KF housing is particularly suited
to high humidity and other damp conditions.
Approved to CBE standard EN 60934 (IEC 60934).
Motors, transformers, solenoids, battery chargers, extra low voltage
systems.
127-P10-H-KF 127-T12-H
For further details please see chapter: Technical Information
Voltage rating AC 250 V; DC 28 V
(UL: AC 250 V; DC 50 V)
Current ratings 0.05...25 A
Typical life 0.05...16 A 5,000 operations at 2 x I
N
, inductive
17...25 A 5,000 operations at 2 x I
N
, resistive
Ambient temperature -20...+60 °C (-4...+140 °F)
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664 A) withstand voltage degree
2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area AC 3,000 V
Insulation resistance > 100 MΩ (DC 500 V)
Interrupting capacity I
cn
0.05...2.5 A 8 x I
N
3...5 A 20 x I
N
6...12 A 200 A
13...25 A 300 A
Interrupting capacity I
N
U
N
(UL 1077) 0.05...20 A AC 250 V 2,000 A
0.05...25 A DC 50 V 2,500 A
Degree of protection operating area IP40
(IEC 60529/DIN 40050) terminal area IP00
Vibration 8 g (57-500 Hz) ± 0.61 mm (10-57 Hz)
to IEC 60068-2-6, test Fc,
10 frequency cycles/axis
Shock 25 g (11 ms), to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH
to IEC 60068-2-78, test Cab
Mass 127-P10-..: approx. 20 g
127-T..-: approx. 35 g
Standard current ratings and typical internal resistance values
Type No.
127
Mounting options
leave blank for integral/plug-in option
T12 track mounting with screw terminals M4
Terminal design (for use with and without flange -F)
P10 blade terminals A6.3-0.8 (QC .250)
Manual release
H manual release facility
Special housing
KF for tropical and high humidity conditions
Current ratings
0.05...25 A
127 - F - P10 - H - KF - 10 A ordering example
The exact part number required can be built up from the table of choices
shown above. Ordering references for optional features should be omitted if not
required.
Current
rating (A)
Internal
resistance (Ω)
Current
rating (A)
Internal
resistance (Ω)
0.05 280 1.5 0.6
0.08 100 1.8 0.4
0.1 110 2 0.3
0.15 56 2.5 0.2
0.2 29 3 0.1
0.25 18 3.5 0.06
0.3 14 4 0.06
0.35 9.8 4.5 0.05
0.4 7 5 0.05
0.45 5.9 6 0.02
0.5 4.9 7 0.02
0.6 3.4 8 0.02
0.7 2.5 10 < 0.02
0.8 1.8 15 < 0.02
0.9 1.5 16 < 0.02
1 1.2 20 < 0.02
1.2 0.8 25 < 0.02
Authority Standard Rated voltage Current ratings
VDE IEC / EN 60934 AC 250 V
DC 28 V
0.05 A…25 A
0.05 A…25 A
UL UL 1077 AC 250 V
DC 50 V
0.05 A…20 A
0.05 A…25 A
CSA C22.2 No 235 AC 250 V
DC 50 V
0.05 A…20 A
0.05 A…25 A
CQC GB 17701 AC 250 V
DC 28 V
0.05 A…25 A
0.05 A…25 A
www.e-t-a.de
2
Thermal Overcurrent Circuit Breaker 127-...
1646
1
The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, please multiply the
circuit breaker current ratings by the derating factor shown below. See also
section Technical information.
Ambient temperature °F
°C
-4
-20
+14
-10
+32
0
+73.4
+23
+104
+40
+122
+50
+140
+60
Derating factor
0.76 0.84 0.92 1 1.08 1.16 1.24
blade terminal
DIN 46244-A6.3-0.8
(QC .250)
.157
.780
1.22
.453
127-T12-H
spacing
31
ø4
11.5
52
63
44
54
G profile
EN 50035-G...
47
M4
13
7
14
tightening torque
for M4 max. 1.2 Nm
6
12
.157
1.85
2.05
2.48
.472
ON
OFF
.236
1.73
2.13
.551
.276
.512
.453
1.22
127-P10-H-KF
0.05...25 A
132
ø 4
19.8
11.5
31
ON8
.315
13.5
.531
45
1.77
9.4
.370
OFF
127-T12-H
35
53
max. 2
34
max. 2
25
35
1
53
operating area
mounting area
1.38
2.09
1.38
.984
.039
2.09
max .079
max .079
1.34
max. 2
max .079
Dimensions
Installation drawings
Trip time in seconds
... times rated current
0.05 - 2.7 A
2.8 - 23 A
10000
1000
100
10
1
0.1
25 A
14 402681020
Typical time/current characteristics at +23 °C/+73.4 °F
Internal connection diagram
1
2
This is a metric design and millimeter dimensions take precedence (
mm
)
inch
www.e-t-a.de
3
Thermal Overcurrent Circuit Breaker 127-...
1646
1
Thermal Overcurrent Circuit Breaker 127-...
Accessories
Connector bus links -K10
X 210 589 01/2.5 mm
2
(AWG 14), black (up to 20 A max. load)
X 210 589 02/1.5 mm
2
(AWG 16), brown (up to 13 A max. load)
Connector bus links -P10
X 210 588 01/1.5 mm
2
(AWG 16), brown (up to 13 A max. load)
X 210 588 02/2.5 mm
2
(AWG 14), black (up to 20 A max. load)
X 210 588 03/2.5 mm
2
(AWG 14), red (up to 20 A max. load)
X 210 588 04/2.5 mm
2
(AWG 14), blue (up to 20 A max. load)
Mounting sockets
10F-P10 (up to 16 A max. load)
75
10F-K10 (up to 20 A max. load)
10F-A10 (up to 16 A max. load)
A
ccessories for sockets (up to 20 A max. load)
2-way bus bar Y 301 166 02 4-way bus bar Y 301 166 01
~70
100 quick-connect tabs 6.3 (.250)
DIN 46247 tinned brass,
insulated
~2.76
~70
50 pin lugs to DIN 46230
tinned copper
~2.76
ø2.5
.099
22.9
4.2
7.9
12.5
2.9
8.5
15
thickness = 0.8 mm
.031 in.
15 15 15
52.9
.165
.311
.492
.114
.335
.591
.902
.591 .591 .591
2.08
blade terminals DIN 46244-A6.3-0.8 (QC .250)
1
45
wire corss sectional areas
2 x max. 2.5 mm
2
(AWG14) stranded
2 x max. 4 mm
2
(AWG12) solid
1
30
21
22
11
12
5.6
9.5
50
7.5
15
75
12
13
6
12
7
68
21
22
11
12
blade terminals DIN 46244-A6.3-0.8 (QC .250)
8
59
8
7
21 22
11 12
2.68
.315
.591
.296
.039
.039
.220
.374
1.97
1.77
2.95
.236
.472
.472
.276
.512
.315
.276
2.32
1.18
wire corss sectional areas
2 x max. 2.5 mm
2
(AWG14) stranded
2 x max. 4 mm
2
(AWG12) solid
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications
without notice is reserved.Product markings may not be exactly as the ordering codes.
Errors and omissions excepted.
This is a metric design and millimeter dimensions take precedence (
mm
)
inch

127-F-P10-H-KF-4A