2878696

PHOENIX CONTACT Deutschland GmbH Page 1 / 6
http://www.phoenixcontact.de Feb 8, 2011
Extract from the online
catalog
IL MOD BK DI8 DO4-PAC
Order No.: 2878696
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2878696
Modbus/RTU(ASCII) bus coupler, 8 inputs, 24 V DC, 4 outputs, 24 V
DC, 500 mA, complete with I/O connectors
Commercial data
GTIN (EAN)
4 046356 099967
sales group K410
Pack 1 pcs.
Customs tariff 85389091
Catalog page information Page 258 (AX-2009)
Product notes
WEEE/RoHS-compliant since:
11/27/2007
http://
www.download.phoenixcontact.com
Please note that the data given
here has been taken from the
online catalog. For comprehensive
information and data, please refer
to the user documentation. The
General Terms and Conditions of
Use apply to Internet downloads.
Product description
The bus coupler for the Modbus/RTU(ASCII) protocol has 4 digital outputs and 8 digital inputs. This package contains all
the necessary Inline connectors for connecting the supply and the I/Os.
The Inline terminals can be labeled using pull-out labeling fields. The fields have insert cards that can be labeled
individually to suit the application. Additionally, there is the ZBFM-6... Zack marker strip for labeling the terminal points.
IL MOD BK DI8 DO4-PAC Order No.: 2878696
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2878696
PHOENIX CONTACT Deutschland GmbH Page 2 / 6
http://www.phoenixcontact.de Feb 8, 2011
Technical data
General data
Width 80 mm
Height 119.8 mm
Depth 71.5 mm
Note on dimensions Specfications with male connectors
Weight 320 g
Note on weight specifications with male connectors
Mounting type DIN rail
Ambient temperature (operation) -25 °C ... 60 °C
Ambient temperature (storage/transport) -45 °C ... 85 °C
Permissible humidity (operation) 95 % (according to DIN EN 61131-2)
Permissible humidity (storage/transport) 95 % (according to DIN EN 61131-2)
Air pressure (operation) 80 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level)
Degree of protection IP20
Mechanical tests Vibration resistance in acc. with IEC 60068-2-6 5g
Shock test in acc. with IEC 60068-2-27 Operation: 25 g, 11 ms
duration, semi-sinusoidal shock impulse
Interface
Fieldbus system Lokalbus
Name Inline local bus
Type of connection Inline data jumper
Transmission speed 500 Kbit / 2 MBaud
Fieldbus system Modbus RTU
Name Modbus RTU
Type of connection D-SUB-9 female connector
Transmission speed 1,2 kBit/s bis 115,2 kBit/s
Number of positions 9
Name Supply
Type of connection 8-pos. Inline connector
Power supply for module electronics
Supply voltage 24 V DC (via Inline connector)
Supply voltage range 19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption max. 0.98 A (from U
BK
)
IL MOD BK DI8 DO4-PAC Order No.: 2878696
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2878696
PHOENIX CONTACT Deutschland GmbH Page 3 / 6
http://www.phoenixcontact.de Feb 8, 2011
Inline potential routing
Communications power U
L
7.5 V DC ±5%
Power supply at U
L
max. 0.8 A DC
Main circuit supply U
M
24 V DC
Supply voltage range U
M
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at U
M
max. 8 A DC (Sum of U
M
+ U
S
)
Current consumption from U
M
max. 8 A DC
Segment supply voltage U
S
24 V DC
Supply voltage range U
S
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at U
S
max. 8 A DC (Sum of U
M
+ U
S
)
Current consumption from U
S
max. 8 A DC
I/O supply voltage U
ANA
24 V DC
Supply voltage range U
ANA
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at U
ANA
max. 0.5 A DC
Digital inputs
Input name Digital inputs
Description of the input EN 61131-2 type 1
Type of connection Spring-cage connection
Connection method 2, 3-wire
Number of inputs 8
Typical response time Approx. 500 µs
Protective circuit Polarity reversal Suppressor diode
Input voltage 24 V DC
Input voltage range "1" signal 15 V DC ... 30 V DC
Typical input current per channel Typ. 3 mA
Digital outputs
Output name Digital outputs
Type of connection Spring-cage connection
Connection method 2, 3-wire
Number of outputs 4
Protective circuit Short-circuit and overload protection Free running circuit
Output voltage 24 V DC -1 V (At nominal current)
Nominal output voltage 24 V DC
Maximum output current per channel 500 mA

2878696

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
I/O Modules IL MOD BK DI8 DO4-PAC
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS