PSC-160A -C =Blank,-C ; Blank=PCB only, -C=Enclosed type=Blank,-C ; Blank=PCB only, -C=Enclosed type
160W Single Output with Battery Charger(UPS Function)
PSC-160 series
OUTPUT
SAFETY STANDARDS
MTBF
DIMENSION
OTHERS
PACKING
UL60950-1, TUV EN60950-1 approved
, EAC TP TC 004
Compliance to EN55032 (CISPR32) Class B, EN61000-3-2,-3, EAC TP TC 020
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, light industry level, criteria A, EAC TP TC 020
257K hrs min. MIL-HDBK-217F (25 )℃
PCB:152.4*76.2*32mm (L*W*H) ; Enclosed type:155.4*85*37mm (L*W*H)
PCB:0.35Kg;42pcs/15.7Kg/1.22CUFT ; Enclosed type: 0.45Kg;32pcs/15.4Kg/0.94CUFT
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2.0KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH℃
SAFETY &
EMC
(Note 4)
EMC IMMUNITY
EMC EMISSION
SPECIFICATION
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
-20 ~ +70 (Refer to "Derating Curve")℃
20 ~ 90% RH non-condensing
-20 ~ +85 , 10 ~ 95% RH℃
±℃℃0.03%/ (0~45 ) on CH1 output
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
ENVIRONMENT
RATED CURRENT
CURRENT RANGE
RATED POWER
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
ALARM
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
AC OK
Note.5
BATTERY LOW
AC CURRENT (Typ.)
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
88%
2.5A/115VAC 1.5A/230VAC
COLD START 35A/115VAC 70A/230VAC
<1mA / 240VAC
FUNCTION
Battery low voltage : < 11V Battery low voltage : < 22V
Relay contact output, ON : AC OK ; OFF : AC Fail ; Max. rating : 30V / 1A
Relay contact output, OFF : Battery OK ; ON : Battery Low ; Max. rating : 30V / 1A
3.8A
0 ~ 5.8A
160W
4A
--------
7.6A
0 ~ 11.6A
160W
POWER FACTOR (Typ.)
PF 0.95/230VAC PF 0.98/115VAC at full load≧≧
90%
MODEL PSC-160BPSC-160A
DC VOLTAGE 27.6V
CH1
13.8V
CH2
13.8V
CH1
OUTPUT NUMBER
VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
Note.4
HOLD UP TIME (Typ.)
2000ms, 30ms/230VAC 2000ms, 30ms/115VAC at full load
40ms/230VAC 40ms/115VAC at full load
240mVp-p
CH1: 24 ~ 29V
±1.0%
±0.5%
±0.5%
--------
--------
--------
--------
150mVp-p
CH1: 12 ~ 15V
±1.0%
±0.5%
±0.5%
RIPPLE & NOISE (max.)
Note.2
VOLTAGE TOLERANCE Note.3
OVERLOAD
OVER VOLTAGE
BATTERY CUT OFF
CH1:28.98 ~ 37.26V
20 1V±
105 ~ 150% rated output power
CH1:14.49 ~ 18.63V
Protection type : Hiccup mode, recovers automatically after fault condition is removed
Protection type : Shut down o/p voltage, re-power on to recover
10 0.5V±
PROTECTION
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.℃
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time.
5. Please refer to suggested Application 2.(2) (3) in page 3.、
6. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it
still meets EMC directives. For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
7. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than ℃℃
2000m(6500ft).
2A
--------
27.6V
CH2
--------
--------
--------
--------
File Name:PSC-160-SPEC 2018-01-12