QUINT-PS/ 1AC/24DC/ 3.5
103126_en_05 PHOENIX CONTACT 5
Safe isolation DIN VDE 0100-410
DIN VDE 0106-1010
Protection against electric shock DIN 57100-410
Protection against electric shock, basic requirements for safe isolation in
electrical equipment
DIN VDE 0106-101
Limitation of mains harmonic currents EN 61000-3-2
Device safety GS (tested safety)
Network variants (undervoltage) Semi F47-0706
Certificate CB Scheme
Approvals
UL approvals UL Listed UL 508
UL/C-UL Recognized UL 60950
UL/C-UL Listed UL 1604 Class I, Division 2, Groups A, B, C, D
CSA CAN/CSA-C22.2 No. 60950-1-07
CSA-C22.2 No. 107.1-01
Shipbuilding German Lloyd, ABS, LR, RINA, NK, BV
Conformance with EMC guideline 2004/108/EC and for low-voltage guideline 2006/95/EC
Noise immunity according to EN 61000-6-2
Electrostatic discharge EN 61000-4-2
Housing Level 4
Contact discharge 8 kV (Contact discharge)
Discharge in air 15 kV (Air discharge)
Comments Criterion B
Electromagnetic HF field EN 61000-4-3
Housing Level 4
Frequency range 80 MHz ... 1000 MHz (20 V/m)
1 GHz ... 3 GHz (10 V/m)
Field intensity
Comments Criterion A
Fast transients (burst) EN 61000-4-4
Input 4 kV (level 4 - asymmetrical)
Output 2 kV (level 1 - asymmetrical)
Signal 1 kV (level 1 - asymmetrical)
Comments Criterion B
Surge current loads (surge) EN 61000-4-5
Input 4 kV (inst. class 4 - asymmetrical: conductor to ground)
2 kV (inst. class 4 -symmetrical: conductor to conductor)
Output 2 kV (level 3 - asymmetrical: conductor to ground)
1 kV (level 1 - symmetrical: conductor to conductor)
Signal 1 kV (level 3 - asymmetrical: conductor to ground)
Comments Criterion B
Conducted interference EN 61000-4-6
Input/Output/Signal Level 3 - asymmetrical
Frequency range 0.15 MHz ... 80 MHz
Voltage 10 V
Comments Criterion A
Standards (Continued)