AHES3290

–1–
ASCTB360E 201604-T
Compact size 2 Form A and
2 Form A 1 Form B 35A power
relays for energy management
and industrial equipment
HE-S RELAYS
Protective construction: Flux-resistant type
TYPICAL APPLICATIONS
• Photovoltaic power generation systems (Solar inverter)
• Uninterruptible Power Supplies (UPS)
• Inverter
• Office air conditioner
• Industrial equipment
RoHS compliant
FEATURES
1. High-capacity and long life 35A 277V AC 5×10
4
(long life
type)
2. Electrical life (resistive load)
3. Compact size and low operating power
W: 30 × L: 36 × H: 40 mm W: 1.181 × L: 1.417 × H: 1.575 inch
Operating power: 1,880 mW (holding power: 170 mW)
4. Reduced coil holding voltage contributes to saving
energy of equipment
The coil holding voltage can be reduced up to 30%V of the
nominal coil voltage. This equals to operating power of
approximately 170 mW, which contributes equipment energy
savings.
* Coil holding voltage is the coil voltage after 100 ms from the applied nominal coil
voltage.
5. Contact gap: 3.2 mm .126 inch (VDE0126 compliant)
Compliant with European photovoltaic standard VDE0126
Compliant with EN61810-1 2.5 kV surge breakdown voltage
(between contacts)
6. Insulation distance (initial)
• Between Form A contact and coil: Min. 11.0 mm .433 inch
(Clearance/Creepage)
• Between Form B contact and coil: Min. 3.2 mm .126 inch
(Clearance/Creepage)
• Between Form A contact sets: Min. 8.2 mm .323 inch
(Clearance/Creepage)
• Between Form A contact and Form B contact: Min. 12.8 mm
.504 inch (Clearance/Creepage)
7. Contact gap (initial)
• Form A contact: Min. 3.2 mm .126 inch/each contact
• Form B contact: Min. 0.7 mm .028 inch
Min. 0.5 mm .020 inch (When Form A contact
welded)
8. Mirror contact mechanisms (Compliant with EN60947-4-1
mirror contact)
Form A contact Standard type Long life type
35A 277V AC
30A 220V AC
20A 277V AC
3×10
4
1×10
5
5×10
4
1×10
5
2×10
5
Detection of main contact welding makes it possible to
construct a safety circuit.
• Designed so that Form A contact and Form B contact will
not close at the same time.
When Form A contact welded, Form B contact gap of at
least 0.5 mm .020 inch is maintained.
* Form B contact, when used to monitor the condition of Form A contact, can be
used exclusively as an auxiliary contact.
Condi-
tions
Normal operation
When Form A
contact welded
Non-excitation Excitation Non-excitation
Mirror
contact
mecha-
nisms
Form B
contact
Form A
contact
Form B
contact
Form A
contact
Form B
contact
Form A
contact
Welding
Min. 0.5 mm
Min. .020 inch
New
HE-S (AHES3, 4)
–2–
ASCTB360E 201604-T
ORDERING INFORMATION
TYPES
Standard packing: Carton: 25 pcs.; Case: 100 pcs.
RATING
1. Coil data
Notes: *1. With 30%V coil holding voltage
*2. With no more than 24 hours per time with non-consecutive voltage application time.
Contact arrangement Nominal coil voltage
Part No.
Standard type Long life type
2 Form A
6V DC AHES3190 AHES3290
9V DC AHES3195 AHES3295
12V DC AHES3191 AHES3291
24V DC AHES3192 AHES3292
48V DC AHES3193 AHES3293
2 Form A 1 Form B
6V DC AHES4190 AHES4290
9V DC AHES4195 AHES4295
12V DC AHES4191 AHES4291
24V DC AHES4192 AHES4292
48V DC AHES4193 AHES4293
Nominal coil
voltage
Pick-up voltage
(at 20°C 68°F)
(Initial)
Drop-out voltage
(at 20°C 68°F)
(Initial)
Nominal operating
current
[±10%] (at 20°C 68°F)
Coil resistance
[±10%] (at 20°C 68°F)
Nominal operating
power
(at 20°C 68°F)
Max. applied voltage
(at 55°C 131°F)
6V DC
75%V or less of
nominal voltage
5%V or more of
nominal voltage
313mA 19.1Ω
ON: 1,880mW
Holding: 170mW*
1
110%V of nominal
coil voltage
150%V of nominal
coil voltage*
2
9V DC 209mA 43.1Ω
12V DC 157mA 76.6Ω
24V DC 78mA 306.4Ω
48V DC 39mA 1,225.5Ω
Contact arrangement / Operating function
3: 2 Form A Single side stable type
4: 2 Form A 1 Form B Single side stable type
AHES 9
Contact specifications
1: Standard type
2: Long life type
Terminals form
9: PC board terminal type
Nominal coil voltage (DC)
Part No.
Nominal coil voltage (V)
0
6
1
12
2
24
3
48
5
9
Note: Certified by UL/C-UL and VDE
HE-S (AHES3, 4)
–3–
ASCTB360E 201604-T
2. Specifications
Notes: *1. This value can change due to the switching frequency, environmental conditions, and desired reliability level, therefore it is recommended to check this with the
actual load.
*2. Wave is standard shock voltage of ±1.2×50μs according to JEC-212-1981
*3. Coil holding voltage is the coil voltage after 100 ms from the applied nominal coil voltage.
*4. Release time will lengthen if a diode, etc., is connected in parallel to the coil. Be sure to verify operation under actual conditions.
*5. The upper operation ambient temperature limit is the maximum temperature that can satisfy the coil temperature rise value. Refer to Usage, transport and storage
conditions in NOTES.
*6. Regarding Form B contact, only the 2 Form A 1 Form B type applies.
Characteristics Item
Specifications
Standard type Long life type
Contact
Arrangement 2 Form A, 2 Form A 1 Form B 2 Form A, 2 Form A 1 Form B
Form A
contact
Contact resistance (Initial)
Max. 100mΩ (By voltage drop 6V DC 1A),
Max. 3mΩ (By voltage drop 6V DC 20A, Reference value)
Contact material AgSnO2 type
Form B
contact*
6
Contact resistance (Initial) Max. 100mΩ (By voltage drop 6V DC 1A)
Contact material Au flashed AgNi type
Rating
Form A
contact
Nominal switching capacity
(Resistive load)
35A 277V AC
Max. switching voltage 480V AC, 110V DC
Contact carring power
(Resistive load)
9,695VA
Max. switching current 35A
Min. switching capacity
(Reference value)*
1
100mA 5V DC
Form B
contact*
6
Nominal switching capacity
(Resistive load)
1A 277V AC, 1A 30V DC
Max. switching voltage 277V AC, 30V DC
Contact carring power
(Resistive load)
277VA
Max. switching current 1A
Min. switching capacity
(Reference value)*
1
10mA 5V DC
Nominal operating power
1,880mW (after applying min.100ms coil nominal voltage)
170mW (30%V of coil holding voltage)
Electrical
characteristics
Insulation resistance (Initial) Min. 1,000MΩ (at 500 V DC) Measurement at same location as “Breakdown voltage” section.
Short current (A contact, Initial) Max. 1,000A 1 ms, 3 times (Reference value)
Breakdown
voltage
(Initial)
Between open Form A contacts 2,000 Vrms for 1 min. (Detection current: 10mA)
Between Form A contact and coil 5,000 Vrms for 1 min. (Detection current: 10mA)
Between Form A contact sets 5,000 Vrms for 1 min. (Detection current: 10mA)
Between open Form B contacts 1,000 Vrms for 1 min. (Detection current: 10mA)
Between Form B contact and coil 2,000 Vrms for 1 min. (Detection current: 10mA)
Between Form A contact and
Form B contact
5,000 Vrms for 1 min. (Detection current: 10mA)
Surge breakdown voltage*
2
(Between contact and coil)
10,000V (Between Form A contact and coil) (Initial)
2,500V (Between Form B contact and coil) (Initial)
Coil holding voltage*
3
30 to 110%V (Form A contact carrying current: 35A, at –40 to +55°C –40 to +131°F)
30 to 60%V (Form A contact carrying current: 35A, at –40 to +85°C –40 to +185°F)
Operate time (at 20°C 68°F) (Initial) Max. 30 ms (at nominal coil voltage, excluding contact bounce time)
Release time (at 20°C 68°F)*
4
(Initial) Max. 10 ms (at nominal coil voltage, excluding contact bounce time, without diode)
Mechanical
characteristics
Shock
resistance
Functional 98 m/s
2
(Half-wave pulse of sine wave: 11 ms; detection time: 10 μs)
Destructive 980 m/s
2
(Half-wave pulse of sine wave: 6 ms)
Vibration
resistance
Functional 10 to 55 Hz at double amplitude of 1.0 mm .039 inch (Detection time: 10 μs)
Destructive 10 to 55 Hz at double amplitude of 1.5 mm .059 inch
Expected life
Mechanical Min. 5×10
6
(at 180 times/min.)
Electrical
(Form A
contact)
Resistive load
Min. 3×10
4
(35A 277V AC) (ON : OFF = 1s : 9s) Min. 5×10
4
(35A 277V AC) (ON : OFF = 1s : 9s)
Min. 1×10
5
(30A 220V AC) (ON : OFF = 1s : 9s)
Min. 1×10
5
(20A 277V AC) (ON : OFF = 1s : 9s) Min. 2×10
5
(20A 277V AC) (ON : OFF = 1s : 9s)
Inductive load
Min. 3×10
4
(35A 250V AC) (cos
φ
= 0.8)
(ON : OFF = 0.1s : 10s)
Min. 5×10
4
(35A 250V AC) (cos
φ
= 0.8)
(ON : OFF = 0.1s : 10s)
Electrical
(Form B
contact)*
6
Resistive load
Min. 1×10
5
(1A 277V AC) (ON : OFF = 1s : 9s)
Min. 1×10
5
(1A 30V DC) (ON : OFF = 1s : 9s)
Conditions Conditions for operation, transport and storage*
5
Temperature: –40 to +55°C –40 to +131°F (Coil holding voltage 30 to 110%V)
Temperature: –40 to +85°C –40 to +185°F (Coil holding voltage 30 to 60%V or storage)
Humidity: 5 to 85% R.H. (Not freezing and condensing at low temperature)
Air pressure: 86 to 106 kPa
Unit weight Approx. 64 g 2.26 oz