https://www.phoenixcontact.com/us/produkte/1932575
11.10.2012Page2/6
PCB terminal block-MKDSP 25/ 1-15.00-F-1932575
Technical data
Technical data
Range of articles MKDSP 25/..-FL
Insulating material group I
Rated voltage (III/3) 1000 V
Rated voltage (III/2) 1000 V
Rated voltage (II/2) 1000 V
Connection in acc. with standard EN-VDE
Nominal current IN 125 A
Nominal cross section 25 mm²
Maximum load current 125 A (with 35 mm2 conductor cross section)
Insulating material PA
Inflammability class according to UL 94 V0
Internal cylindrical gage B 7
Stripping length 18 mm
Nominal voltage, UL/CUL Use Group B 600 V
Nominal current, UL/CUL Use Group B 115 A
Nominal voltage, UL/CUL Use Group C 600 V
Nominal current, UL/CUL Use Group C 115 A
Connection data
Conductor cross section solid min. 0.5 mm²
Conductor cross section solid max. 35 mm²
Conductor cross section stranded min. 0.5 mm²
Conductor cross section stranded max. 25 mm²
Conductor cross section stranded, with ferrule without plastic
sleeve min.
1 mm²
Conductor cross section stranded, with ferrule without plastic
sleeve max.
25 mm²
Conductor cross section stranded, with ferrule with plastic sleeve
min.
1.5 mm²
Conductor cross section stranded, with ferrule with plastic sleeve
max.
25 mm²
Conductor cross section AWG/kcmil min. 20
Conductor cross section AWG/kcmil max 2
2 conductors with same cross section, solid min. 0.5 mm²
2 conductors with same cross section, solid max. 6 mm²
2 conductors with same cross section, stranded min. 0.5 mm²
2 conductors with same cross section, stranded max. 6 mm²
2 conductors with same cross section, stranded, ferrules without
plastic sleeve, min.
0.5 mm²
2 conductors with same cross section, stranded, ferrules without
plastic sleeve, max.
4 mm²
2 conductors with same cross section, stranded, TWIN ferrules
with plastic sleeve, min.
0.5 mm²
2 conductors with same cross section, stranded, TWIN ferrules
with plastic sleeve, max.
6 mm²
Minimum AWG according to UL/CUL 20