11-800-526-2324 • www.us.tdk-lambda.com/lp/ Disclaimer: us.tdk-lambda.com/lp/legal.htm
JFS Series
Features
u Power factor Corrected
u Wide range output adjustment
u Single wire current share
u Input transient protection
u UL508 Industrial Controls Approval
u Factory Mutual Approval (Class 1, Div 2)
u 5 Year Warranty
u EN61000-4 Input Transient
Single Output Industrial Power Supplies
Notes: (Consult Installation Manual for detailed specifi cations, test methods and application notes)
(1) At 220VAC
(2) At 170VAC
Model JFS0500 JFS0750 JFS1000 JFS1500 JFS2000
AC Input Voltage - 85-265VAC (170-265VAC JFS2000), 47-63Hz
DC Input Voltage Range - 120-330VDC (240-330VDC for JFS2000)
Input Current (typ@110VAC) A rms 6 9 12 20 12
(1)
Inrush Current (110 / 220VAC) A 35 / 70 - / 70
Effi ciency (typ@110VAC) % 75 82
(2)
Power Factor - Meets EN61000-3-2 (0.99 typical)
Overcurrent Protection - <110% (auto recovery)
Overvoltage Protection V 24V models set at 30V, 48V models set at 60V (auto recovery)
Hold Up Time (Typ) ms 16
Transient Reponse - For 25% load change, recovers to regulation within 5ms
Remote Sense - Compenstates for 0.25V drop per leg
Remote Adjust - With either external Resistor or Voltage
Remote On / Off - Low = OFF, Open = ON
Signals & Indicators - Open Collector AC Fail and DC Good, Green LED
Parallel Connection - Single wire current share
Operating Temperature °C -20 to +70°C, derate linearly to 50% load from 50°C (30 min warm up at -20°C)
Storage Temperature °C -40 to +85
Humidity (non condensing) %RH 10 - 90
Cooling - Internal fan
Withstand Voltage - Input - Ground 2kVAC, Input - Output 3kVAC, Output - Ground 500VDC
Vibration - Per IEC68-2-6
Shock - Per IEC68-2-27
Safety Agency Approvals - UL508, UL60950, CSA22.2 No.60950, EN60950, FM3611 & CE Mark
Conducted & Radiated EMI - EN55022 Class A, FCC Docket 20780 Part 15, subpartJ, Class A
Weight (Net / Shipping) lbs 6 / 7 7 / 8 9 / 10
Size (WxHxD) mm See output line drawings
Warranty - 5 years
Specifi cations