PRD Series Power Relay
Contact ratings (continued)
Type Load Cycles
UL 508
1)
Models with screws or quick connects for main terminals
Code F, AgCdO, 1 pole
50A, 240VAC, general purpose
2)
20x10
3
30A, 277VAC, resistive 100x10
3
1.5HP, 120VAC 100x10
3
2HP, 250VAC 100x10
3
10A, 600VAC 100x10
3
Code F, AgCdO, 2 pole
50A, 240VAC, general purpose
2)
20x10
3
30A, 240VAC 100x10
3
20A, 277VAC 100x10
3
1.5HP, 120VAC 100x10
3
2HP, 250VAC 100x10
3
10A, 600VAC 100x10
3
2) In order to achieve 50A rating with contact code F, termination Code 0 or A is required.
Code H, Ag with magnetic blowout, 1 or 2 pole
20A, 125VDC 100x10
3
1/3HP, 125VDC 100x10
3
Code J, AgCdO with magnetic blowout, 1 or 2 pole
20A, 125VDC 100x10
3
1/3HP, 125VDC 100x10
3
Code N, W stationary with AgCdO movable, 1 or 2 pole
25A, 250VAC 100x10
3
1HP, 125VAC 100x10
3
2HP, 250VAC 100x10
3
UL 508
1)
Models with box lugs for main terminals
Code P, Ag, 1 form X
50A, 277VAC, general purpose 100x10
3
30A, 277VAC, ballast 6x10
3
15A, 277VAC, tungsten 6x10
3
102LRA, 17FLA, 240VAC 30x10
3
120LRA, 20FLA, 120VAC 30x10
3
1.5HP, 120VAC 30x10
3
3HP, 240VAC 30x10
3
Factory ratings
Models with box lugs for main terminals
Code R, Ag with magnetic blowout, 1 form X
60A, 28VDC, resistive 100x10
3
30A, 125VDC 100x10
3
Mechanical endurance DC Coil, 1x10
6
ops.; AC Coil 5x10
5
ops.
Auxiliary Snap-Action Switch Contact Data
Contact arrangement 1 form C (CO)
Rating 5A, 120VAC, 60Hz., 25°C
Contact material Ag
n
Contact ratings to 50A
n
Magnetic blowouts available for switching DC loads
n
Contact arrangement up to 2 form C (2CO)
n
1 form C auxiliary switch available
n
UL class B insulation
Typical applications
Industrial controls, lighting.
Approvals
UL E22575; CSA LR15734; VDE 40020133 (available only on PRD with DC
coil and Termination code 1)
Models with all screw terminals are UL Listed. Others are UL Recognized.
Technical data of approved types on request.
Contact Data
Contact arrangement
1 and 2 form A (NO); 1 and 2 form C (CO);
1 form X (NO-DM)
Rated voltage 600VAC,125VDC
Rated current 50A
Contact material Ag, AgCdO, W
Min. recommended contact load 1A, 12VDC or 12VAC
Initial contact resistance 75mΩ max.
Initial voltage drop 75mV
Frequency of operation 7200 ops/hr
Operate/releases time max. 40/20ms
Bounce time max. 10ms
Contact ratings
Type Load Cycles
UL 508
1)
Models with screws or quick connects for main terminals
Code Y, Ag, 1 pole
25A, 277VAC 100x10
3
1HP, 120VAC 100x10
3
2HP, 250VAC 100x10
3
10A, 600VAC 100x10
3
7A, 50VDC, resistive 100x10
3
Code Y, Ag, 2 pole
25A, 240VAC 100x10
3
20A, 277VAC 100x10
3
1HP, 120VAC 100x10
3
2HP, 250VAC 100x10
3
7A, 50VDC, resistive 100x10
3
10A, 600VAC 100x10
3
Code G, AgCdO, 1 pole
30A, 277VAC, resistive 100x10
3
1.5HP, 120VAC 100x10
3
2HP, 250VAC 100x10
3
10A, 600VAC 100x10
3
Code G, AgCdO, 2 pole
30A, 240VAC 100x10
3
20A, 277VAC 100x10
3
1.5HP, 120VAC 100x10
3
2HP, 250VAC 100x10
3
10A, 600VAC 100x10
3
1) Any PRD relay deviating electrically or physically from the standard models in the table is
not UL or CSA listed. All horsepower ratings are for single phase motors..
2
06-2016, Rev. 0616
www.te.com
© 2015 Tyco Electronics Corporation,
a TE Connectivity Ltd. company.
Catalog and product specification according
to IEC 61810-1 and to be used only together
with the ‘Definitions’ section.
Catalog and product data is subject to the
terms of the disclaimer and all chapters of
the ‘Definitions’ section, available at
http://relays.te.com/definitions
Catalog product data, ‘Definitions’ section,
application notes and all specifications are
subject to change.
Potter & Brumfield
General Purpose
Panel/Plug-in Relays
PRD Series Power Relay (Continued)
Insulation Data
Initial dielectric strength
between open contacts 2000V
rms
between contact and coil 2000V
rms
between adjacent contacts 2000V
rms
Initial insulation resistance
between insulated elements 100MΩ
Other Data
Material compliance: EU RoHS/ELV, China RoHS, REACH, Halogen content
refer to the Product Compliance Support Center at
www.te.com/customersupport/rohssupportcenter
Ambient temperature
AC coil: -55ºC to 45ºC
DC coil: -55°C to 80°C
Category of environmental protection
IEC 61810 RT0 - open relay
Terminal type Screw, Quick connects, Box lugs
Weight 284g
Packaging/unit tray/20 pcs., box/40pcs.
Accessories
Product Code Description
35D013 Metal dust cover
Coil Data
Coil voltage range 6 to 110VDC
6 to 480VAC
Coil insulation system according UL Class B
Coil versions, DC coil
Coil Rated Operate Release Coil Rated coil
code voltage voltage voltage resistance power
VDC VDC VDC Ω±10% W
6 6 4.5 0.6 18 2
12 12 9 1.2 71 2
24 24 18 2.4 288 2
48 48 36 4.8 1150 2
110 110 82.5 11 6050 2
All figures are given for coil without preenergization, at ambient temperature +23°C.
Other coil voltages on request.
Coil versions, AC coil
Coil Rated Operate Release Coil Rated coil
code voltage voltage voltage resistance power
VAC VAC VAC Ω±15% VA
6 6 5.1 0.6 0.86 9.8
12 12 10.2 1.2 3.2 9.8
24 24 20.4 2.4 12 9.8
120 120 102 12 290 9.8
240 240 204 24 1200 9.8
480 480 408 48 4500 9.8
All figures are given for coil without preenergization, at ambient temperature +23°C.
Other coil voltages on request.
Dimensions
PRD/PRDA 1, 3, 5 and 7 PRD/PRDA 11 PRD-3_P and R
2.28 MAX.
(57.9)
.375
(9.53)
.31
(7.9)
1.875
(47.63)
2.50
(63.5)
2.5 MAX.
(64)
.81
(20.6)
.59 MAX.
(15.0)
BOX LUG
CONNECTOR
.875 MAX.
(22.23)
1.687
(42.85)
3.375 MAX.
(85.73)
.31
(7.9)
1.875
(47.63)
2.51 MAX.
(63.8)
1
2
3
4
5
6
7
8
4.250 MAX.
(107.95)
3.00
(76.2)
.375
(9.53)
2.50 MAX.
(63.5)
3.375 MAX.
(85.73)
W/O AUX SWITCH
.375
(9.53)
2.23
(56.6)
3.375
(85.73)
2.28 MAX.
(57.9)
2.50 MAX.
(63.5)
ON PRD7
2
4
6
3
1
5
.187 + .005
– .003
4.75 + .13
– .08
1.875
(47.63)
2.51 MAX.
(63.75)
.31
(7.9)
2.5 MAX.
(63.3)
.81
(20.6)
.875 MAX.
(22.23)
2.5 MAX.
(63.5)
W/O AUX SWITCH
COIL
COIL
COIL
5
6
2
1
( )
2 MTG. HOLES
DIA. .187 + .005
– .003
4.75 + .13
– .08
( )
2 MTG. HOLES
DIA.
.187 + .005
– .003
4.75 + .13
– .08
( )
2 MTG. HOLES
DIA.
3
06-2016, Rev. 0616
www.te.com
© 2015 Tyco Electronics Corporation,
a TE Connectivity Ltd. company.
Catalog and product specification according
to IEC 61810-1 and to be used only together
with the ‘Definitions’ section.
Catalog and product data is subject to the
terms of the disclaimer and all chapters of
the ‘Definitions’ section, available at
http://relays.te.com/definitions
Catalog product data, ‘Definitions’ section,
application notes and all specifications are
subject to change.
Potter & Brumfield
General Purpose
Panel/Plug-in Relays
PRD Series Power Relay (Continued)
Product code structure Typical product code PRD -7 A Y 0 -120
Type
PRD Open relay
PRDA Open relay with aux. 1 form C (CO) snap-action switch
Main contact arrangement
1 1 form A (1 NO) 3 1 form X (1 NO-DM)
5 1 form C (1 CO) 7 2 form A (2 NO)
7V 2 form A (2 NO) with 3mm contact gap
1)
11 2 form C (2 CO)
1) Code 7V is only available as a UL Recognized model, not UL Listed
Coil input
A AC, 50/60Hz D DC
Main contact material and type
Y .312” (7.92mm) dia. Ag [25A max. rating]
G .312” (7.92mm) dia. AgCdO [30A max. rating]
F .312” (7.92mm) dia. AgCdO [50A max. rating]
2)
H Ag with magnetic blowout [20A DC max. rating]
3)
J AgCdO with magnetic blowout [20A DC max. rating]
N W stationary & AgCdO movable [25A max. rating]
4)
P Ag [50A max. rating]
5)
R Ag with magnetic blow out [50A max. rating]
5)
2) Available with Main contact arrangement code 1, 5, 7 or 11 only, and Termination code 0 or A only.
3) Available with Main contact arrangement code 3, 7 or 11 only
4) Available with Main contact arrangement code 1, 5, 7 or 11 only.
5) Available with Main contact arrangement code 3 only, and Termination code 4 only.
Termination
PRD types only
0 #8-32 screw term. for main contacts, #6-32 screw term. for coil.
1 .250” (6.35mm) QC for main contacts and coil
3 #8-32 screw term. for main contacts, .250” (6.35mm) QC for coil.
4 Box lug term. which accept #6 - #14 wire for main contacts, #6-32 screw term. for coil.
6)
6) Available with Main contact arrangement code 3 only, and Main contact material code P or R only.
PRDA (with aux. switch) types only
A #8-32 screw term. for main contacts, #6-32 screw term. for coil, screw term. for aux. switch
B .250” (6.35mm) QC for main contacts, coil and aux. switch
L Twin .250” (6.35mm) QC for main contacts, .250” (6.35mm) QC for coil and aux. switch
Coil voltage
Coil code: please refer to coil versions table
Terminal assignment for models with magnetic blowout
PRD3 with blowout PRD7 with blowout PRD 11 with blowout
-
+
-
-
-
+
THIS SIDE OF MAGNET
A
TTRACTS NORTH SEEKING
POLE OF COMPASS.
THIS SIDE OF MAGNET
ATTRACTS NORTH SEEKING
POLE OF COMPASS.
THIS SIDE OF MAGNET
ATTRACTS NORTH SEEKING
POLE OF COMPASS.
POLARITY
MARKING
POLARITY
MARKING
POLARITY
MARKING
(VDE approved Termination code)

PRD-3DY0-12

Mfr. #:
Manufacturer:
TE Connectivity / Potter & Brumfield
Description:
General Purpose Relays SPST-NO-DM 12VDC
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment: