Surge arrester B88069X6700C253
3-electrode arrester T90-A230X
PPD AB PD / PPD AB PM Issue 07 / 2013-03-07
Please read Cautions and warnings and Page 2 of 5
Important notes at the end of this document.
Features Applications
Very small size
Fast response time
High current rating
Stable performance over life
Extremely low capacitance
High insulation resistance
RoHS-compatible
Line protection
Station protection
Base stations
Electrical specifications
DC spark-over voltage
1) 2) 3)
DC spark-over voltage
2) 4)
184 ... 276
176 ... 550
V
V
Impulse spark-over voltage
at 100 V/µs - for 99% of measured values
3)
- for 50% of measured values
3)
at 1 kV/µs - for 99% of measured values
3)
- for 50% of measured values
3)
< 600
< 550
< 700
< 650
V
V
V
V
Service life
10 operations 50 Hz; 1 s
6)
5 A
10 operations 50 Hz; 1 s
5)
10 A
10 operations [5x (+) & 5x (-)] 8/20 µs
5)
10 kA
10 operations [5x (+) & 5x (-)] 8/20 µs
6)
5 kA
5 operations 10/250 µs
5)
2.5 kA
2 operations 10/350 µs
5)
2.5 kA
300 operations 10/1000 µs
5)
200 A
DC holdover voltage
8)
at 52 V
DC
/ 260
at 80 V
DC
/ 330
at 135 V
DC
/ 1300
< 150
< 150
< 150
ms
ms
ms
Activation after reflow soldering
7)
1 operation U = 600 V; 1 s
2 A
Insulation resistance at 100 V
DC
4)
> 1
G
Capacitance at 1 MHz
4)
< 1.5 pF
Transverse delay time
4)
< 0.2 µs
Arc voltage at 1 A
Glow to arc transition current
Glow voltage
~ 10
~ 1
~ 60
V
A
V
Weight ~ 0.8 g
Storage temperature -40 ... +90 °C
Climatic category (IEC 60068-1) 40/ 90/ 21