https://www.phoenixcontact.com/us/produkte/3061826
17.01.2013Page2/21
Feed-through terminal block-PT 6-QUATTRO/2P-3061826
Technical data
Technical data
Connection in acc. with standard IEC 61984
Nominal current I
N
41 A
Nominal voltage U
N
1000 V
Open side panel ja
Insertion/withdrawal cycles mechanical 100
Surge voltage test setpoint 9.8 kV
Result of surge voltage test Test passed
Power frequency withstand voltage setpoint 4.26 kV
Result of power-frequency withstand voltage test Test passed
Tight fit on carrier NS 35
Setpoint 5 N
Result of tight fit test Test passed
Conductor cross section short circuit testing 6 mm²
Short-time current 0.72 kA
Short circuit stability result Test passed
Proof of thermal characteristics (needle flame) effective duration 30 s
Result of thermal test Test passed
Test specification, oscillation, broadband noise DIN EN 50155 (VDE 0115-200):2008-03
Test spectrum Service life test category 1, class B, on vehicle body
Test frequency
f
1
= 5 Hz to f
2
= 150 Hz
ASD level
1.857 (m/s
2
)
2
/Hz
Acceleration 0.8 g
Test duration per axis 5 h
Test directions X-, Y- and Z-axis
Oscillation, broadband noise test result Test passed
Test specification, shock test DIN EN 50155 (VDE 0115-200):2008-03
Shock form Half-sine
Acceleration 5 g
Shock duration 30 ms
Number of shocks per direction 3
Test directions X-, Y- and Z-axis (pos. and neg.)
Shock test result Test passed
Temperature index, insulating material (DIN EN 60216-1 (VDE
0304-21))
125 °C
Static insulating material application in cold -60 °C
Connection data
Conductor cross section solid min. 0.5 mm²
Conductor cross section solid max. 10 mm²
Conductor cross section AWG/kcmil min. 20
Conductor cross section AWG/kcmil max 8
Conductor cross section stranded min. 0.5 mm²
Conductor cross section stranded max. 6 mm²