https://www.phoenixcontact.com/us/products/2904961
05/18/2015Page3/5
Repeater power supply-MACX PL-RPSSI-2I-2904961
Technical data
Connection data
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 7 mm
Screw thread M3
Connection method Screw connection
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
General
Maximum transmission error < 0.1 % (of final value)
Transmission error, typical < 0.05 % (of final value)
Maximum temperature coefficient < 0.01 %/K
Step response (10-90%) < 1.3 ms (for 4 mA ... 20 mA step)
Status display Green LED (PWR supply voltage)
Inflammability class according to UL 94 V0
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Housing material PA 66-FR
Color yellow
Designation Input/output/power supply
Electrical isolation
300 V
rms
(Rated insulation voltage (surge voltage category II; pollution
degree 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
Designation Output 1/output 2
Electrical isolation 1.5 kV AC (50 Hz, 1 min., test voltage)
Conformance CE-compliant, additionally EN 61326
ATEX II 3 G Ex nA IIC T4 Gc X
Data communication (bypass)
HART function Yes
Protocols supported HART
EMC data
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Typical deviation from the measuring range final value 3 %
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 3 %
Designation Conducted interferences