2904961

https://www.phoenixcontact.com/us/products/2904961
05/18/2015Page1/5
Repeater power supply-MACX PL-RPSSI-2I-2904961
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Measuring transducer power supply and input signal conditioner, HART-transparent. Transfers supplied or active
4 - 20 mA electrically isolated signals from the field to two loads. 4-way electrical isolation, PLd
Product Features
Key commercial data
Packing unit 1 pc
Weight per Piece (excluding packing) 240.0 GRM
Custom tariff number 85437090
Country of origin Germany
Technical data
Note
Utilization restriction
EMC: class A product, see manufacturer's declaration in the download
area
Dimensions
Width 12.5 mm
Height 99 mm
Depth 114.5 mm
Ambient conditions
Ambient temperature (operation) -20 °C ... 60 °C (Any mounting position)
Ambient temperature (storage/transport) -40 °C ... 80 °C
Maximum altitude ≤ 2000 m
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
https://www.phoenixcontact.com/us/products/2904961
05/18/2015Page2/5
Repeater power supply-MACX PL-RPSSI-2I-2904961
Technical data
Ambient conditions
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
Degree of protection IP20
Input data
Signal input Repeater power supply operation
Current input signal 4 mA ... 20 mA
Transmitter supply voltage > 21.5 V (20 mA)
> 21 V (23mA)
Signal input Signal conditioner operation
Current input signal 4 mA ... 20 mA
Voltage drop < 3.9 V
Output data
Signal output Repeater power supply operation
Current output signal 4 mA ... 20 mA (active)
Load/output load current output < 450 Ω (20 mA)
< 380 Ω (23mA)
Output ripple
< 20 mV
rms
Output behavior in the event of an error 0 mA (Cable break in the input)
0 mA (Cable short-circuit in the input)
Signal output Signal conditioner operation
Current output signal 4 mA ... 20 mA (active)
Load/output load current output < 450 Ω (20 mA)
< 380 Ω (23mA)
Output ripple
< 20 mV
rms
Output behavior in the event of an error 0 mA (Cable break in the input)
≥ 23 mA (Cable short-circuit in the input)
Power supply
Designation Repeater power supply operation
Supply voltage range 19.2 V DC ... 30 V DC (24 V DC (-20% ... +25%))
Max. current consumption < 75 mA (24VDC / 20mA)
Power consumption < 1.45 W (24 V DC/ 20 mA)
Connection data
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
https://www.phoenixcontact.com/us/products/2904961
05/18/2015Page3/5
Repeater power supply-MACX PL-RPSSI-2I-2904961
Technical data
Connection data
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Stripping length 7 mm
Screw thread M3
Connection method Screw connection
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
General
Maximum transmission error < 0.1 % (of final value)
Transmission error, typical < 0.05 % (of final value)
Maximum temperature coefficient < 0.01 %/K
Step response (10-90%) < 1.3 ms (for 4 mA ... 20 mA step)
Status display Green LED (PWR supply voltage)
Inflammability class according to UL 94 V0
Electromagnetic compatibility Conformance with EMC Directive 2004/108/EC
Housing material PA 66-FR
Color yellow
Designation Input/output/power supply
Electrical isolation
300 V
rms
(Rated insulation voltage (surge voltage category II; pollution
degree 2, safe isolation as per EN 61010-1))
2.5 kV (50 Hz, 1 min., test voltage)
Designation Output 1/output 2
Electrical isolation 1.5 kV AC (50 Hz, 1 min., test voltage)
Conformance CE-compliant, additionally EN 61326
ATEX  II 3 G Ex nA IIC T4 Gc X
Data communication (bypass)
HART function Yes
Protocols supported HART
EMC data
Designation Electromagnetic RF field
Standards/regulations EN 61000-4-3
Typical deviation from the measuring range final value 3 %
Designation Fast transients (burst)
Standards/regulations EN 61000-4-4
Typical deviation from the measuring range final value 3 %