CS1W-FLN22

CS1W-FLN22
4
FL-net Unit Specifications
Item Specifications
Model number CS1W-FLN22
Type 100Base-TX (10Base-T is also possible)
Applicable PLCs CS-series PLCs
Unit classification CS-series CPU Bus Unit
Mounting location CPU Rack or Expansion Rack
Number of Units that can be
mounted
4 max. (including Expansion Racks)
Transfer
specifications
Media access
method
CSMA/CD
Modulation Baseband
Transmission paths Star
Baud rate 100 Mbps (100Base-TX) 10 Mbps (10Base-T)
Transmission
media
Unshielded twisted-pair (UTP) cable
Categories: 5, 5e
Shielded twisted-pair (STP) cable
Categories: 100 at 5, 5e
Unshielded twisted-pair (UTP) cable
Categories: 3, 4, 5, 5e
Shielded twisted-pair (STP) cable
Categories: 100 at 3, 4, 5, 5e
Transmission
distance
100 m max. (distance between hub and node)
Number of cascade
connections with
repeater hub
24
Current consumption (Unit) 380 mA max. at 5 VDC
Vibration resistance
Conforms to JIS 0040.
10 to 57 Hz, 0.075-mm amplitude, 57 to 150 Hz, acceleration: 9.8 m/s
2
in X, Y, and Z directions for 80 minutes each
(Time coefficient; 8 minutes × coefficient factor 10 = total time 80 minutes)
Shock resistance
Conforms to JIS 0041.
147 m/s
2
three times each in X, Y, and Z directions
Ambient temperature
Operating: 0 to 55°C
Storage: –20 to 75°C
Humidity 10% to 90% (with no condensation)
Atmosphere Must be free from corrosive gas.
Weight 200 g max.
Dimensions 35 × 130 ×101 mm (W × H × D)
5
CS1W-FLN22
CX-FLnet
CX-FLnet
The CX-FLnet Support Software is used to make settings for OMRON FL-net Units mounted to Programmable Controllers (PLCs). The CX-FLnet
Support Software is installed on a computer running Windows 2000 (Service Pack 4 or higher), XP, Vista, or 7.
The CX-FLnet can be used to make settings for the following FL-net Units:
CS1W-FLN22, CJ1W-FLN22, CS1W-FLN02/12
CX-FLnet Functions
The CX-FLnet provides mainly the following functions.
CX-FLnet Availability
The CX-FLnet is available only as a component of the CX-One FA Integrated Tool Package. Refer to the CX-One Setup Manual (W463, provided
with the CX-One) for the CX-One installation and uninstallation procedures.
For detalis on CX-FLnet Support Software Operations refer to the FL-net Units Operation Manual (W440).
Function Description
Online connection
The following two methods can be used for connection.
Direct PLC Connection
Perform the settings after making a direct serial connection to each PLC to which FL-net Units are mounted.
Connection via a Network
Online connection and settings are made from the PLC connected to the computer running CX-FLnet (i.e., the gateway PLC) to each
PLC (i.e., the target PLCs) to which FL-net Units are mounted via the FL-net network or other networks (e.g., Ethernet or Controller
Link).
Settings
The following settings can be made.
CPU Bus Unit Setup Area
Data Link Setup
- Local Node Setup Area
- Other Node Setup Area
- Extension Setting
- Unit Area Setup (token watchdog timer)
File Communications settings for the online connection and data link settings can be saved and read in CSV format.
Monitor
Data Link Status
FL-net Unit Status (FA Link active status, transceiver power supply, received message or not, token monitoring timeout setting
exceeded, and IP address setting error)
Communications Cycle Time
Message Sequential Status
FL-net Unit Error Log
Status of nodes participating in the FL-net network
CS1W-FLN22
6
External Interface
CS1W-FLN22, 100BASE-TX
Individual Ethernet addresses are assigned to all communications devices connected to an Ethernet system. With the FL-net Unit, the Ethernet
address is shown in 12 digits, hexadecimal, on the right side of the Unit.
Note: The Ethernet address can also be checked by means of the FINS command CONTROLLER DATA READ.
Ethernet Connectors
The following standards and specifications apply to the connectors for the Ethernet twisted-pair cable.
Electrical specifications: Conforming to IEEE802.3 standards.
Connector structure: RJ45 8-pin Modular Connector (conforming to ISO 8877)
Connector pin Signal name Abbr. Signal direction
1 Transmission data + TD+ Output
2 Transmission data – TD– Output
3 Reception data + RD+ Input
4 Not used.
5 Not used.
6 Reception data – RD– Input
7 Not used.
8 Not used.
Hood Frame ground FG
NODE
NO.
1
×16
0
0
×16
1
UNIT
NO.
100BASE-TX
10BASE-T
0
FLN22
RUN
HER
TX
RX
100M
PER
LNK
MSG
TS
LED Indicators
Display the operating status of the Unit.
Unit Number Switch
Sets the unit number in one digit hexadecimal.
Node Number Switches
Set the Unit's FINS node number in two digits hexadecimal.
Ethernet Connector
Connects the Ethernet transceiver cable.
FL-net UNIT
CS1W-FLN22
OMRON Corporation MADE IN JAPAN
Lot No.

Ethernet Address
Ethernet address (12 digits)

CS1W-FLN22