KT (AKT2,4,7,8,9,4H,4B)
12
INSTALLATION
1. KT2 series
Please install vertically in order to satisfy the IP66 specification for dust and splash proofing.
The possible control panel plate thickness for installation is between 1 to 10 mm.
(1) Insert the unit from the front of the control panel.
(2) Insert the mounting frame until that the edges (2) make contact with the panel.
(3) Tighten the clamp screw and then turn it 3/4 of a turn after the edge of the screw reaches the panel.
2. KT4, 7, 8, 9 series
• Panel Mounting
Mountable panel thickness: Within 1 to 15mm .039 to .591inch
Insert a controller from the front side of the panel.
Attach the mounting brackets by the holes at the top and bottom
of the case and secure the controller in place with the screws.
• DIN rail mounting (KT7)
1) Hook 1 of the KT7 on the upper side of the DIN rail.
2) Making the 1 part of the KT7 as a support, fit the lower part
of the KT7 to the DIN rail.
KT7 will be completely fixed to the DIN rail with a “Click” sound.
Recommended DIN rail: Part No. ATA48011
Recommended fastening plate: Part No. ATA4806
MODE
G/T
pv
av
EVT T/B
AT
Notice
As the case is made of resin, do not
use excessive force while screwing
in the mounting bracket. The torque
is approximately 0.12N·m
KT7
MODE
5 678
9
G/T
pv
av
EVT T/B AT
1
DIN rail
2
Fastening plate
3. KT4H/4B series
Please install vertically in order to satisfy
the IP66 specification for dust and splash
proofing.
The possible control panel plate
thickness for installation is between 1 to 5
mm.
1) Insert the unit from the front of the
control panel.
2) Push the installation frame fully into
contact with the panel and tighten the
screws (screw torque from 0.05 N·m to
0.06N·m).
Rubber gasket