KT (AKT2,4,7,8,9,4H,4B)
13
OPTION
1. Shunt resistor
2. Terminal cover
Note: 2pcs of terminal cover of AKT8801 can be used as an AKT9801 cover.
3. Current transformer (CT)
4. Tool cable
AKT4810 (for KT2, 4, 8, 9, 4H and 4B) AKT4811 (for KT7)
AKT2801 (for KT2) AKT4801 (for KT4) AKT8801 (for KT8)
AKT9801 (for KT9)
AKT4H801 (for KT4H/4B)
74
±6
2.913
±.236
26
±1
1.024
±.039
47.5
23.8
3.5
15.5
1.870
.937
.138
.610
40
48
19 20
88
92
24.5
6
22.3
9 × 8.4 = 75.69 × 8.4 = 75.6
47.7
29
20
6
44.5
1.575
1.890
.748 .787
3.465
3.622
.965
.236
.878
9 × .331 = 2.9769 × .331 = 2.976
1.878
1.142
.787
.236
1.752
46.5
17
1.831
.669
>PC<
47.5
44.5
1.870
1.752
• External dimension
1) CT1 (for 5,10 and 20A)
Note: CT1 or CT2 for current detection is provided as an accessory when heater
burn-out alarm function is added.
2) CT2 (for 50A)
lk
KL
21
40
30
2-3.5 dia.
5.8 dia.
25
10
3
10.5
15
0.5
7.5
2.8
.827
1.575
1.181
2-.138 dia.
.228 dia.
.984
.394
.118
.413
.591
.020
.295
.110
kl
30
100
40
40
15
30
2-M3 .118
12 dia.
1.181
3.937
1.575
1.575
.591
1.181
.472 dia.
AKT4H820
n2.5 Plug 3-Pole type
200±20 50
7.784±.787 1.969
2000±40
78.74±1.575
USB Plug
20
.787
35
1.378
KT (AKT2,4,7,8,9,4H,4B)
14
EXTERNAL CONNECTION DIAGRAM
5. KT4H/4B series
1. KT2 series
TC: Input terminal for thermo couple.
• RTD: Input terminal for the resistance temperature sensor.
• DC: Input terminal for DC current or DC voltage.
For DC current input, connect a separately sold receipt resistor (50) between the input
terminals.
• OUT1: Output terminal for the control output or heating output [option: heating/cooling control].
• POWER SUPPLY: Power supply terminal.
• EV1/OUT2: Output terminal for event output 1 or cooling output [option: heating/cooling control].
• EV2: Output terminal for event output 2.
• DI: Input terminal for DI input. (There are three types of D1 input, the SV1/SV2 external switching
function, the OUT/OFF (RUN/STOP) output switching function, and timer function.)
• RS-485: Communication terminal for serial communication. (EV1, 2 is alarm output)
2. KT4 series
• POWER SUPPLY: Power supply
• OUT1: Control output 1 (heat output)
• OUT2: Control output 2 (cooling output)
• RELAY: Relay contact output
• V/A: DC voltage output/direct current output
• V: Contactless relay output
• A1: Alarm 1 output
• EVT: Event output (A2 output and heater cutoff alarm output)
• CT: CT input
• TC: Thermocouple
• RTD: Resistance temperature detection
• DC: Direct current or DC voltage
• RS-485: Serial communications
100 to 240V AC
POWER SUPPLY
24V AC/DC
POWER SUPPLY
NO
EV1/OUT2
EV2
NO
3A
250V
AC
3A
250V
AC
TC
DC
RTD
B
B
A
V/A
OUT1
RELAY
1
7
2
8
3
9
4
10
5
11
6
5 6
12
SG
D1
YA (–)RS-485 YA (+)
KT2
0.1A
24V
DC
2
3
4
5
1
2
1
7
8
9
10
6
12
13
14
15
11
POWER
SUPPLY
POWER
SUPPLY
24V AC/DC
100 to
240V AC
CT NO
NO
OUT2
SA1
EVT
3A
250V
AC
3A
250V
AC
YA (–)
YB
(+)
RS-485
NO SG
0.3A
250V
AC
KT4
TC DCRTD
B
B
A
V/A
OUT1
RELAY
3. KT8 and KT9 series
Note: That main setting No. 2 will not be possible on the KT8 and KT9 when the communications
functions is added.
4. KT7 series
• POWER SUPPLY: Power supply
• OUT: Control output
• RELAY: Relay contact output
• V/A: DC voltage output/direct current output
• EVT: Event output
[Alarm, loop fault alarm or heater cutoff alarm (optional)]
• TC: Thermocouple
• RTD: Resistance temperature detection
• DC: Direct current or DC voltage
• RS-485: Serial communications
• CT: CT input
24V AC/DC
250V AC
SV2
CT
A
B
B
TC
RTD
DC
A2/(HB)
YA(–)
YB(+)
RS-485
SG
3A
250V AC
3A
250V AC
OUT2/HB
KT8/KT9
A1
100 to 240V AC
POWER
SUPPLY
POWER
SUPPLY
GND
2
1
2
3
4
OUT1
RELAY
RELAY
V/A
V/A
NO
NO
NO
3A
250V AC
NO
NC
5
6
7
8
9
10
20
19
18
17
16
15
14
13
12
11
3
• POWER SUPPLY: Power
supply
• OUT1: Control output 1
• OUT2: Control output 2
(cooling output)
• RELAY: Relay contact output
V/A: DC voltage output/direct
current output
• A1: Alarm 1 output
• A2: Alarm 2 output
• HB: Heater cutoff alarm
output
• SV2: Second main setup
• CT: CT input
• TC: Thermocouple
• RTD: Resistance
temperature detection
• DC: Direct current or DC
voltage
• RS-485: Serial
communications
1
5 6 7 8 9
2 3 41 2
POWER SUPPLY POWER SUPPLY
24V AC/DC 100to 240V AC
OUT
V/A
RELAY
KT7
250V AC
3A
0.1A
24V DC
TC
RTD
DC
A
BB
EVT
RS-485
No.1
No.1
No.2
No.3
No.4
No.5
No.6
SG
NC
YB(+)
YA(–)
NC
SG
No.6
No.1
No.6
CT
POWER SUPPLY ....... Power supply
EVT1 .......................... Alarm 1 output
EVT2 .......................... Alarm 2 output (option) or heater burn-out
Alarm output (option)
OUT1 ......................... Control output or heating output (option)
OUT2 ......................... Cooling output (option)
TC .............................. Thermocouple input
RTD ........................... Resistance temperature detection input
DC .............................. Direct current input (DCA) or DC voltage input (DCV)
(For DC voltage input, + side terminal number differs depending on the voltage.
Also, DC current input, connect s shunt resistor between No. 10 and 12 terminal.)
CT1 ............................ Current transformer input 1 (option: Single, three phase)
CT2 ............................ Current transformer input 2 (option: Three-phase)
DI ............................... Contact input (option)
RS-485 ....................... Serial communication RS-485 (option)
KT (AKT2,4,7,8,9,4H,4B)
15
Communication Function Connection Diagram (PLC Connection Diagram)
3. KT4H/4B series
NOTICE ON OPERATION
1. KT2, 4, 8 and 9 series 2. KT7 series
Notes: 1. Terminating Resistors (Terminators)
The KT series has a built-in pull-up resistor or pull-down resistor, which
serves as the terminating resistor. For this reason, do not connect the
terminating resistor on the communication line.
2. Please use a RJ-116 polarized type modular connector.
Please use a cable that is suitable for a modular connector.
Shielded cable
RS-485
KT4
YA (–)
YB (+)
COM
13
14
15
KT8 , 9
YA (–)
YB (+)
COM
11
14
17
KT4
YA (–)
YB (+)
COM
13
14
15
KT2
YA (–)
YB (+)
COM
10
11
12
KT2
YA (–)
YB (+)
COM
10
11
12
KT8 , 9
YA (–)
YB (+)
COM
11
14
17
PLC
(–)
(+)
Communicatin cable
No.0
No.1
KT7
No.30
Terminal
3
to YB (+)
Terminal
4
to YA (–)
PLC
(–)
(+)
Shielded cable
RS-485
KT4H
16
YA ()
17
YB (+)
18
COM
KT4H
16
YA ()
17
YB (+)
18
COM
PLC
()
(+)
Notes:
1. To prevent current flow along shield sections, ground one end of the shield line. (If both ends of the
shield section are grounded, a closed circuit with the earth will form and electricity flowing through the
shield line will cause increased susceptibility to noise.)
2. Terminating Resistors (Terminators)
The KT4H series has a built-in pull-up resistor or pull-down resistor. For this reason, do not connect the
terminating resistor on the communication line.
1. NOTICE ON SITE SELECTION
This instrument is intended to be used in
the following environment (IEC61010-1)
Overvoltage category II, Pollution degree
2
Mount the controller in a place with:
1) A minimum of dust, and an absence of
corrosive gases
2) No flammable, explosive gases
3) Few mechanical vibrations or shocks
4) No exposure to direct sunlight, an
ambient temperature of 0 to 50°C (32 to
122°F) that does not change rapidly
(When installing inside a panel, make
particular allowance for heat dissipation.
Avoid installation in situations such as
above equipment that generates heat.)
5) Locations in which temperature rapidly
changes may cause condensation.
6) Locations or atmospheres in which
gasoline, thinners, alcohol, or other
organic solvents are present, or in which
ammonia, sodium hydroxide, or other
strong alkaline substances may adhere.
7) Locations susceptible to direct impact
or the transmission of vibrations, or
where splashing with water is possible.
8) In the proximity of equipment in which
large switching surges occur or near
high-voltage cables, high-voltage
equipment, power lines, power
equipment, ham radio transmitters, or
equipment containing these or similar
devices.
9) An ambient non-condensing humidity
of 35 to 85%RH
10) No large capacity electromagnetic
switches or cables through which large
current is flowing
11) No water, oil or chemicals or where
the vapors of these substances can come
into direct contact with the controller
2. NOTICE ON THE WIRING
1) The terminal block of KT4, 8, 9, 4H, 4B
series are designed to be wired from the
left side (KT2 series are designed to be
wired from the upper and lower direction).
The lead wire must be inserted from the
left side of the terminal, and fastened by
the terminal screw. Use a solderless
terminal with insulation sleeve that fits to
the M3 screw.
2) Terminal fastening torque is approxi-
mately 0.6N·m to 1.0N·m (KT4, 8, 9, 4H
and 4B).
For KT7 series by M3.0 screw is less
than 0.5N·m and by M2.0 screw 0.25N·m
respectively.
3) Use a thermocouple and
compensating lead wire according to the
input specification of the controller.
4) Use a 3-wire system of RTD according
to the input specification of the controller.
5) This controller has no built-in power
switch, circuit breaker or fuse. Therefore,
it is necessary to install them in the circuit
near the external controller.
(Recommended fuse: Time-lag fuse,
rated voltage 250V AC, rated current 2A)
6) In the case of 24V AC/DC power
supply, do not confuse the polarity when
it is DC.
7) With the relay contact output type, use
an auxiliary electromagnetic switch
externally according to the capacity of the
load to protect the built-in relay contact.
8) When wiring, keep input wire
(thermocouple, RTD, etc.) away from AC
source and load wire to avoid external
interference.
9) Turn the power supply to the
instrument off before wiring or checking.
Working or touching the terminal with the
power switched on may result in Electric
Shock which could cause severe injury or
death.
Wire-
pressed
terminal
Company
name
Part number
Fastening
torque
Fork type
NICHIFU
Co., Ltd.
1.25Y-3
0.6 Nm,
Max.
1.0 Nm.
J.S.T. Mfg.
Co., Ltd.
VD1.25-B3A
Round
type
NICHIFU
Co., Ltd.
1.25-3
J.S.T. Mfg.
Co., Ltd.
V1.25-3
3.2mm dia. 3.2mm
Max. 5.8mm Max. 5.8mm
.126inch dia. .126inch
.228inch .228inch

AKT7111100

Mfr. #:
Manufacturer:
Panasonic
Description:
CONTROL TEMP/PROCESS REL/SS OUT
Lifecycle:
New from this manufacturer.