NOTE: ANY COPY OF THIS DOCUMENT THAT DOES NOT HAVE A
RED “CONTROL” STAMP IS AN UNCONTROLLED COPY.
Page 6 SPECIFICATION 80, ISSUE 1
TABLE 1 (CONTINUED)
REQUIREMENTS FOR FINISHED WIRE AND CABLE
EXAMINATION OR TEST
REQUIREMENT
TEST
METHOD
TEST
TYPE 1
/
Finished Cable
Blocking
3.5.1 and MIL-C-27500
MIL-C-27500
Q
Cabling MIL-C-27500 MIL-C-27500 1
Conductor and Shield Continuity 3.5.3 and MIL-C-27500 MIL-C-27500 3
Crosslinking Proof Test Specification Sheet and 3.5.4 4.6.4 2
Dielectric Withstand Specification Sheet MIL-C-27500 3
Dimensions Specification Sheet 4.6.6 1
Flammability 3.5.5 4.6.7.1 Q
Identification of Product 3.5.6 4.6.6 1
Immersion 3.5.7 4.6.8 Q
Jacket Color 3.5.2 4.6.6 1
Jacket Concentricity 3.5.10 4.6.10 2
Jacket Elongation and Tensile Strength Specification Sheet 4.6.9 1
Jacket Flaws Specification Sheet and 3.5.11 4.6.11 3
Jacket Material and Construction 3.3.3 4.6.6 1
Jacket Thickness Specification Sheet 4.6.6 2
Life Cycle 3.5.12 4.6.12 Q
Low Temperature-Cold Bend 3.5.13 and MIL-C-27500 MIL-C-27500 Q
Secant Modulus 3.5.14 4.6.13 Q
Shield Material and Construction 3.3.2 MIL-C-27500 1
Shield Coverage Specification Sheet MIL-C-27500 1
Weight Specification Sheet 4.6.15 1
Workmanship MIL-C-27500 MIL-C-27500 1
1/ TEST TYPE:
Q - Qualification Test (4.2)
1 - Quality Conformance Test, Group 1 (4.3)
2 - Quality Conformance Test, Group 2 (4.3)
3 - Quality Conformance Test, Group 3 (4.3)
P - Process Control Inspection (4.4)
NOTE: ANY COPY OF THIS DOCUMENT THAT DOES NOT HAVE A
RED “CONTROL” STAMP IS AN UNCONTROLLED COPY.
SPECIFICATION 80, ISSUE 1 Page 7
3.5.2 Color
Color shall be in accordance with MIL-STD-104, Class 1. White is preferred for both
insulation and jacket. Color code designators, and colored stripes and bands, if used, shall
be in accordance with MIL-STD-681.
3.5.3 Conductor and Shield Continuity
When finished cable is tested in accordance with MIL-C-27500, there shall be no loss of
continuity in the conductors or shield.
3.5.4 Crosslinking Proof Test
When finished wire and cable is tested in accordance with 4.6.4, there shall be no cracking of
the insulation or jacket and no dielectric breakdown.
3.5.5 Flammability
3.5.5.1 Procedure 1
When qualification samples are tested in accordance with 4.6.7.1, the burn length shall not
exceed 3 inches (76 mm) and the afterburn time shall not exceed 3 seconds.
3.5.5.2 Procedure 2
When AWG 22 and 20 wire specimens are tested in accordance with 4.6.7.2, the burn length
shall not exceed 3 inches (76 mm) and the afterburn time shall not exceed 3 seconds.
3.5.6 Identification of Product
When specified, the finished wire and cable shall be identified by a marking applied to the
outer surface. The identification shall consist of the appropriate mark as specified by contract
or the applicable specification sheet. The mark shall be in a contrasting color to that of the
finished wire or cable. Identification shall be applied with the vertical axis of the characters
parallel to the longitudinal axis of the wire when the nominal diameter of the wire is 0.050
inch (1.27 mm) or smaller. The vertical axis of the characters may be either perpendicular or
parallel to the longitudinal axis of the wire when the nominal diameter of the wire exceeds
0.050 inch (1.27 mm). Wires with diameters of 0.035 inch (0.89 mm) and smaller shall not be
marked.
3.5.7 Immersion
When qualification samples are tested in accordance with 4.6.8, the diameter change shall be
no more than 5 percent, and there shall be no cracking of the insulation or jacket and no
dielectric breakdown.
3.5.8 Insulation Flaws
One hundred percent of finished wire shall pass the impulse dielectric test or the spark test of
MIL-W-22759 using the voltage specified in the applicable specification sheet. The test shall
be performed during the final winding of the wire on shipment spools or reels.
NOTE: ANY COPY OF THIS DOCUMENT THAT DOES NOT HAVE A
RED “CONTROL” STAMP IS AN UNCONTROLLED COPY.
Page 8 SPECIFICATION 80, ISSUE 1
3.5.9 Insulation Resistance
The minimum insulation resistance for 1000 feet of the wire specimens shall be 500 megohms
(152.4 M
-1 km) for AWG 22 and 20, and 100 megohms (30.5 M
-1 km) for AWG 8.
3.5.10 Jacket Concentricity
When finished cable is tested in accordance with 4.6.10, the jacket concentricity shall be 70
percent, minimum.
3.5.11 Jacket Flaws
One hundred percent of finished shielded and jacketed cable shall pass the jacket flaws test of
4.6.11 using the voltage specified in the applicable specification sheet.
3.5.12 Life Cycle
When tested in accordance with 4.6.12, using a test temperature of 230 ± 3°C for the AWG 8
specimen, and 200 ± 3°C for the other specimens, qualification samples shall exhibit no
cracking of the insulation or jacket and no dielectric breakdown.
3.5.13 Low Temperature-Cold Bend
When qualification samples are tested at -65 ± 3°C, there shall be no cracking of the insulation
or jacket and no dielectric breakdown.
3.5.14 Secant Modulus
When tested in accordance with 4.6.13, the secant modulus shall not exceed 5.0 x 10
4
lbf/in
2
(345 N/mm
2
) for AWG 22 and 20 wire specimens, or 4.0 x 10
4
lbf/in
2
(276 N/mm
2
) for cable
and AWG 8 wire specimens.
4. QUALITY ASSURANCE PROVISIONS
4.1 RESPONSIBILITY FOR INSPECTION
The supplier is responsible for the performance of all the inspection tests specified herein. The
supplier may utilize his own or any other inspection facility and services acceptable to the
buyer. Inspection records of the examination and tests shall be kept complete and available to
the buyer as required.
4.2 QUALIFICATION INSPECTION
Qualification inspection shall consist of all tests in Table 1, as applicable to finished wire or to
finished cable.