NOTE: ANY COPY OF THIS DOCUMENT THAT DOES NOT HAVE A
RED “CONTROL” STAMP IS AN UNCONTROLLED COPY.
Page 12 SPECIFICATION 80, ISSUE 1
TABLE 3
MANDREL DIAMETERS FOR CABLES FOR BEND TEST
(POST-ENVIRONMENTAL)
Finished Cable Diameter Mandrel Diameter
inch
mm
inch
mm
0.083
2.11
.750 19
> 0.083 and 0.111 >2.11 and
2.82
1.00 25
> 0.111 and 0.139 >2.82 and
3.53
1.25 32
> 0.139 and 0.194 >3.53 and
4.93
1.75 44
> 0.194 and 0.250 >4.93 and
6.35
2.25 57
> 0.250 and 0.334 >6.35 and
8.48
3.00 76
> 0.334 and 0.444 >8.48 and
11.3
4.00 102
> 0.444 and 0.556 >11.3 and
14.1
5.00 127
> 0.556 and 0.667 >14.1 and
16.9
6.00 152
> 0.667 and 0.889 >16.9 and
22.6
8.00 203
> 0.889 and 1.111 >22.6 and
28.2
10.0 254
> 1.111 and 1.556 >28.2 and
39.5
14.0 356
> 1.556 and 2.000 >39.5 and
50.8
18.0 457
4.6.2 Conductor and Finished Wire Diameter
Diameter measurements shall be made on a 24-inch (610-mm), minimum, length of finished
wire taken from the end of the sample unit. The conductor shall be made accessible by
stripping and removing the insulation carefully so as not to nick, cut, cold-work, or otherwise
damage the conductor. Three points for measurement shall be located 8 inches (203 mm) apart
along the conductor or finished wire specimen length, as applicable. For AWG 10 and smaller,
measure-ments shall be made at each point at two approximately perpendicular planes or as
required to assure that the minimum and maximum reading is attained at each point. A total of
six measure-ments shall be performed on each specimen. Measurements shall be made with a
micrometer caliper or equivalent device capable of resolving a measurement to 0.0001 inch
(0.0025 mm). For AWG 8 and larger, a circumferential measuring tape may be used in lieu of a
micrometer, and a total of three measurements, taken 8 inches (203 mm) apart, shall be
performed on each specimen. The circumferential measuring tape shall be capable of resolving
a measurement to 0.001 inch (0.025 mm) over a diameter range of 0.200 inch (5.08 mm) and
larger. The average diameter of all applicable measurements shall be calculated and recorded.
4.6.3 Conductor Elongation (High Strand Count)
High-strand-count conductors shall be tested for elongation in accordance with Method 3211
of FED-STD-228, except that the test shall be performed upon the whole conductor for regular
bunch-stranded constructions, and upon one whole member removed from rope bunch-
stranded constructions. In either case, elongation shall be measured upon breakage of the first
strand of the whole conductor or member, as applicable.
4.6.4 Crosslinking Proof Test
Crosslinking proof tests of finished wire and cable shall be conducted in accordance with the
life cycle test method of 4.6.12. The time and temperature specified for the crosslinking proof
test on the applicable specification sheet shall be used.
NOTE: ANY COPY OF THIS DOCUMENT THAT DOES NOT HAVE A
RED “CONTROL” STAMP IS AN UNCONTROLLED COPY.
SPECIFICATION 80, ISSUE 1 Page 13
4.6.5 Examination of Preparation for Delivery
Preparation for delivery of materials ready for shipment shall be examined to determine
compliance with the requirements of Section 5.
4.6.6 Examination of Product
All samples of wire and cable shall be examined to determine conformance with this specifica-
tion and the applicable specification sheet with regard to requirements not covered by specific
test methods.
4.6.7 Flammability
4.6.7.1 Procedure 1
Procedure 1 flammability testing shall be in accordance with ASTM F 777, with a flame
application period of 30 seconds. The procedure of ASTM F 777 conforms with FAR,
Part 25, Appendix F (g).
4.6.7.2 Procedure 2
(N/A for cable and AWG 8 wire samples)
The test shall be performed in a sheet metal cabinet conforming to FED-STD-191, Method
5903. Two inches (51 mm) of insulation shall be removed from one end of an 18-inch (457-
mm) specimen of finished wire and the specimen shall be mounted as shown in Figure 1. A
1.5-inch (38-mm) high yellow flame from a Bunsen burner conforming to FED-STD-191,
Method 5903, shall be applied to the specimen at the junction of the insulation and the bare
conductor in such a manner that the lower end of the insulation is located 0.75 inch (19 mm)
into the flame. After 12 seconds of flame application, the burner shall be removed from below
the specimen and immediately turned off. The burn length and the time of burning after
removal of the flame shall be recorded. The burn length shall be the distance from the original
bend made in the conductor to the farthest point of damage. Damage shall consist of bare
conductor and charred insulation. Light discoloration of the insulation shall not constitute
failure.
FIGURE 1 - Flammability Test Apparatus, Procedure 2
(shown without metal cabinet)
NOTE: ANY COPY OF THIS DOCUMENT THAT DOES NOT HAVE A
RED “CONTROL” STAMP IS AN UNCONTROLLED COPY.
Page 14 SPECIFICATION 80, ISSUE 1
4.6.8 Immersion
Specimens of sufficient length to perform the subsequent tests shall be measured at their
midpoints to determine their initial diameters, and shall then be immersed to within 6 inches
(152 mm) of their ends in each of the fluids (using a separate specimen for each fluid) for the
time and temperature specified in Table 4. During immersion, the radius of bend of the
specimens shall be not less than 14, nor more than 35, times the specified maximum diameter
of the wire or cable under test. Upon removal from the fluids, the specimens shall remain for 1
hour in free air at room temperature. The diameters shall then be remeasured at the original
point of measurement and compared to the initial diameters. The percent change in diameter
shall then be calculated. For finished wire, 1 inch (25 mm) of insulation shall be removed from
each end of a 24-inch (610-mm) length of each specimen. For finished cable, 2 inches (51 mm)
of the jacket shall be removed from each end of a 24-inch (610-mm) length of each specimen,
and the shield shall be pushed back and formed into a pigtail at each end of the specimen. One
inch (25 mm) of insulation of each of the primary wires shall then be removed from each end
of the specimen. The specimens shall then be subjected to the bend test (4.6.1 - use the
mandrels and test weights specified on the applicable specification sheet for the Crosslinking
Proof Test), followed by the voltage withstand test (4.6.14).
TABLE 4
IMMERSION TEST FLUIDS
TEST FLUID
TEST TEMPERATURE
IMMERSION
TIME
(a) MIL-L-23699, Lubricating Oil, Aircraft Turbine
Engine,Synthetic Base
48 to 50°C (118 to 122°F) 20 hours
(b) MIL-H-5606, Hydraulic Fluid, Petroleum Base,
Aircraft, Missile and Ordnance
48 to 50°C (118 to 122°F) 20 hours
(c) TT-I-735, Isopropyl Alcohol 20 to 25°C (68 to 77°F) 168 hours
(d) MIL-T-5624, Turbine Fuel, Aviation, Grade JP-4
or JP-8
20 to 25°C (68 to 77°F) 168 hours
(e) SAE-AS-1241, Fire Resistant Phosphate Ester
Hydraulic Fluid for Aircraft
48 to 50°C (118 to 122°F) 20 hours
(f) MIL-L-7808, Lubricating Oil, Aircraft Turbine
Engine, Synthetic Base; or NATO 148
118 to 121°C (244 to 250°F)
30 minutes
4.6.9 Insulation Elongation and Tensile Strength
Specimens of the entire insulation shall be carefully removed from the conductor and tested for
tensile strength and elongation in accordance with FED-STD-228, Methods 3021 and 3031,
respectively, using 1-inch (25-mm) bench marks, a 1-inch (25-mm) initial jaw separation, and a
jaw separation speed of 2 inches (51 mm) per minute. For cables, the method shall be the same,
but only the cable jacket shall be tested.
4.6.10 Jacket Concentricity
The concentricity of the cable jacket shall be determined by first locating and recording the
minimum wall thickness measured on a cross-section of the jacket. The maximum wall thick-
ness of this same cross-section of the jacket shall also be measured and recorded. The ratio of
the minimum wall thickness to the maximum wall thickness shall define the concentricity. All
wall-thickness measurements shall be made under suitable magnification. The wall thickness
shall be the radial distance between the inner and outer rim of the jacket.

82A0111-22-F868-9CS2920

Mfr. #:
Manufacturer:
Raychem / TE Connectivity
Description:
Hook-up Wire 82A011122F8689CS2920 PRICE PER FOOT
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet