https://www.phoenixcontact.com/us/products/2702131
05/15/2015Page4/6
Bus coupler-IL EIP BK DI8 DO4 2TX-XC-PAC-2702131
Technical data
Inline potentials
Segment supply voltage U
S
24 V DC
Supply voltage range U
S
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at U
S
max. 8 A DC (Sum of U
M
+ U
S
)
Current consumption from U
S
max. 8 A DC
I/O supply voltage U
ANA
24 V DC
Supply voltage range U
ANA
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply at U
ANA
max. 0.5 A DC
Digital inputs
Input name Digital inputs
Connection method Inline connector
2, 3-wire
Number of inputs 8
Typical response time approx. 500 µs
Protective circuit Protection against polarity reversal Suppressor diode
Input characteristic curve IEC 61131-2 type 1
Input voltage 24 V DC
Input voltage range "0" signal -30 V DC ... 5 V DC
Input voltage range "1" signal 15 V DC ... 30 V DC
Nominal input current at U
IN
typ. 3 mA
Typical input current per channel typ. 3 mA
Delay at signal change from 0 to 1 1.2 ms
Delay at signal change from 1 to 0 1.2 ms
Digital outputs
Output name Digital outputs
Connection method Inline connector
2, 3-wire
Number of outputs 4
Protective circuit Short-circuit and overload protection Free running circuit
Output voltage 24 V DC -1 V (At nominal current)
Nominal output voltage 24 V DC
Maximum output current per channel 500 mA
Maximum output current per module / terminal block 2 A
Maximum output current per module 2 A
Nominal load, inductive 12 VA (1.2 H; 48 Ω)
Nominal load, lamp 12 W