6
Table 1. IEC/EN/DIN EN 60747-5-2 Insulation Characteristics*
Description Symbol
ACPL-772L
Option 060
ACPL-072L
Option 060 Units
Installation classification per DIN VDE 0110/1.89, Table 1
for rated mains voltage ≤ 150 Vrms
for rated mains voltage ≤ 300 Vrms
for rated mains voltage ≤ 450 Vrms
I – IV
I – IV
I – III
I – IV
I – III
Climatic Classification 55/105/21 55/105/21
Pollution Degree (DIN VDE 0110/1.89) 2 2
Maximum Working Insulation Voltage V
IORM
630 560 V
peak
Input to Output Test Voltage, Method b**
V
IORM
x 1.875=V
PR
, 100% Production Test with t
m
=1 sec,
Partial discharge < 5 pC
V
PR
1181 1050 V
peak
Input to Output Test Voltage, Method a**
V
IORM
x 1.5=V
PR
, Type and Sample Test, t
m
=60 sec, Partial discharge < 5 pC
V
PR
945 840 V
peak
Highest Allowable Overvoltage (Transient Overvoltage t
ini
= 10 sec) V
IOTM
6000 4000 V
peak
Safety-limiting values – maximum values allowed in the event of a failure,
also see Figure 2.
Case Temperature
Input Current
Output Power
T
S
I
S, INPUT
P
S, OUTPUT
175
230
600
150
150
600
°C
mA
mW
Insulation Resistance at T
S
, V
IO
= 500 V R
IO
>109 >109
W
* Isolation characteristics are guaranteed only within the safety maximum ratings which must be ensured by protective circuits in application.
Surface mount classification is class A in accordance with CECCOO802.
** Refer to the optocoupler section of the Isolation and Control Components Designer’s Catalog, under Product Safety Regulations section IEC/EN/
DIN EN 60747-5-2, for a detailed description of Method a and Method b partial discharge test profiles.
Note: These optocouplers are suitable for “safe electrical isolation” only within the safety limit data. Maintenance of the safety data shall be ensured
by means of protective circuits.
Note: The surface mount classification is Class A in accordance with CECC 00802.
Table 2. Insulation and Safety Related Specifications
Parameter Symbol
Value
Units Conditions
ACPL-
772L ACPL-072L
Minimum External
Air Gap (Clearance)
L(101) 7.1 4.9 mm Measured from input terminals to output termi-
nals, shortest distance through air.
Minimum External
Tracking (Creepage)
L(102) 7.4 4.8 mm Measured from input terminals to output termi-
nals, shortest distance path along body.
Minimum Internal Plastic
Gap (Internal Clearance)
0.08 0.08 mm Through insulation distance conductor to con-
ductor, usually the straight line distance thickness
between the emitter and detector.
Tracking Resistance
(Comparative Tracking Index)
CTI >175 >175 V DIN IEC 112/VDE 0303 Part 1
Isolation Group IIIa IIIa Material Group (DIN VDE 0110, 1/89, Table 1)
All Avago Technologies data sheets report the creepage and clearance inherent to the optocoupler component itself. These dimensions are needed as
a starting point for the equipment designer when determining the circuit insulation requirements. However, once mounted on a printed circuit board,
minimum creepage and clearance requirements must be met as specified for individual equipment standards. For creepage, the shortest distance
path along the surface of a printed circuit board between the solder fillets of the input and output leads must be considered.
There are recommended techniques such as grooves and ribs which may be used on a printed circuit board to achieve desired creepage and clearances.
Creepage and clearance distances will also change depending on factors such as pollution degree and insulation level.