PHOENIX CONTACT page 4 of 8
11
11
AC input:
Input voltage 85 - 264 V AC
Frequency 45 - 65 Hz
(0.2 mm
2
to 2.5 mm
2
solid)
(0.2 mm
2
to 2.5 mm
2
flexible)
(24 - 14 AWG)
Internal fuse 2 AT
Recommended fuse
10 A or 16 A c.b./Characteristic B
22
22
DC output:
Output voltage 5 V DC (default),
can be set from 4.5 - 5.5 V DC using
a potentiometer
3
(0.2 mm
2
to 2.5 mm
2
solid)
(0.2 mm
2
to 2.5 mm
2
flexible) (AWG 24 - 14)
The device is idling-proof and short-circuit-proof.
33
33
Potentiometer 4.5 - 5.5 V DC
44
44
DC OK LED
55
55
Universal latching foot for EN DIN rails
5. Safety and Warning Instructions
To ensure safe operation of the device and that
all functions can be used, please read these
instructions carefully.
Caution: Never carry out work when the
power is turned on, this is highly
dangerous.
Figure 04
5 6 7 8
L NC NC N
MINI POWER
L(+)
N(-)
DC
OK
NC
NC
+
–
–
+
IN 100-240 V AC
OUT 5 V DC
4.5-5.5
V DC
MINI-PS-100-240AC/5DC/3
Order No.: 29 38 71 4
U
INDUSTRIAL
CONTROL
EQUIPMENT
43KA
LISTED
APPROV
ALS
u
INFORMATION
TECHNOLOGY
EQUIPMENT
Power Supply
INPUT
OUTPUT
AC:
100-240V
50-60Hz
Range:
85-264V
0.4-0.2A
DC:
90-350V
0.4-0.2A
5V DC
±1%
3A
R
e
a
d
i
n
s
t
a
l
l
a
t
i
o
n
i
n
s
t
r
u
c
t
i
o
n
s
b
e
f
o
r
e
c
o
n
n
e
c
t
i
n
g
t
o
m
a
i
n
s
www.interface.phoenixcontact.com
TEMPERA
TURE
- 25 … + 60 °C
- 13 … + 140 °F
–25
2
1
4
3
5
Power Supply, Primary Switch Mode, Narrow Design – MINI-PS-100-240AC/5DC/3
4. Device View, Connections, and Control Elements
Installation and startup
must only be carried out by
qualified personnel. The relevant country-specific
regulations (e.g., VDE, DIN) must also be observed.
Before startup it is particularly important to ensure
that:
• The line has been connected correctly and protection
is provided against electric shock.
• The device can be switched off outside the power
supply according to EN 60950 regulations (e.g., by
the line protection on the primary side).
• All supply lines have sufficient fuse protection and
are the correct size.
• All output cables are the correct size for the maximum
device output current or have separate fuse
protection.
• Sufficient convection is ensured.
MINI POWER is a built-in device. After installation
the terminal area must be covered to provide sufficient
protection against unauthorized access to live parts.
This is ensured by installing the device in the control
cabinet or distributor box.
The device contains dangerous live components
and high levels of stored energy.