PHOENIX CONTACT page 3 of 8
Power Supply, Primary Switch Mode, Narrow Design – MINI-PS-100-240AC/24DC/4
General Data
Insulation voltage: Input/output
Approval package
Electrical equipment of machines
Safety transformers for switched-mode power supply units
Electrical safety
(of IT equipment)
Industrial control equipment
Equipping high voltage installations
with electronic equipment
Safety extra-low voltage
Safe isolation
Protection against dangerous shock currents,
basic requirements for safe isolation
in electrical equipment
Limitation of harmonic line currents
Mounting position
Can be mounted with spacing - Vertical
- Horizontal
Degree of protection
Class of protection
MTBF
Housing version
Weight
Dimensions (W x H x D)
Climatic Data
Ambient temperature Operation
Storage
Humidity
Vibration according to IEC 68-2-6
Shock according to IEC 68-2-27
Degree of pollution
Climatic category
cc
cc
Conforms to the EMC Directive 89/336/EEC and the
Low Voltage Directive 73/23/EEC
EMC (Electromagnetic Compatibility)
Noise Immunity According to EN 61000-6-2:
Electrostatic discharge
(ESD)
EN 61000-4-2
3)
Housing
Contact discharge:
Air discharge:
Electromagnetic
HF field
EN 61000-4-3
2)
Housing
Frequency:
Field strength:
Fast transients
(burst)
EN 61000-4-4
3)
Input:
Output:
Signal:
Surge current loads EN 61000-4-5
3)
Input:
Output:
Conducted
interference
EN 61000-4-6
2)
I/O/S:
Frequency:
U
0
:
Voltage dips EN 61000-4-11
3)
Input:
Simulation of
radiophone
EN 50204 Frequency:
Field strength:
Noise Emission According to EN 50081-2:
Radio interference EN 55011
Radio interference EN 55011
EN 55011 corresponds to CISPR11/EN 55022 corresponds to
CISPR22
EN 61000 corresponds to IEC 1000
2)
Criterion A: Normal operating characteristics within the specified
limits.
3)
Criterion B: Temporary adverse effects on the operating
characteristics that the device corrects independently.
3 kV AC (type test)/3 kV AC (routine test)
EN 60 204 (Surge Voltage Category III)
EN 61 558-2-17
EN 60950 / VDE 0805
UL/C-UL Recognized UL 60 950
u
1)
UL/C-UL Listed UL 508
1)
EN 50 178/VDE 0160
PELV (EN 60 204)
SELV (EN 60 950)
VDE 0100-410
DIN VDE 0106-101
According to EN 61000-3-2
On horizontal NS 35 DIN rail according to EN 50022
≥
5 cm (1.969 in.)
0 cm
IP 20
ΙΙ
, (in closed control cabinets)
> 500 000 h according to IEC 1709 (SN 29 500)
Polyamide PA, color green
0.4 kg, approximately
67.5 x 99 x 114.5 mm (2.657 x 3.898 x 4.508 in.)
-25°C to +70°C (-13°F to +158°F) (> +60°C [+140°F] derating)
-40°C to +85°C (-40°F to +185°F)
Up to 95% at +25°C (+77°F), no condensation
< 15 Hz, amplitude ±2.5 mm/15 Hz - 150 Hz, 2.3 g
30 g all space directions
2 (according to EN 50 178)
3K3 (according to EN 60 721)
1)
UL approval for ambient tempertatunre up to +60 °C (+140 °F)
Requirements
EN 61 000-6-2 MINI-PS-100-240AC/24DC/4
4 kV
8 kV
> Level 3
8 kV
8 kV
80 - 1000 MHz
10 V/m
Level 3
80 - 1000 MHz
10 V/m
2 kV asymmetrical
5)
2 kV asymmetrical
5)
1 kV asymmetrical
5)
4 kV (Level 4)
2 kV (Level 3)
1 kV (Level 2)
2 kV asymmetrical
5)
1 kV symmetrical
4)
0.5 kV asymmetrical
5)
0.5 kV symmetrical
4)
1 kV asymmetrical
5)
4 kV (Level 4)
2 kV (Level 4)
0.5 kV (Level 1)
0.5 kV (Level 1)
0.5 kV (Level 1)
asymmetrical
5)
0.15 - 80 MHz
10 V
Level 3
0.15 - 80 MHz
10 V
30% reduction of the input voltage
for 0.5 periods
See input data:
Mains buffering
> 20 ms
Not required 900 MHz/1800 MHz
20 V/m
Class A
6)
EN 55011 (EN 55022) Class B
7)
Class A
6)
EN 55011 (EN 55022) Class B
7)
4)
symmetrical: Cable to cable
5)
asymmetrical: Cable to ground
6)
Class A: Industrial application
7)
Class B: Industrial and domestic applications