PHOENIX CONTACT page 4 of 8
11
11
AC input:
Input voltage 85 - 264 V AC
Frequency 45 - 65 Hz
(0.2 mm
2
to 2.5 mm
2
solid)
(0.2 mm
2
to 2.5 mm
2
flexible)
(25 - 14 AWG)
Internal fuse T3.15 AL 250 V
Recommended fuse
6 A or 10 A c.b./Characteristic B
22
22
DC output:
Output voltage 24 V DC (default),
can be set from 22.5 - 28.5 V DC using
a potentiometer
4
(0.2 mm
2
to 2.5 mm
2
solid)
(0.2 mm
2
to 2.5 mm
2
flexible) (25 - 14 AWG)
The device is idling-proof and short-circuit-proof.
33
33
DC OK output active
44
44
Potentiometer 22.5 - 28.5 V DC
55
55
DC OK LED
66
66
Universal latching foot for EN DIN rails
5. Safety and Warning Instructions
To ensure that the device can be operated safely
and all functions can be used, please read these
instructions carefully.
Caution: Never carry out work when the
power is turned on, this is highly
dangerous.
L(+) N(-)
MINI-PS-100-240AC/24DC/4
Order No.: 29 38 8
3
7
U
INDUSTRIAL
CONTROL
EQUIPMENT
1YD8
LISTED
APPROV
ALS
u
INFORMATION
TECHNOLOGY
EQUIPMENT
Power Supply
INPUT
OUTPUT
AC:
100-240V
50-60Hz
Range:
85-264V
1.6-0.7A
DC:
90-350V
1.3-0.4A
24V DC
±1%
4A
R
e
a
d
i
n
s
t
a
l
l
a
t
i
o
n
i
n
s
t
r
u
c
t
i
o
n
s
b
e
f
o
r
e
c
o
n
n
e
c
t
i
n
g
t
o
m
a
i
n
s
www.interface.phoenixcontact.com
TEMPERA
TURE
- 25 … + 60 °C
- 13 … + 140 °F
–25
MINI POWER
DC
OK
OUT DC 24V 4 A
22.5-28.5
V DC
L(+)
N(-)
IN AC 100-240 V
+
+
DC
OK
–
–
–
2
1
5
4
5
Figure 04
3
Power Supply, Primary Switch Mode, Narrow Design – MINI-PS-100-240AC/24DC/4
4. Device View, Connections, and Control Elements
Installation and startup
must only be carried out by
qualified personnel. The relevant country-specific
regulations (e.g., VDE, DIN) must also be observed.
Before startup it is particularly important to ensure
that:
• The mains have been connected correctly and
protection is provided against electric shock.
• The device can be switched off outside the power
supply according to EN 60950 regulations (e.g., by
the line protection on the primary side).
• All supply lines have sufficient fuse protection and
are the correct size.
• All output cables are the correct size for the maximum
device output current or have separate fuse
protection.
• Sufficient convection is ensured.
MINI POWER is a built-in device. After installation
the terminal area must be covered to provide sufficient
protection against unauthorized access to live parts.
This is ensured by installing the device in the control
cabinet or distributor box.
The device contains dangerous live components
and high levels of stored energy.