LTC3562
13
3562fa
Table 1. Write Word Protocol Used by the LTC3562
171181811
S Slave Address WR A
*Sub-Address
A Data Byte A P**
S = Start Condition, WR = Write Bit = 0, A = Acknowledge, P = Stop Condition
* The sub-address uses only the fi rst four most signifi cant bits, A7, A6, A5, and A4, for sub-addressing. The two least signifi cant bits, A1 and A0, are
used to program the regulator operating mode.
**Stop can be delayed until all of the data registers have been written.
Table 2. Sub-Address and Data Byte Mapping
SUB-ADDRESS BYTE DATA BYTE
A7 A6 A5 A4 A3 A2 A1 A0 B7 B6 B5 B4 B3 B2 B1 B0
PROGRAM
R600A
PROGRAM
R400A
PROGRAM
R600B
PROGRAM
R400B
NOT USED REGULATOR
OPERATING
MODE
(SEE TABLE 3)
ENABLE
REGULATOR
DAC CODE
(See Tables 4, 5 and 6)
Figure 3. Bit Assignments
Figure 4. Timing Parameters
OPERATION
ACK
123
ADDRESS WR
456789123456789123456789
1100101 0
11001010
A7 A6 A5 A4 A3 A2 A1 A0
A7 A6 A5 A4 A3 A2 A1 A0
B7 B6 B5 B4 B3 B2 B1 B0
76543210
ACK
STOPSTART
SDA
SCL
ACK
SUB-ADDRESS
DATA BYTE
3562 F03
t
SU, DAT
t
HD, STA
t
HD, DAT
SDA
SCL
t
SU, STA
t
HD, STA
t
SU, STO
3562 F04
t
BUF
t
LOW
t
HIGH
START
CONDITION
REPEATED START
CONDITION
STOP
CONDITION
START
CONDITION
t
r
t
f
t
SP
LTC3562
14
3562fa
If a Type-A regulator is being programmed, then bits B3
through B0 program the DAC that controls the regulators
feedback servo voltage. This 4-bit sequence programs the
feedback voltage from 425mV to 800mV in 25mV incre-
ments (Table 4). Bits B6 through B4 are not used when
programming a Type-A regulator.
If a Type-B regulator is being programmed, then bits B6
through B0 program the DAC that controls the regulators
output voltage. This 7-bit sequence programs the output
voltage from 600mV to 3.775V in 25mV increments
(Tables 5 and 6).
Bus Write Operation
The master initiates communication with the LTC3562 with
a start condition and a 7-bit address followed by the write
bit R/W = 0. If the address matches that of the LTC3562,
the LTC3562 returns an Acknowledge. The master should
then deliver the sub-address byte for the regulator(s)
being programmed. Again the LTC3562 acknowledges
and then the data byte is delivered starting with the most
signifi cant bit. The data byte and the two mode bits in the
sub-address byte are transferred to an internal holding
latch for each programmed regulator upon the return
of an Acknowledge. After the sub-address byte and data
byte have been transferred to the LTC3562, the master
may terminate the communication with a stop condition.
Alternatively, a repeat-start condition can be initiated by
the master and the entire sequence can be repeated, this
time accessing a different sub-address code to program
another regulator. Likewise, the master can also initiate a
Repeat-Start so that another chip on the I
2
C bus can be
addressed. This cycle can continue indefi nitely and the
LTC3562’s regulators will remember the last input of valid
data that it received. Once all chips on the bus have been
addressed and sent valid data, a global stop condition can
be sent and the LTC3562 will update its regulators with
the data that it had received.
In certain circumstances the data on the I
2
C bus may
become corrupted. In these cases the LTC3562 responds
appropriately by preserving only the last set of complete
data that it has received. For example, assume the LTC3562
has been successfully addressed and is receiving data
when a stop condition mistakenly occurs. The LTC3562
will ignore this stop condition and will not respond until a
new start condition, correct address, new set of data and
stop condition are transmitted.
Likewise, with only one exception, if the LTC3562 was
previously addressed and sent valid data but not updated
with a Stop, it will respond to any Stop that appears on
the bus, independent of the number of Repeat-Starts that
have occurred. If a Repeat-Start is given and the LTC3562
successfully acknowledges its address, it will not respond
to a Stop until all three bytes of the new data have been
received and acknowledged.
I
2
C Examples
To program R600A in forced Burst Mode operation with
its feedback servo voltage set to 600mV:
Sub-Address Byte – 1000XX10
Data Byte – 1XXX0111
To program R600B and R400B in LDO mode with their
output voltages set to 1.250V:
Sub-Address Byte – 0011XX01
Data Byte – 10011010
To put the entire chip in shutdown and disable all regula-
tors:
Sub-Address Byte – 1111XXXX
Data Byte – 0XXXXXXX
Disabling the I
2
C Port
The I
2
C serial port can be disabled by grounding the DV
CC
pin. In this mode, regulators R600A and R400A can only be
activated through the individual logic input pins RUN600A
and RUN400A. Disabling the I
2
C port also resets the feed-
back servo voltages to the default setting of 0.8V.
Note that if the I
2
C port gets disabled while a Type-A
regulator is enabled and its RUN pin is activated, the
regulator will remain enabled and its feedback voltage will
immediately be reset to the default setting of 0.8V. If the
I
2
C port gets disabled and the RUN pins are not activated,
then the regulators will immediately go into shutdown
mode. Since regulators R600B and R400B do not have
RUN pins, they immediately go into shutdown once the
I
2
C port gets disabled.
OPERATION
LTC3562
15
3562fa
Table 5. Type-B Regulator Base Output Voltage Programming
B6 B5 B4 B3 B2
TYPE-B REGULATOR
BASE OUTPUT VOLTAGE
00000 0.600
00001 0.700
00010 0.800
00011 0.900
00100 1.000
00101 1.100
00110 1.200
00111 1.300
01000 1.400
01001 1.500
01010 1.600
01011 1.700
01100 1.800
01101 1.900
01110 2.000
01111 2.100
10000 2.200
10001 2.300
10010 2.400
10011 2.500
10100 2.600
10101 2.700
10110 2.800
10111 2.900
11000 3.000
11001 3.100
11010 3.200
11011 3.300
11100 3.400
11101 3.500
11110 3.600
11111 3.700
Table 4. Type-A Regulator Servo Voltage Programming
B3 B2 B1 B0
TYPE-A REGULATOR
SERVO (FEEDBACK) VOLTAGE
0000 0.425
0001 0.450
0010 0.475
0011 0.500
0100 0.525
0101 0.550
0110 0.575
0111 0.600
1000 0.625
1001 0.650
1010 0.675
1011 0.700
1100 0.725
1101 0.750
1110 0.775
1111 0.800
Table 3. Regulator Operating Modes
A1 A0 REGULATOR MODE
0 0 Pulse Skip Mode
0 1 LDO Mode
1 0 Forced Burst Mode Operation
1 1 Burst Mode Operation
Table 6. Type-B Regulator Incremental Output Voltage Programming
B1 B0 TYPE-B REGULATOR INCREMENTAL OUTPUT VOLTAGE
0 0 +0.000
0 1 +0.025
1 0 +0.050
1 1 +0.075
POR600A Pin
The POR600A pin is an open-drain output used to indicate
that regulator R600A has been enabled and has reached
its fi nal voltage. POR600A remains low impedance until
regulator R600A reaches 92% of its regulation value. A
230ms delay is included to allow a system microcontroller
ample time to reset itself. POR600A may be used as a
power on reset to the microprocessor powered by regula-
tor R600A or may be used to enable regulator R400A for
supply sequencing. POR600A is an open drain output and
requires a pull-up resistor to the output voltage of regulator
R600A or another appropriate power source.
OPERATION

LTC3562EUD#PBF

Mfr. #:
Manufacturer:
Analog Devices / Linear Technology
Description:
Switching Voltage Regulators Quad Synch Step-Down DC/DC Regulator
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet