J7KNA-09-01 24D

11 Mini Motor Contactor J7KNA
Mini Motor Contactor
Main contactor
• AC & DC operated
• Integrated auxiliary contacts
• Screw fixing and snap fitting ( 35 mm DIN rail )
• Range from 4 to 5.5 kW ( AC 3 ,380/415V )W ( AC 3 ,380/415V )
• 4 -main pole version ( 4 kW AC and DC coil )
• Auxiliary contacts suitable for electronic devices ( DIN 19240 )N 19240 )
• Finger proof ( VBG 4)
Accessoires
• 2 and 4 pole additional auxiliary contacts in different
configurations
• Mechanical interlock
• Suppressors
)
Approved Standardstandards
Ordering Informationg Information
Model Number Legendber Legend
1. Mini Motor Contactors
1) Mini Contactor
2) Rated Motor Current (AC3 400V)
09: 9A
12: 12A
3) Integrated auxiliary contact
10: 1 NC 0 NC
01: 0 NO 1NC
4: 4 main pole type (no aux contact)
4) Coil voltage ( AC operated )
24: AC24V 50/60Hz
48: AC48-50V 50Hz,AC48V 60Hz
60: AC60V 50Hz
90: AC100V 50/60Hz
110: AC110-115V 50Hz,AC120-125V 60Hz
180: AC200V 50/60Hz
230: AC220-230V 50Hz,AC240V 60Hz
240: AC230V-240V 50Hz
400: AC380-400V 50Hz,AC440V 60Hz
415: AC400-415V 50Hz
550: AC525-550V 50Hz,AC600V 60Hz
Coil voltage ( DC operated )DC operated )
24D: DC24V
48D: DC48V
110D: DC110V
125D: DC125V
24VS: DC24V with diode
48VS: DC48V with diode
110VS: DC110V with diode
125VS: DC125V with diode
2. Aux. Contact Modules for Mini Motor Contactors
1) Auxiliary Contact Modules
2) AM: for mini motor contactor
3) Combination of NO/NC contacts
11: 1 NO 1 NC
02: 0 NO 2 NC
22: 2 NO 2 NC
40: 4 NO 0 NC
Standard Guide No (US,C)
UL NLDX, NLDX7X, NLDX7
ICE 947-5-1
VDE 0660
EN 60947-5-1
J7KNA-##-##-#####
123 4
J73KN-##-##
123
12 Mini Motor Contactor J7KNA
System overviewystem overvieww
Mini Motor Contactors
AC Operated
DC Solenoid Operated
Auxiliary contact blocks with screw terminals for contactors J7KNA-09... and J7KNA-12...with screw terminals for contactors J7KNA-09... and J7KNA-12...A-09... and J7KNA-12...
Ratings Rated Current Aux. Contacts Type Pack Weight
AC2, AC3 AC3 AC1
380V
400V
415V
kWW
500V
kW
660V
690V
kW
400V
A
690V
ANONC
Accept pt
Overlod
Relay see
page 52
Coil Voltage
*1
24 24V 50/60Hz
230 220-230V 50Hz pcs. kg/pc.
3-pole, With Screw Terminals
4 449201- J7TKN-A J7KNA-09-10-##### 10 0.16
5.5 5.5 5.5 12 20 1 - J7TKN-A J7KNA-12-10-##### 10 0.16
4 44920- 1J7TKN-A J7KNA-09-01-##### 10 0.16
5.5 5.5 5.5 12 20 - 1 J7TKN-A J7KNA-12-01-##### 10 0.16
4-pole, With Screw Terminals
4 44920- - J7TKN-A J7KNA-09-4-#####
*1)Other coil voltages see page 14
Ratings Rated Current Aux. Contacts Type Pack Weight
AC2, AC3 AC3 AC1
380V
400V
415V
kW
500V
kW
660V
690V
kW
400V
A
690V
ANONC
Accept
Overlod
Relay see
page 52
DC Coil Voltage
24DD 24V 50/60Hz
24VS
*1
24V 50/60Hz w. diode
*2
pcs. kg/pc.
3-pole, With Screw Terminals
4 449201- J7TKN-A J7KNA-09-10-###D(-VS) 10 0.19
5.5 5.5 5.5 12 20 1 - J7TKN-A J7KNA-12-10-###D(-VS) 10 0.19
4 44920- 1J7TKN-A J7KNA-09-01-###D(-VS) 10 0.19
5.5 5.5 5.5 12 20 - 1 J7TKN-A J7KNA-12-01-###D(-VS) 10 0.19
*1)with built-in coil suppressor (varistor)
*2)with built-in coil suppressor (diode with zener diode)
Contacts Rated Current Thermal Rated Currentd Current Type Pack Weight
NO NC
AC15
230V
A
400V
A A pcs. kg/pc.
1 1 3210 J73KN-AM-11 10 0.04
- 2 3210 J73KN-AM-02 10 0.04
2 2 3210 J73KN-AM-22 10 0.04
Mini Motor Contactor J7KNA 13
System overviewverview
Mini Motor Contactorstor Contactors
AC Operated
DC Solenoid Operated
Auxiliary contact blocks with screw terminals for contactors J7KNA-09... and J7KNA-12...ew terminals for contactors J7KNA-09... and J7KNA-12...09... and J7KNA-12...
Wiring Diagrams Auxiliary Contact Blocks Contactor with Auxiliary Contact
Contacts suitable for Electronic
Circuits according to DIN 19240
for rated voltage 24V DC
(test ratings 17V DC, 5mA) 7V DC, 5mA)
Positively guided contacts
Block
Distinc. Number
according to DIN
EN 50012 Type NO NC
Distinc. Number
according to DIN
EN 50012 NO NC
3-pole, With Screw Terminals
10
J73KN-AM-11 1121 21
Prefered combinations according
to DIN EN 50012
J73KN-AM-02 0212 12
J73KN-AM-22 2232 32
01
J73KN-A-11 11- 12
Contacts according to
DIN EN 50005
J73KN-A-02 02- 03
J73KN-A-40 40- 41
J73KN-A-22 22- 23
4-pole, With Screw Terminals
00
J73KN-A-11 11- 11
Contacts according to
DIN EN 50005
J73KN-A-02 02- 02
J73KN-A-40 40- 40
J73KN-A-22 22- 22
1
2
3
4
5
6
7
8
A1
A2
Wiring Diagrams Auxiliary Contact Blocks Contactor with Auxiliary Contact with Auxiliary Contact
Contacts suitable for Electronic
Circuits according to DIN 19240
for rated voltage 24V DC
(test ratings 17V DC, 5mA)
Positively guided contacts
Block
Distinc. Number
according to DIN
EN 50012 Typepe NO NC
Distinc. Number
according to DIN
EN 50012 NO NC
3-pole, With Screw Terminals
10
J73KN-AM-11 1121 21
Prefered combinations according
to DIN EN 50012
J73KN-AM-02 0212 12
J73KN-AM-22 2232 32
01
J73KN-A-11 11- 12
Contacts according to
DIN EN 50005
J73KN-A-02 02- 03
J73KN-A-40 40- 41
J73KN-A-22 22- 23
Wiring Diagrams Contacts suitable for Electronic
Circuits according to DIN 19240
for rated voltage 24V DC
(test ratings 17V DC, 5mA)
Positively guided contacts
J73KN-AM-11 J73KN-AM-02 J73KN-AM-22 J73KN-A-11 J73KN-A-02 J73KN-A-40 J73KN-A-22

J7KNA-09-01 24D

Mfr. #:
Manufacturer:
Description:
Industrial Relays Contacto
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union