FLM DI 8 M12
4 697000
Local LED Diagnostic and Status Indicators
Figure 7 LED diagnostic and status
indicators of the FLM DI 8 M12
F L M D I 8
I N
L B
D
U S
L B
O U T
U
L S
I 2
I 4
I 6
I 8
I 1
I 3
I 5
I 7
U
L S
D
X
X
6 9 7 0 A 0 0 3
X
X
X
X
X
X
X X
X X
X X
X X
E
U S
Des. Color Meaning
D Green
LED
Diagnostics
ON: Bus active
Flashing,
0.5 Hz:
Communications power
present, bus not active
Flashing,
2 Hz:
Communications power
present, bus active,
I/O error
Flashing,
4 Hz:
Communications power
present,
transmission path to the left of
the flashing device failed,
device to the left of the
flashing device failed,
devices to the right of the
flashing device are not part of
the configuration frame
OFF: Communications power not
present, bus not active
US Green
LED
Voltage supply for inputs
IN1 to IN8
ON: Voltage supply present
OFF: Voltage supply too low
E Red LED Overload of
voltage supply U
S
ON: Voltage supply overloaded
OFF: Voltage supply not
overloaded
XX Yellow
LED
Status indicators of the
inputs
ON: Input active
OFF: Input not active
FLM DI 8 M12
697000 5
Internal Circuit Diagram
Figure 8 Internal wiring of the connection
points
For information on electrically
isolated areas, please refer to
page 11.
6 9 7 0 A 0 0 4
8
O P C
#
#
#
#
2 4 V
5 V
#
#
#
#
U
L S
I N
L B I N
L B O U T
U
L S
O U
T
Key:
Functional earth ground
Protocol chip
(bus logic including
voltage conditioning)
Power supply unit with electrical
isolation
Optocoupler
LED
Input
Electrically isolated area
OPC
2 4 V
5 V
FLM DI 8 M12
6 697000
Connection Example
Figure 9 Typical connection of sensors
Connection Notes
6 9 7 0 A 0 0 5
I 1
I 2
I N 2
+ 2 4 V
I N 1
+ 2 4 V
Meet noise immunity requirements
Connect FE using a mounting screw
or a cable connection to the FE
connection latch (when mounting on
a non-conductive surface).
Ensure degree of protection
To ensure IP65/IP67 protection,
cover unused sockets with protective
caps.
Avoid damage to the electronics
Make sure you only supply the
sensors with the voltage U
S
provided
at the connection points.
Avoid polarity reversal
Avoid polarity reversal of the supply
voltages U
L
and U
S
in order to
prevent damage to the device.
Observe connection point
assignment
When connecting the sensors,
observe the assignment of the
connection points to the IN
process data (see "Process Data" on
page 7).

2736288

Mfr. #:
Manufacturer:
Phoenix Contact
Description:
I/O Modules FLM DI 8 M12 M12, 8 INPUTS
Lifecycle:
New from this manufacturer.
Delivery:
DHL FedEx Ups TNT EMS
Payment:
T/T Paypal Visa MoneyGram Western Union

Products related to this Datasheet